2907719 Phoenix Contact 24VDC 40A DIN Rail Redundancy Module

$148.66

Phoenix Contact 2907719 12-24VDC 2x20A/1x40A QUINT4 DIN rail diode redundancy module, 10-30VDC input, featuring SFB technology, ATEX/IECEx, and UL 508.

SKU: 2907719 Category: Brand:

Description

Phoenix Contact 2907719 is an industrial 4th-generation DIN rail redundancy module designated under factory type code QUINT4-DIODE/12-24DC/2X20/1X40, where the nomenclature specifies the QUINT4-DIODE series, a 12–24 VDC nominal system voltage, and dual 2x 20 A or single bridged 1x 40 A continuous load capacity. Engineered with high-reliability dual-channel Schottky ORing diode topology, it decouples two parallel power supplies across a 10 VDC to 30 VDC operating input window to eliminate single points of failure caused by output stage short circuits or wiring faults. The module supports a continuous static output current of 40 A (2x 20 A), a dynamic boost rating of 60 A (2x 30 A) for 5 seconds, and Selective Fuse Breaking (SFB) technology delivering up to 240 A (2x 120 A) for 15 ms to trip downstream magnetic circuit breakers instantaneously. With an ultra-low forward voltage drop of 0.5 V, it maintains over 97% efficiency at 24 VDC while dissipating just 20 W at full 40 A load.

Housed in a rugged IP20 corrosion-resistant metal enclosure measuring 36 mm × 130 mm × 125 mm (1.42 in × 5.12 in × 4.92 in), this compact decoupler snaps directly onto standard TS-35 DIN rails in high-density control cabinets. Heavy-duty screw cage clamps accommodate conductor cross-sections up to 16 mm² (6 AWG) across dedicated In 1+, In 2+, and dual Out+ / Out- terminals, preventing wiring hotspots under continuous high-current operation. The maintenance-free passive diode architecture provides inherent 30 VDC reverse polarity and backfeed protection alongside 750 VAC / 1000 VDC galvanic isolation to the chassis. Certified for extreme environments from -40 °C to +70 °C (-40 °F to +158 °F) with full load delivery up to +60 °C (+140 °F), it holds UL 508, UL 61010-2-201, Class I Div 2, ATEX Zone 2, IECEx, and DNV GL marine approvals.

Key Features

  • Dual-Channel 2x20A / 1x40A Decoupling: Isolates two parallel 12–24 VDC power supplies at up to 20 A per channel or a single 40 A supply in 1+1 and N+1 redundant architectures.
  • Dynamic Boost & SFB Pulse Capacity: Delivers 2x 30 A (1x 60 A) dynamic boost for 5 seconds and 2x 120 A (1x 240 A) Selective Fuse Breaking pulses for 15 ms.
  • Low-Loss Schottky Diode Topology: Limits forward voltage drop to 0.5 V typical across the decoupling stage, achieving over 97% efficiency at 24 VDC and restricting thermal dissipation to 20 W at 40 A.
  • Extreme -40°C to +70°C Thermal Rating: Supports cold startup at -40 °C (-40 °F) and continuous full-load operation up to +60 °C (+140 °F) with a linear 2.5%/K derating slope to +70 °C.
  • Hazardous Location & Marine Approvals: Certified to UL 121201 Class I Division 2 (Groups A, B, C, D), ATEX Ex ec IIC T4 Gc, IECEx, and DNV GL standards for petrochemical and offshore cabinets.
  • Slim 36mm Metal DIN Enclosure: Occupies only 36 mm (1.42 in) of horizontal TS-35 rail width while integrating high-current 16 mm² (6 AWG) screw terminals for direct heavy-gauge power distribution.
  • Continuous Backfeed & Short-Circuit Isolation: Blocks reverse voltages up to 30 VDC instantaneously, preventing a shorted PSU output stage or feeder cable fault from dragging down the redundant DC bus.

