Description
TDK-Lambda DPP960-24-3 (also known as DPP960243) is a high-power 960W three-phase DIN rail AC-DC power supply engineered within the rugged DPP120–960 series. The part number nomenclature identifies the 960W power class (DPP960), 24VDC nominal regulated output (-24), and three-phase AC input architecture (-3). Accepting a wide 340 to 575VAC three-phase input (47–63Hz) with passive PFC compliant to EN61000-3-2, it delivers a continuous 40A output adjustable from 22.5 to 28.5VDC via a front-panel potentiometer. Operating at a 52kHz switching frequency, the unit achieves 92% typical efficiency, holds output ripple and noise to 80mV peak-to-peak (20MHz bandwidth), and maintains ±1% line and load regulation in standalone mode.
Engineered for demanding industrial automation environments, the DPP960-24-3 incorporates active current sharing for parallel operation of up to two units (up to 90% load), a 0.3A normally open DC Good relay contact, and dual Green/Red status LEDs. Comprehensive protection circuits include 110–130% overcurrent protection, 30–33V overvoltage protection, and auto-recovery overtemperature protection, backed by 3kVAC input-to-output and 1.5kVAC input-to-ground galvanic isolation. Housed in a convection-cooled metal enclosure measuring 275.8 × 126.2 × 111.9 mm (10.86 × 4.97 × 4.41 in) for tool-free TS35/7.5 or TS35/15 DIN rail mounting, it operates from -40°C to +71°C (full load up to +61°C) and carries UL508 Listed, UL60950-1, EN60950-1, and CE certifications.
Key Features
- High-Power 960W 24VDC Output: Delivers 40A continuous current across an adjustable 22.5 to 28.5VDC range with 92% typical efficiency and low 80mV peak-to-peak ripple and noise.
- Wide 340–575VAC Three-Phase Input: Supports global 380V, 400V, and 480VAC three-phase grids at 47–63Hz, plus bi-phase operation with linear output derating to 75% load.
- Parallel Current-Share Capability: Enables parallel connection of up to two units (up to 90% combined load) with integrated current sharing to expand system power capacity.
- Integrated DC Good Relay & Status LEDs: Features a 0.3A normally open DC Good relay closing above 17.6–19.4V alongside green power-on and red DC output-low LED indicators.
- Wide -40°C to +71°C Operating Range: Supports cold-start operation down to -40°C (-40°F) and full 960W convection-cooled output up to +61°C (+141.8°F) without external fans.
- Comprehensive Industrial Protections: Safeguards downstream loads with 110–130% overcurrent limiting, 30–33V overvoltage shutdown, auto-recovery overtemperature protection, and 3kVAC input-to-output isolation.
- UL508 Listed & Class B EMC Compliance: Certified to UL508, UL/EN60950-1, and CE while meeting EN55022 Class B conducted/radiated emissions and full IEC 61000-4 industrial immunity.
Technical Specifications
| Manufacturer | TDK-Lambda |
|---|---|
| Manufacturer Part Number (MPN) | DPP960-24-3 |
| Alternate Part Number | DPP960243 |
| Product Series | DPP120 – 960 Series |
| Product Category | Three-Phase DIN Rail |
| Component Type | AC-DC Industrial DIN Rail Power Supply |
| Input Phase Configuration | Three-Phase (Bi-phase permissible at 75% max load) |
| Rated Output Power | 960 W |
| Nominal Output Voltage | 24 VDC |
| Output Voltage Adjustment Range | 22.5 to 28.5 VDC |
| Rated Output Current | 40 A |
| Output Voltage Accuracy | -0%, +1% of Nominal |
| Line Regulation | ±1% |
| Load Regulation (Single Unit Mode) | ±1% |
| Load Regulation (Parallel Mode) | ±5% |
| Output Ripple and Noise (20 MHz BW) | 80 mV peak-to-peak |
| Hold-Up Time (at 380–480 VAC) | > 15 ms |
| Parallel Operation Capability | Up to 2 units (up to 90% load, Current Share) |
| AC Input Voltage Range | 340 to 575 VAC (Three-Phase) |
| Bi-Phase Input Operation | Permissible (Output load must be derated to 75%) |
| Input Frequency Range | 47 to 63 Hz |
| Efficiency (Typical) | 92% |
| AC Input Current (Typical at 400 VAC) | 1.72 A |
| Inrush Current (Cold Start at 380–480 VAC, Typ.) | 30 A |
| Power Factor (Typical) | 0.8 (Passive PFC) |
| Switching Frequency | 52 kHz |
