Description
TDK-Lambda RWS600B-24/RFO (also known as RWS600B24RFO) is a 600W single-output enclosed AC-DC power supply from the general-purpose RWS-B Series, where the -24 suffix denotes a 24VDC nominal output and /RFO equips the unit with Remote On/Off (/R) plus DC Good and Parallel Operation (/FO) signals alongside Remote Sense. Built around an active Power Factor Correction (PFC) front end (50–70 kHz) and a 190 kHz main switching stage with conservatively rated electrolytic capacitors, it accepts a universal 85–265VAC (47–63 Hz) or 120–330VDC input while withstanding 300VAC input surges for up to 5 seconds. The unit delivers 25A continuous at 24VDC (adjustable from 21.6 to 27.6VDC) with 150 mVp-p maximum ripple and noise, 96 mV line regulation, 192 mV load regulation, and up to 88.5% conversion efficiency at 230VAC.
Engineered for demanding industrial control cabinets, the RWS600B-24/RFO integrates constant-current overcurrent protection above 105% load and latch-off overvoltage protection at 115–140% nominal output, backed by 3,000VAC input-to-output galvanic isolation. Forced-air cooling via an internal fan enables full 600W operation from -20 °C to +50 °C (-4 °F to +122 °F), derating linearly to 50% load at +70 °C (+158 °F) at altitudes up to 3,000 meters. Housed in a rugged perforated metal chassis measuring 120 × 61 × 190 mm (4.72 × 2.40 × 7.48 in) with M5 output studs, an M3.5 covered AC barrier strip, and eight M4 chassis mounting holes, it carries UL 508, IEC/UL/CSA/EN 62368-1, CE, UKCA, SEMI F47, and Class B conducted/radiated EMI approvals with a 7-year manufacturer warranty.
Key Features
- High-Efficiency 600W 24VDC Output: Delivers 25A continuous (21.6–27.6VDC trim range) with 88.5% typical efficiency at 230VAC (85% at 115VAC), 150 mVp-p max ripple, and 10,000 µF capacitive load capability.
- Factory /RFO Control & Parallel Suite: Includes isolated Remote On/Off control, DC Good status signal, Remote Sense voltage-drop compensation, and active current-sharing parallel operation for N+1 redundancy or higher power.
- Universal AC/DC Input & Active PFC: Operates across 85–265VAC (90–264VAC safety certified) or 120–330VDC with 300VAC/5s surge immunity, 0.95/0.90 power factor, and IEC 61000-3-2 harmonic compliance.
- Industrial Protection & 3kVAC Isolation: Features constant-current overload protection (>105%), AC-recycle overvoltage protection (115–140%), 3,000VAC input-to-output isolation, and 2,000VAC input-to-ground dielectric withstand.
- Wide Thermal Envelope & Long-Life Design: Operates from -20 °C to +70 °C with full 600W output up to +50 °C via internal fan cooling, conservatively rated electrolytic capacitors, and 2.15M-hour Telcordia MTBF.
- Class B EMI & Global Industrial Approvals: Meets EN 55011/55032 Class B, FCC Class B, VCCI-B, and SEMI F47 line-dip standards without external filters, certified to UL 508 and IEC/UL/CSA/EN 62368-1.