Technical Specifications

Manufacturer Phoenix Contact
Manufacturer Part Number (MPN) 2907719
OEM Cross-Reference / Replaced Part QUINT4-DIODE/12-24DC/2X20/1X40 (Replaces Legacy QUINT-DIODE/12-24DC/2X20/1X40, MPN 2320157)
Compatible Equipment / Series Phoenix Contact QUINT4-PS, TRIO3-PS, and UNO2-PS 12 VDC / 24 VDC DIN Rail Power Supplies (10 A to 40 A)
Product Series QUINT4-DIODE (4th Generation QUINT Redundancy Modules)
Product Category Redundancy Modules
Component Type Dual-Channel 1+1 / N+1 DIN Rail Diode Redundancy & Decoupling Module
Circuit Topology Passive Common-Cathode Dual Power Schottky ORing Diode Decoupler
Nominal System / Output Voltage 12 VDC to 24 VDC
Operating Voltage Range 10 VDC to 30 VDC
Rated Output Current 40 A continuous (configured as 2x 20 A dual inputs or 1x 40 A bridged input up to +60 °C)
Max. Total Output Current 60 A Dynamic Boost (2x 30 A for 5 s) / 240 A SFB Selective Fuse Breaking Pulse (2x 120 A for 15 ms)
Forward Voltage Drop (Vdrop) 0.5 V typ. (at 20 A per channel / 40 A total load)
Rated Output Power 960 W continuous (at 24 VDC, 40 A) / 1440 W Dynamic Boost (at 24 VDC, 60 A for 5 s)
Transfer / Switchover Time 0 ms (Instantaneous, zero-interruption passive diode conduction switchover)
Number of Input Channels 2 Independent Input Channels (In 1+, In 2+)
Rated Input Current per Channel 20 A static continuous (2x 20 A) / 30 A dynamic boost for 5 s (2x 30 A) / 40 A single bridged input (1x 40 A)
Max. Reverse Voltage Withstand 30 VDC (Continuous reverse blocking capability per diode branch)
Efficiency > 97% (at 24 VDC nominal operation); Power dissipation: 10 W (at 20 A) / 20 W (at 40 A)
Mounting Style DIN Rail TS-35/7.5 or TS-35/15 (EN 60715 Snap-On Mounting)
Cooling Method Natural Air Convection (No internal cooling fan required)
Overall Width (W) 36.0 mm (1.42 in)
Overall Height (H) 130.0 mm (5.12 in)
Overall Depth (D) 125.0 mm (4.92 in)
Net Weight 0.65 kg / 650 g (1.43 lbs / 22.93 oz)
Termination / Connector Style Heavy-Duty Screw Cage Clamp Terminals (M4 captive screws, stripping length 10 mm)
Input Terminal Pinout Bottom Terminal Block: In 1+ (Channel 1 Positive Input), In 2+ (Channel 2 Positive Input), – (Chassis / Reference Minus Return)
Output & Signal Terminal Pinout Top Terminal Block: Out+ (2x internally bridged Positive Redundant Load Outputs)
Terminal Wire Gauge Range 0.5 mm² to 16 mm² solid / 0.5 mm² to 16 mm² flexible / 20 AWG to 6 AWG
Terminal Tightening Torque 1.2 Nm to 1.5 Nm (10.6 lb-in to 13.3 lb-in)
Enclosure / Potting Material Anodized Aluminum Heatsink Chassis with Zinc-Coated Sheet Steel Housing
Overload Protection (OLP) Mode Passive high-surge thermal capability up to 60 A for 5 s; current limiting governed by upstream power supplies
Short Circuit Protection (SCP) Supports 240 A (15 ms) SFB peak fault pass-through to trip downstream magnetic circuit breakers selectively
Reverse Polarity Protection Continuous blocking up to 30 VDC between input channels and load bus
Withstand Isolation Voltage (I/P to FG / Case) 750 VAC (Type Test) / 500 VAC (Routine Test) / 1000 VDC (Input/Output to Housing PE)
Isolation Resistance (at 500 VDC) > 100 MΩ (Input/Output to Protective Earth Chassis)
Operating Ambient Temperature Range -40 °C to +70 °C (-40 °F to +158 °F)
Full-Load Operating Temperature Limit +60 °C (+140 °F) at full 40 A (2x 20 A) continuous load
High-Temperature Derating Rate 2.5% per °C (1.0 A / K) linear load derating from +60 °C to +70 °C (+140 °F to +158 °F)
Altitude Derating Up to 5000 m (16,400 ft); above 2000 m (6,560 ft) derate output current by 0.6% per 100 m or ambient temp by 0.5 K per 100 m
Storage Temperature Range -40 °C to +85 °C (-40 °F to +185 °F)
Operating Relative Humidity ≤ 95% RH (at +25 °C / +77 °F, non-condensing)
Climatic Category (IEC 60068-1) 3K3 (EN 60721-3-3)
Vibration Resistance 15 Hz to 150 Hz, 2.3g acceleration (IEC 60068-2-6, DNV GL Class B); Shock: 30g for 18 ms (IEC 60068-2-27)
Flammability Rating UL 94V-0 (Terminal Housing Insulator)
Ingress Protection (IP) IP20 (Touch-safe finger protection per IEC 60529), Pollution Degree 2, Protection Class III
Safety Approvals (UL / North America) UL Listed UL 508, UL/C-UL Recognized UL 60950-1, UL 61010-1, UL 61010-2-201, ANSI/ISA-12.12.01 (UL 121201) Class I Div 2 Groups A, B, C, D T4
Safety Approvals (IEC / EN / TÜV) IEC/EN 61010-1, IEC/EN 61010-2-201, EN 60950-1, ATEX Ex II 3 G Ex ec IIC T4 Gc (EN 60079-0, EN 60079-7), IECEx Ex ec IIC T4 Gc
Safety Approvals (Regional / Global) CE, UKCA, CB Scheme, EAC, DNV GL Marine Approval
EMC Conducted & Radiated Emissions EN 55011 (CISPR 11) Class B, EN 55032 (CISPR 32) Class B, EN 61000-6-3, EN 61000-6-4
EMC Immunity Standards EN 61000-6-2 Industrial Immunity: EN 61000-4-2 (ESD ±8 kV contact / ±15 kV air), EN 61000-4-3 (RF Field 20 V/m), EN 61000-4-4 (EFT/Burst ±4 kV), EN 61000-4-5 (Surge ±1 kV L-L / ±2 kV L-PE), EN 61000-4-6 (Conducted RF 10 V)
MTBF (IEC 61709 / SN 29500) > 40,000,000 Hours (at +40 °C / +104 °F ambient, 24 VDC nominal operation)
Environmental Compliance RoHS Compliant (2011/65/EU & 2015/863), REACH SVHC Free, WEEE, China RoHS, Lead-Free