| Overcurrent Protection (OCP) Threshold | 110% to 130% of rated current (Typical) |
| Overvoltage Protection (OVP) Threshold | 30 to 33 VDC |
| Overtemperature Protection (OTP) Mode | Yes, Auto-Recovery |
| Withstand Isolation Voltage (I/P to O/P) | 3 kVAC (1 minute) |
| Withstand Isolation Voltage (I/P to Ground / FG) | 1.5 kVAC (1 minute) |
| Isolation Resistance (O/P to Ground at 500 VDC) | > 100 MΩ (at 25 °C & 70% RH) |
| Operating Ambient Temperature Range | -40 °C to +71 °C (-40 °F to +159.8 °F) |
| Full-Load Operating Temperature Limit | +61 °C (+141.8 °F) |
| High-Temperature Derating Rate | Linear derating 3.5%/°C from +61 °C to +71 °C (+141.8 °F to +159.8 °F) |
| Storage Temperature Range | -40 °C to +85 °C (-40 °F to +185 °F) |
| Operating Humidity (Non-Condensing) | 20% to 95% RH |
| Vibration Resistance | IEC 60068-2-6 (10–500 Hz, 2G on X, Y & Z axes) |
| Shock Resistance | IEC 60068-2-27 (Half sinewave, 4G, 22 ms, 3 times each face) |
| MTBF (Bellcore Issue 6 at 40 °C, GB) | 352,000 hours |
| Safety Agency Approvals (North America) | UL508 Listed, UL60950-1 |
| Safety Agency Approvals (Europe / International) | EN60950-1, CE |
| Conducted & Radiated EMI Standard | EN55022 Class B |
| Harmonic Current Emissions Standard | EN61000-3-2 (Passive PFC compliant) |
| ESD Immunity Standard | IEC 61000-4-2 |
| Radiated RF Immunity Standard | IEC 61000-4-3 |
| EFT / Burst Immunity Standard | IEC 61000-4-4 |
| Surge Immunity Standard | IEC 61000-4-5 |
| Conducted RF Immunity Standard | IEC 61000-4-6 |
| Power Frequency Magnetic Field Immunity | IEC 61000-4-8 |
| Voltage Dips & Interruptions Immunity | IEC 61000-4-11 |
| DC Good Relay Output | 0.3 A rated normally open (NO) relay contacts; closes when output > 17.6–19.4 VDC |
| Front-Panel Status Indicators | Green LED = Power On; Red LED = DC Output Low |
| Cooling Method | Natural Convection |
| Recommended Installation Clearance | 25 mm (0.98 in) on all sides |
| Mounting Style | Tool-free snap-on DIN rail (TS35/7.5 or TS35/15) |
| Enclosure Material | Metal |
| Overall Width (W) | 275.8 mm (10.86 in) |
| Overall Height (H) | 126.2 mm (4.97 in) |
| Overall Depth (D) | 111.9 mm (4.41 in) |
| Overall Dimensions (W × H × D) | 275.8 × 126.2 × 111.9 mm (10.86 × 4.97 × 4.41 in) |
| Net Weight (Typical) | 3,400 g (3.40 kg / 7.50 lbs) |
| Manufacturer Warranty | 3 Years |
Industrial Applications & Compatible Systems
TDK-Lambda DPP960-24-3 provides bulk 24VDC industrial control power directly from three-phase 380–480VAC mains across heavy manufacturing and process facilities:
- Industrial Motor Control Centers (MCCs): Powers high-current 24VDC contactor coils, brake releases, soft-starter control logic, and variable frequency drive (VFD) auxiliary I/O boards.
- Factory & Automotive Automation Lines: Supplies centralized 40A bulk DC power for multi-rack PLCs, distributed EtherCAT/PROFINET I/O islands, pneumatic valve manifolds, and robotic cell safety relays.
- Chemical Processing & Heavy Process Control: Operates reliably in harsh wide-temperature cabinets (-40°C to +71°C) feeding transmitters, actuators, and process controllers with integrated DC Good relay fault monitoring.
- Burn-In, Test & Measurement Racks: Delivers low-ripple (80mV pk-pk) regulated 24VDC power and scalable parallel current-sharing up to 1,728W (two units at 90% load) for automated production test benches.
Installation, Thermal Management & MRO Guidelines
Installation & Engineering Guidelines: Mount the DPP960-24-3 vertically onto standard TS35/7.5 or TS35/15 DIN rails and maintain a minimum 25 mm (0.98 in) unobstructed airflow clearance on all sides to ensure proper natural convection cooling. For ambient cabinet temperatures exceeding +61°C (+141.8°F), linearly derate the output load by 3.5%/°C up to +71°C (+159.8°F), and apply a 75% maximum load cap if operating from a bi-phase AC input. When wiring two units in parallel for higher current capacity, configure current sharing and limit combined continuous loading to 90% of total rated capacity while sizing upstream three-phase circuit breakers to accommodate the 30A cold-start inrush current.