DPP960-24-3 TDK-Lambda 960W 24VDC 3-Phase DIN Rail PSU

$620.23

TDK-Lambda DPP960-24-3 (DPP960243) 960W 24VDC 40A 3-phase DIN rail power supply, 340-575VAC input, 92% efficiency, featuring current share, DC Good relay, and UL508.

SKU: DPP960-24-3 Category: Brand:

Description

TDK-Lambda DPP960-24-3 (also known as DPP960243) is a high-power 960W three-phase DIN rail AC-DC power supply engineered within the rugged DPP120–960 series. The part number nomenclature identifies the 960W power class (DPP960), 24VDC nominal regulated output (-24), and three-phase AC input architecture (-3). Accepting a wide 340 to 575VAC three-phase input (47–63Hz) with passive PFC compliant to EN61000-3-2, it delivers a continuous 40A output adjustable from 22.5 to 28.5VDC via a front-panel potentiometer. Operating at a 52kHz switching frequency, the unit achieves 92% typical efficiency, holds output ripple and noise to 80mV peak-to-peak (20MHz bandwidth), and maintains ±1% line and load regulation in standalone mode.

Engineered for demanding industrial automation environments, the DPP960-24-3 incorporates active current sharing for parallel operation of up to two units (up to 90% load), a 0.3A normally open DC Good relay contact, and dual Green/Red status LEDs. Comprehensive protection circuits include 110–130% overcurrent protection, 30–33V overvoltage protection, and auto-recovery overtemperature protection, backed by 3kVAC input-to-output and 1.5kVAC input-to-ground galvanic isolation. Housed in a convection-cooled metal enclosure measuring 275.8 × 126.2 × 111.9 mm (10.86 × 4.97 × 4.41 in) for tool-free TS35/7.5 or TS35/15 DIN rail mounting, it operates from -40°C to +71°C (full load up to +61°C) and carries UL508 Listed, UL60950-1, EN60950-1, and CE certifications.

Key Features

  • High-Power 960W 24VDC Output: Delivers 40A continuous current across an adjustable 22.5 to 28.5VDC range with 92% typical efficiency and low 80mV peak-to-peak ripple and noise.
  • Wide 340–575VAC Three-Phase Input: Supports global 380V, 400V, and 480VAC three-phase grids at 47–63Hz, plus bi-phase operation with linear output derating to 75% load.
  • Parallel Current-Share Capability: Enables parallel connection of up to two units (up to 90% combined load) with integrated current sharing to expand system power capacity.
  • Integrated DC Good Relay & Status LEDs: Features a 0.3A normally open DC Good relay closing above 17.6–19.4V alongside green power-on and red DC output-low LED indicators.
  • Wide -40°C to +71°C Operating Range: Supports cold-start operation down to -40°C (-40°F) and full 960W convection-cooled output up to +61°C (+141.8°F) without external fans.
  • Comprehensive Industrial Protections: Safeguards downstream loads with 110–130% overcurrent limiting, 30–33V overvoltage shutdown, auto-recovery overtemperature protection, and 3kVAC input-to-output isolation.
  • UL508 Listed & Class B EMC Compliance: Certified to UL508, UL/EN60950-1, and CE while meeting EN55022 Class B conducted/radiated emissions and full IEC 61000-4 industrial immunity.

