TDK-Lambda DRB240-24-3-A0 (also known as DRB240243A0) is an industrial three-phase DIN rail AC-DC power supply from the DRB120-3 to DRB960-3 series, where the -3 denotes three-phase operation and the -A0 suffix specifies screw-clamp terminal blocks with standard uncoated PCBs. Accepting a wide nominal input of 380 to 500 VAC three-phase (342 to 575 VAC maximum continuous range) as well as 450 to 810 VDC, it delivers a tightly regulated 24 VDC output (adjustable from 22.5 to 29 VDC) at 10 A continuous (240 W) and up to 15 A (360 W, 150% boost) for 60 seconds to start heavy capacitive or inductive loads. Operating with a variable 50 to 135 kHz switching topology, it achieves 93.1% / 93.2% efficiency at 400 / 500 VAC, 0.05% line regulation, 0.2% single-unit load regulation, and 40 mV ripple and noise at room-to-elevated ambient temperatures.
Engineered for harsh automation cabinets, the unit incorporates >142% constant-current and hiccup overcurrent protection, auto-recovery overvoltage protection below 32.7 V, auto-recovery overtemperature protection, a DC Good relay contact, remote on/off inhibit input, and a front-panel DIP switch for parallel droop-mode current sharing. Reinforced three-zone galvanic isolation provides 6,400 VAC input-to-output, 2,210 VAC input-to-ground, and 1,390 VAC output-to-ground withstand ratings. Housed in a slim 55 × 129 × 138.2 mm (2.17 × 5.08 × 5.44 in) convection-cooled aluminum enclosure for TS-35/7.5 or TS-35/15 DIN rails, it operates at full load from -25 °C to +55 °C (-40 °C cold start-up) with linear derating up to +70 °C and holds IEC/EN/UL/CSA 61010-1, 61010-2-201, and 62368-1 approvals.
Key Features
- Wide Three-Phase AC & High-Voltage DC Input: Operates across 380 to 500 VAC nominal three-phase (342 to 575 VAC maximum, 620 VAC 5 s surge) and 450 to 810 VDC with 240 W single-phase dropped-phase capability.
- 150% Peak Boost Power for 60 Seconds: Delivers 10 A (240 W) continuous and 15 A (360 W) peak output for up to 60 seconds into 20,000 µF max capacitive loads without nuisance breaker tripping.
- High Conversion Efficiency & Low Standby Draw: Achieves 93.1% efficiency at 400 VAC and 93.2% at 500 VAC with 1.6 W to 1.9 W maximum no-load power consumption and 10-year typical electrolytic capacitor life.
- Reinforced 6,400 VAC Input-to-Output Isolation: Provides 6,400 VAC (1 min) input-to-output, 2,210 VAC input-to-ground, and 1,390 VAC output-to-ground/signal dielectric strength with under 1 mA leakage at 575 VAC.
- Built-In Control Signals & Parallel Droop Mode: Includes a >95% DC Good relay contact, remote on/off enable (<4 V or closed contact), green DC OK LED, and front DIP switch for N+1 or capacity paralleling.
- Industrial Immunity & Global Safety Certifications: Certified to IEC/EN/UL/CSA 61010-1, 61010-2-201, and 62368-1 with Class B EN 55011 emissions and EN 61000-4-2 through -4-11 industrial EMC immunity.
- Ultra-Slim 55 mm Aluminum DIN Rail Chassis: Measures 55 × 129 × 138.2 mm (2.17 × 5.08 × 5.44 in) at 780 g, supporting -40 °C cold start-up and full-load convection cooling up to +55 °C.