Technical Specifications
| Manufacturer | TDK-Lambda |
|---|---|
| Manufacturer Part Number (MPN) | RWS600B-24/RFO |
| Alternate Part Number | RWS600B24RFO |
| Product Series | RWS50B–RWS600B Series |
| Product Category | PSU Mounting Brackets |
| Component Type | Enclosed AC-DC Switching Power Supply |
| Circuit Topology | Active PFC + High-Frequency Isolated PWM Converter |
| Nominal Output Voltage | 24 VDC |
| Output Voltage Adjustment Range | 21.6 to 27.6 VDC (via onboard potentiometer) |
| Rated Output Current | 25 A |
| Output Current Range | 0 to 25 A (No minimum load required) |
| Rated Output Power | 600 W |
| Output Ripple & Noise (Max) | 150 mVp-p |
| Line Regulation (Max) | 96 mV (±0.4%) |
| Load Regulation (Max) | 192 mV (±0.8%) |
| Maximum External Capacitive Load | 10,000 µF |
| Temperature Coefficient | ±0.02 %/°C |
| Hold-Up Time (at 110 VAC) | 20 ms (typical) |
| Hold-Up Time (at 220 VAC) | 20 ms (typical) |
| Operating AC Input Voltage Range | 85 to 265 VAC (Safety certified for 90 to 264 VAC) |
| Nominal AC Input Voltage Range | 100 to 240 VAC |
| Input Surge Voltage Withstand | 300 VAC for 5 seconds |
| Input Line Frequency | 47 to 63 Hz (Safety certified for 50 to 60 Hz) |
| DC Input Voltage Range | 120 to 330 VDC (Not safety certified for DC input) |
| Efficiency (at 115 VAC) | 85.0 % (typical) |
| Efficiency (at 230 VAC) | 88.5 % (typical) |
| AC Input Current (at 115 VAC) | 6.6 A (typical) |
| AC Input Current (at 230 VAC) | 3.6 A (typical) |
| Inrush Current (Cold Start at 200 VAC) | 40 A (typical) |
| Power Factor (PF at 100 VAC) | 0.95 (typical) |
| Power Factor (PF at 200 VAC) | 0.90 (typical) |
| Harmonic Current Compliance | Compliant with IEC 61000-3-2 |
| Main Switching Frequency | 190 kHz |
| PFC Stage Switching Frequency | 50 to 70 kHz |
| Overcurrent / Overload Protection (OLP) Threshold | Greater than 105 % of rated output current |
| Overcurrent / Overload Protection (OLP) Mode | Constant current limiting characteristics |
| Overvoltage Protection (OVP) Threshold | 115 to 140 % of nominal output voltage (27.6 to 33.6 VDC) |
| Overvoltage Protection (OVP) Mode | Latched shutdown (Cycle AC input line to reset) |
| Withstand Isolation Voltage (I/P to O/P) | 3,000 VAC (for 1 minute) |
| Withstand Isolation Voltage (I/P to FG / Case) | 2,000 VAC (for 1 minute) |
| Withstand Isolation Voltage (O/P to FG / Case) | 500 VAC (for 1 minute) |
| Earth Leakage Current | Less than 750 µA max (typically 175 µA at 115 VAC, 63 Hz) |
| Operating Ambient Temperature | -20 °C to +70 °C (-4 °F to +158 °F) |
| Full-Load Operating Temperature Limit | +50 °C (+122 °F) at 100% load (600 W) |
| High-Temperature Derating Rate | Linear derating above +50 °C at 2.5 %/°C down to 50% load (300 W) at +70 °C |
| Storage Temperature Range | -30 °C to +75 °C (-22 °F to +167 °F) |
| Operating Relative Humidity | 30 % to 90 % RH (non-condensing) |
| Storage Relative Humidity | 10 % to 90 % RH (non-condensing) |
| Maximum Operating Altitude | 3,000 m (9,842 ft) |
| Vibration Resistance (Non-Operating) | 10 to 55 Hz (1 min sweep), 19.6 m/s² (2 G) constant along X, Y, Z axes for 1 hour each |
| Shock Resistance (Non-Operating) | Less than 196 m/s² (20 G), 11 ms half-sine, ±X, ±Y, ±Z 3 times each |
| MTBF (Telcordia SR-332 Issue 3) | 2,157,340 hours (at +25 °C ambient, full load) |
| North American Safety Certifications | UL 508 (Industrial Control Equipment), UL 62368-1, CSA C22.2 No. 62368-1 |
| International & European Safety Certifications | IEC 62368-1, EN 62368-1, CE Mark, UKCA Mark |
| Conducted & Radiated EMI Emissions | EN 55011 Class B, EN 55032 Class B, FCC Part 15 Class B, VCCI Class B |
| ESD Immunity (EN 61000-4-2) | ±8 kV Air Discharge, ±4 kV Contact Discharge (Performance Criteria B) |