Industrial Applications & Compatible Systems

Phoenix Contact 2907719 provides fault-tolerant 1+1 and N+1 power supply decoupling for mission-critical 12 VDC and 24 VDC industrial automation architectures:

  • Distributed Control Systems (DCS) & Redundant PLC Racks: Decouples redundant 24 VDC 20 A QUINT4 power supplies feeding Siemens SIMATIC PCS 7, Allen-Bradley ControlLogix, and Emerson DeltaV process controllers without interruption during primary PSU failure.
  • Oil, Gas & Petrochemical Class I Div 2 / ATEX Zone 2 Enclosures: Certified to UL 121201 and ATEX Ex ec IIC T4 Gc for deployment in hazardous area safety instrumented systems (SIS), wellhead telemetry panels, and refinery emergency shutdown (ESD) cabinets.
  • Marine, Offshore & Shipboard Bridge Control Consoles: DNV GL marine approval and high 2.3g vibration tolerance secure redundant 24 VDC navigation, ballast control, and propulsion automation buses aboard commercial vessels.
  • High-Current 40A Single-Channel Load Splitting & Backfeed Blocking: Bridges In 1+ and In 2+ to decouple a single 40 A power supply or prevent regenerative back-EMF from servo drives and DC motors from corrupting adjacent control buses.

Installation, Thermal Management & MRO Guidelines

Follow these engineering guidelines when integrating the QUINT4-DIODE redundancy module into industrial control panels:

  • Convection Cooling Clearance & Thermal Spacing: Mount vertically on a horizontal TS-35 DIN rail and maintain at least 50 mm (1.97 in) vertical clearance above and below the aluminum heatsink fins, plus 5 mm (0.20 in) lateral spacing next to active components.
  • Upstream Voltage Drop Compensation (+0.5 V Adjustment): Set the output voltage of both upstream power supplies 0.5 VDC above the target bus voltage (e.g., 24.5 VDC) to compensate for the internal Schottky diode forward voltage drop under load.
  • Symmetric Wire Sizing & Bridged 1x40A Jumper Wiring: Use identical cable lengths and cross-sections (up to 16 mm² / 6 AWG tightened to 1.2–1.5 Nm) from both PSUs to ensure balanced current sharing; when operating at 1x 40 A, install an external copper jumper across In 1+ and In 2+.