Technical Specifications
| Manufacturer | TDK-Lambda |
|---|---|
| Manufacturer Part Number (MPN) | DRB240-24-3-A0 |
| Alternate Part Number | DRB240243A0 |
| Product Series | DRB120-3 – DRB960-3 Series (DRB240-3) |
| Product Category | Redundancy Modules |
| Component Type | Three-Phase AC-DC Industrial DIN Rail Power Supply |
| Termination & Coating Option Code | -A0 (Screw Terminals, Standard Uncoated PCB) |
| Circuit Topology | Variable-Frequency Switching Converter (50–135 kHz) with Parallel Droop Mode |
| Nominal Output Voltage | 24 VDC |
| Output Voltage Adjustment Range | 22.5 to 29 VDC (via Front-Panel Trimmer) |
| Output Voltage Tolerance | ±3% Maximum |
| Rated Continuous Output Current | 10 A |
| Peak Boost Output Current | 15 A (for up to 60 seconds) |
| Rated Continuous Output Power | 240 W |
| Peak Boost Output Power | 360 W (150% Boost for up to 60 seconds) |
| Dropped-Phase Output Power | 240 W (Continuous Operation on 2 Phases) |
| Minimum Load Requirement | No Minimum Load Required (0 A) |
| Maximum Capacitive Load | 20,000 µF |
| Output Ripple & Noise (+25 to +70 °C Ambient) | 40 mVp-p Maximum |
| Output Ripple & Noise (-25 to | 120 mVp-p Maximum |
| Line Regulation | 0.05% |
| Load Regulation (Single-Unit / Non-Parallel Mode) | 0.2% |
| Load Regulation (Parallel Droop Mode) | 2.7% |
| Hold-Up Time (Minimum at 400 VAC) | 20 ms |
| Hold-Up Time (Minimum at 500 VAC) | 40 ms |
| Nominal AC Input Voltage Range | 3-Phase 380 to 500 VAC (Safety Certified Range) |
| Maximum Operating AC Input Voltage Range | 3-Phase 342 to 575 VAC |
| Input Surge Voltage Withstand | 620 VAC (for 5 seconds) |
| DC Input Voltage Range | 450 to 810 VDC (External DC Fuse Required) |
| Input Frequency Range | 47 to 63 Hz |
| AC Input Current (Per Phase Maximum) | 0.8 A max |
| DC Input Current (Maximum) | 0.8 A max |
| Inrush Current (Typical Cold Start at 400 VAC) | 25 A typical |
| Inrush Current (Typical Cold Start at 500 VAC) | 30 A typical |
| Efficiency (Minimum at 400 VAC, 100% Load) | 93.1% |
| Efficiency (Minimum at 500 VAC, 100% Load) | 93.2% |
| Average Efficiency (at 400 VAC, EU 2019/1782) | 92.8% (25%, 50%, 75%, 100% Load Average) |
| Average Efficiency (at 500 VAC, EU 2019/1782) | 92.3% (25%, 50%, 75%, 100% Load Average) |
| Power Factor (Typical at 400 / 500 VAC) | 0.6 typical |
| No-Load Power Consumption (Standby at 400 VAC) | 1.6 W maximum |
| No-Load Power Consumption (Standby at 500 VAC) | 1.9 W maximum |
| Internal Switching Frequency | 50 to 135 kHz (Variable with Line and Load) |
| Overcurrent Protection (OCP / OLP) Threshold | >142% of Rated Output Current |
| Overcurrent Protection (OCP / OLP) Mode | Constant Current Limiting & Hiccup Mode (Auto-Recovery) |
| Overvoltage Protection (OVP) Threshold | <32.7 VDC |
| Overvoltage Protection (OVP) Mode | Auto-Recovery |
| Overtemperature Protection (OTP) Mode | Built-In Thermal Shutdown with Auto-Recovery |
| Withstand Isolation Voltage (Input to Output) | 6,400 VAC (1 Minute) |
| Withstand Isolation Voltage (Input to Ground / PE) | 2,210 VAC (1 Minute) |
| Withstand Isolation Voltage (Output to Ground & Signals) | 1,390 VAC (1 Minute) |
| Earth Leakage Current (at 575 VAC, 60 Hz) | <1 mA |
| Touch Current (at 575 VAC, 60 Hz) | <50 µA |
| Operating Ambient Temperature Range | -25 °C to +70 °C (-13 °F to +158 °F) |
| Cold Start-Up Temperature Capability | -40 °C (-40 °F) |
| Full-Load Operating Temperature Limit | +55 °C (+131 °F) at 100% Load |
| High-Temperature Derating Rate (Above +55 °C) | 2.4 W/°C Linear Derating (+55 °C to +70 °C) |
| Storage Temperature Range | -40 °C to +85 °C (-40 °F to +185 °F) |
| Operating & Storage Humidity | 95% RH Maximum (Non-Condensing) |
| Operating Altitude | 3,000 m Nominal (Up to 6,000 m Maximum without UL Certification) |
| Vibration Resistance (Non-Operating on DIN Rail) | IEC 60068-2-6: 2g, 10 to 500 Hz, 1 Hour per Axis (X, Y, Z) |
| Shock Resistance (Non-Operating on DIN Rail) | IEC 60068-2-27: 30g, 11 ms ±5 ms, 3 Shocks per Axis |
| Expected Electrolytic Capacitor Field Life | 10 Years Typical (Conservatively Rated) |
| MTBF (Telcordia SR-332 Issue 4) | 1,100,000 Hours (at +25 °C Ambient, Full Load) |
| Safety Certifications & Approvals | IEC/EN/UL/CSA 61010-1, IEC/EN/UL/CSA 61010-2-201, IEC/EN/UL/CSA 62368-1, CE, UKCA |