| Radiated RF Immunity (EN 61000-4-3) | 10 V/m (80 MHz–1 GHz), 3 V/m (1.4–2.0 GHz), 1 V/m (2.0–2.7 GHz) (Criteria A) |
| EFT / Burst Immunity (EN 61000-4-4) | ±2 kV (Performance Criteria B) |
| Surge Immunity (EN 61000-4-5) | ±2 kV Normal Mode (Line-to-Line), ±4 kV Common Mode (Line-to-Ground) (Criteria B) |
| Conducted RF Immunity (EN 61000-4-6) | 10 Vrms (Performance Criteria A) |
| Power Frequency Magnetic Field (EN 61000-4-8) | 30 A/m (Performance Criteria A) |
| Voltage Dips & Interruptions (EN 61000-4-11) | 30% dip 500ms (Criteria B), 60% dip 10ms (Criteria B), 100% dip 20ms (Criteria A), 100% dip 5000ms (Criteria B) |
| Semiconductor Voltage Sag Immunity | SEMI F47 Compliant (at input voltages greater than 200 VAC) |
| Control & Monitoring Signals (/RFO Option) | Remote On/Off (/R), DC Good Signal, Parallel Operation Current Share (/FO), and Remote Sense |
| Input Terminal Configuration | 3-Pin Barrier Terminal Strip with M3.5 Screws & Protective Cover (L, N, FG) |
| Output Terminal Configuration | 4-Stud Busbar Terminal Block with M5 Screws (+V, -V) |
| Cooling Method | Forced-Air Cooling via Built-in Internal DC Fan (Airflow from terminal side toward rear) |
| Mounting Style | Chassis Mount via 8× M4 Countersunk Bottom Mounting Holes (6 mm max screw penetration) |
| Overall Width (W) | 120 mm (4.72 in) |
| Overall Height (H) | 61 mm (2.40 in) |
| Overall Length / Depth (L/D) | 190 mm (7.48 in) |
| Overall Dimensions (L × W × H) | 190 × 120 × 61 mm (7.48 × 4.72 × 2.40 in) |
| Net Weight | 1,600 g (1.60 kg / 3.53 lbs) |
| Enclosure Material | Perforated Metal Chassis |
| Manufacturer Warranty | 7 Years ( & EMEA) / 5 Years (Other Regions) |
Industrial Applications & Compatible Systems
TDK-Lambda RWS600B-24/RFO delivers regulated 600W 24VDC bulk power with built-in parallel sharing, DC Good telemetry, and remote shutdown for demanding industrial systems:
- UL 508A Industrial Control Panels & PLC Racks: Powers high-density 24VDC distributed I/O, safety relays, HMI panels, and industrial Ethernet switches where UL 508 listing and Class B EMI compliance simplify panel certification.
- Automated Machinery, Robotics & Actuator Banks: Supplies high-current 24VDC rails for solenoid valve manifolds, stepper drives, pneumatic controllers, and 24V brushless DC conveyor motors with constant-current overload protection.
- Semiconductor Fabrication & Wafer Handling Tools: Meets SEMI F47 line-dip immunity (>200VAC) and Class B conducted/radiated noise limits for sensitive metrology, vacuum valves, and robotic wafer handlers.
- Redundant N+1 & High-Power Parallel Systems: Utilizes the integrated /FO current-sharing bus and DC Good status outputs to parallel multiple 600W units for 1,200W+ loads or fault-tolerant N+1 power architectures.
Installation, Thermal Management & MRO Guidelines
Installation & Engineering Guidelines: Mount the chassis securely using the eight bottom M4 threaded holes while strictly limiting mounting screw penetration to 6 mm maximum to avoid contacting internal PCB clearances. Maintain unobstructed airflow around the internal fan intake and exhaust vents; full 600W output is supported up to +50 °C (+122 °F), above which load current must be linearly derated by 2.5 %/°C to 50% (12.5A / 300W) at +70 °C (+158 °F). Because the cold-start inrush current reaches 40A typical at 200VAC, protect the AC branch circuit with a Type-C or Type-D 10A–16A miniature circuit breaker (MCB) or slow-blow fuse. When utilizing Remote Sense over long 24VDC feeder runs, route twisted-pair sense leads directly to the load terminals to compensate for cable voltage drop without exceeding the 27.6VDC upper trim limit.