Technical Specifications

Manufacturer TDK-Lambda
Manufacturer Part Number (MPN) DPP960-24-3
Alternate Part Number DPP960243
Product Series DPP120 – 960 Series
Product Category Three-Phase DIN Rail
Component Type AC-DC Industrial DIN Rail Power Supply
Input Phase Configuration Three-Phase (Bi-phase permissible at 75% max load)
Rated Output Power 960 W
Nominal Output Voltage 24 VDC
Output Voltage Adjustment Range 22.5 to 28.5 VDC
Rated Output Current 40 A
Output Voltage Accuracy -0%, +1% of Nominal
Line Regulation ±1%
Load Regulation (Single Unit Mode) ±1%
Load Regulation (Parallel Mode) ±5%
Output Ripple and Noise (20 MHz BW) 80 mV peak-to-peak
Hold-Up Time (at 380–480 VAC) > 15 ms
Parallel Operation Capability Up to 2 units (up to 90% load, Current Share)
AC Input Voltage Range 340 to 575 VAC (Three-Phase)
Bi-Phase Input Operation Permissible (Output load must be derated to 75%)
Input Frequency Range 47 to 63 Hz
Efficiency (Typical) 92%
AC Input Current (Typical at 400 VAC) 1.72 A
Inrush Current (Cold Start at 380–480 VAC, Typ.) 30 A
Power Factor (Typical) 0.8 (Passive PFC)
Switching Frequency 52 kHz
Overcurrent Protection (OCP) Threshold 110% to 130% of rated current (Typical)
Overvoltage Protection (OVP) Threshold 30 to 33 VDC
Overtemperature Protection (OTP) Mode Yes, Auto-Recovery
Withstand Isolation Voltage (I/P to O/P) 3 kVAC (1 minute)
Withstand Isolation Voltage (I/P to Ground / FG) 1.5 kVAC (1 minute)
Isolation Resistance (O/P to Ground at 500 VDC) > 100 MΩ (at 25 °C & 70% RH)
Operating Ambient Temperature Range -40 °C to +71 °C (-40 °F to +159.8 °F)
Full-Load Operating Temperature Limit +61 °C (+141.8 °F)
High-Temperature Derating Rate Linear derating 3.5%/°C from +61 °C to +71 °C (+141.8 °F to +159.8 °F)
Storage Temperature Range -40 °C to +85 °C (-40 °F to +185 °F)
Operating Humidity (Non-Condensing) 20% to 95% RH
Vibration Resistance IEC 60068-2-6 (10–500 Hz, 2G on X, Y & Z axes)
Shock Resistance IEC 60068-2-27 (Half sinewave, 4G, 22 ms, 3 times each face)
MTBF (Bellcore Issue 6 at 40 °C, GB) 352,000 hours
Safety Agency Approvals (North America) UL508 Listed, UL60950-1
Safety Agency Approvals (Europe / International) EN60950-1, CE
Conducted & Radiated EMI Standard EN55022 Class B
Harmonic Current Emissions Standard EN61000-3-2 (Passive PFC compliant)
ESD Immunity Standard IEC 61000-4-2
Radiated RF Immunity Standard IEC 61000-4-3
EFT / Burst Immunity Standard IEC 61000-4-4
Surge Immunity Standard IEC 61000-4-5
Conducted RF Immunity Standard IEC 61000-4-6
Power Frequency Magnetic Field Immunity IEC 61000-4-8
Voltage Dips & Interruptions Immunity IEC 61000-4-11
DC Good Relay Output 0.3 A rated normally open (NO) relay contacts; closes when output > 17.6–19.4 VDC
Front-Panel Status Indicators Green LED = Power On; Red LED = DC Output Low
Cooling Method Natural Convection
Recommended Installation Clearance 25 mm (0.98 in) on all sides
Mounting Style Tool-free snap-on DIN rail (TS35/7.5 or TS35/15)
Enclosure Material Metal
Overall Width (W) 275.8 mm (10.86 in)
Overall Height (H) 126.2 mm (4.97 in)
Overall Depth (D) 111.9 mm (4.41 in)
Overall Dimensions (W × H × D) 275.8 × 126.2 × 111.9 mm (10.86 × 4.97 × 4.41 in)
Net Weight (Typical) 3,400 g (3.40 kg / 7.50 lbs)
Manufacturer Warranty 3 Years

Industrial Applications & Compatible Systems

TDK-Lambda DPP960-24-3 provides bulk 24VDC industrial control power directly from three-phase 380–480VAC mains across heavy manufacturing and process facilities:

  • Industrial Motor Control Centers (MCCs): Powers high-current 24VDC contactor coils, brake releases, soft-starter control logic, and variable frequency drive (VFD) auxiliary I/O boards.
  • Factory & Automotive Automation Lines: Supplies centralized 40A bulk DC power for multi-rack PLCs, distributed EtherCAT/PROFINET I/O islands, pneumatic valve manifolds, and robotic cell safety relays.
  • Chemical Processing & Heavy Process Control: Operates reliably in harsh wide-temperature cabinets (-40°C to +71°C) feeding transmitters, actuators, and process controllers with integrated DC Good relay fault monitoring.
  • Burn-In, Test & Measurement Racks: Delivers low-ripple (80mV pk-pk) regulated 24VDC power and scalable parallel current-sharing up to 1,728W (two units at 90% load) for automated production test benches.

Installation, Thermal Management & MRO Guidelines

Installation & Engineering Guidelines: Mount the DPP960-24-3 vertically onto standard TS35/7.5 or TS35/15 DIN rails and maintain a minimum 25 mm (0.98 in) unobstructed airflow clearance on all sides to ensure proper natural convection cooling. For ambient cabinet temperatures exceeding +61°C (+141.8°F), linearly derate the output load by 3.5%/°C up to +71°C (+159.8°F), and apply a 75% maximum load cap if operating from a bi-phase AC input. When wiring two units in parallel for higher current capacity, configure current sharing and limit combined continuous loading to 90% of total rated capacity while sizing upstream three-phase circuit breakers to accommodate the 30A cold-start inrush current.