| Additional Design Compliance Standards | Designed to meet IEC 60950-1, EN 60204-1, IEC/EN 62477-1, IEC/EN 61204-7, IEC/EN 61558-2-16, IEC 60068-2-60, IEC 60068-2-11 |
| EMC Conducted & Radiated Emissions | EN 55011 Class B, CISPR 11 Class B |
| EMC Harmonic Current Emissions | EN 61000-3-2 Class A |
| EMC Electrostatic Discharge (ESD) Immunity | EN 61000-4-2: ±4 kV Contact, ±8 kV Air Discharge (Criteria A) |
| EMC Radiated RF Susceptibility | EN 61000-4-3: 10 V/m (80 MHz–1 GHz), 3 V/m (1.4–2 GHz), 1 V/m (2–2.7 GHz) (Criteria A) |
| EMC Electrical Fast Transient (EFT / Burst) | EN 61000-4-4: Input ±4 kV (5 kHz), Output ±2 kV (5 kHz), Signal ±2 kV (5 kHz) (Criteria A) |
| EMC Surge Immunity | EN 61000-4-5: Input L-L ±2 kV, Input L-PE ±4 kV; Output L-L ±0.5 kV, Output L-PE ±1 kV (Criteria A) |
| EMC Conducted RF Susceptibility | EN 61000-4-6: 10 Vrms (150 kHz to 80 MHz) (Criteria A) |
| EMC Power Frequency Magnetic Field Immunity | EN 61000-4-8: 30 A/m at 50 Hz, 60 s per Axis (X, Y, Z) (Criteria A) |
| EMC Voltage Dips & Interruptions Immunity | EN 61000-4-11 / EN 61000-4-34 (400 VAC, 50 Hz): 70% for 500 ms (Crit A), 40% for 200 ms (Crit A), 0% for 20 ms (Crit A), 0% for 5000 ms (Crit C) |
| DC Good Status Relay Output | Closed Contact Relay when Output Voltage >95% of Nominal |
| Remote On/Off Control Input | Closed Contact or <4 VDC Enables Output (INHIBIT +/-) |
| Parallel Operation Control | Front-Panel DIP Switch for Parallel Droop Mode Current Sharing |
| Visual Status Indicator | Front-Panel Green LED (DC OK) |
| Input Terminal Pinout | L1, L2, L3, PE (Earth) Screw Terminals |
| Output & Signal Terminal Pinout | +V, +V, -V, -V, DC OK Relay (2 Pins), INHIBIT +/- Screw Terminals |
| Cooling Method | Free-Air Natural Convection |
| Mounting Style & DIN Rail Compatibility | Standard TS-35/7.5 or TS-35/15 DIN Rail Mount |
| Overall Width (W) | 55 mm (2.17 in) |
| Overall Height (H) | 129 mm (5.08 in) |
| Overall Depth (D) | 138.2 mm (5.44 in) |
| Overall Dimensions (W × H × D) | 55 × 129 × 138.2 mm (2.17 × 5.08 × 5.44 in) |
| Net Weight | 780 g (1.72 lbs / 27.51 oz) |
| Enclosure Material | Aluminum Housing |
| Manufacturer Warranty | 3 Years |
Industrial Applications & Compatible Systems
TDK-Lambda DRB240-24-3-A0 provides high-efficiency, three-phase 24 VDC bus power for space-constrained industrial machinery and automated control cabinets:
- Industrial Control Cabinets & PLC/SCADA Racks: Powers programmable logic controllers, distributed I/O modules, HMI panels, and industrial Ethernet switches directly from 400 VAC or 480 VAC three-phase mains without requiring a step-down control transformer.
- Packaging, Material Handling & Conveyor Automation: Supplies 150% peak boost power (15 A / 360 W for up to 60 seconds) to energize DC solenoid valves, pneumatic manifolds, electromagnetic brakes, and stepper/brushless DC drives.
- Process Control & Chemical/Water Treatment Instrumentation: Delivers low-ripple (40 mVp-p) 24 VDC power with 6,400 VAC input-to-output isolation and EN 55011 Class B EMC compliance for sensitive analog transmitters, flow meters, and actuator loops.
- Redundant & High-Availability 24 VDC Bus Systems: Parallels multiple units via the front-panel droop-mode DIP switch or pairs with TDK-Lambda DRM40 redundancy modules and DBM20 buffer modules for fault-tolerant N+1 machine power.
Installation, Thermal Management & MRO Guidelines
Installation & Engineering Guidelines: Mount the DRB240-24-3-A0 vertically onto a standard TS-35/7.5 or TS-35/15 DIN rail with unobstructed top and bottom ventilation clearances so natural convection cooling maintains full 240 W output up to +55 °C (+131 °F); above +55 °C, linearly derate output power by 2.4 W/°C up to +70 °C (maximum 204 W at +70 °C). Because cold-start inrush current is limited to 25 A at 400 VAC and 30 A at 500 VAC with 0.8 A maximum steady-state phase current, standard 3-pole C-curve or D-curve miniature circuit breakers can be used without nuisance tripping. When operating from a 450 to 810 VDC bus, install an appropriately rated external DC fuse in series with the input lines, and set the front-panel DIP switch to parallel mode before wiring multiple units together.