Description
Weidmüller 1478100000 is an industrial-grade switched-mode power supply from the heavy-duty PROmax series, designated by OEM type nomenclature PRO MAX 72W 24V 3A to denote its 72 W rated power, 24 VDC nominal output, and 3 A continuous load rating at 60 °C. Engineered for demanding factory automation cabinets, it accepts a universal 85 to 277 VAC (45 to 65 Hz) or 80 to 370 VDC wide-range input with active power factor correction (typical PF 0.9 at 230 VAC) and achieves 89% conversion efficiency. The unit delivers a tightly regulated 24 VDC ±1% output adjustable from 22.5 to 29.5 VDC via a front-panel potentiometer, exhibiting low residual ripple and switching spikes below 50 mVpp. Its high-headroom power stage supports a continuous 120% overload boost (3.6 A at ≤45 °C) and up to 300% short-term peak current for starting inductive loads and motors.
Housed in a rugged, corrosion-resistant metal enclosure measuring 32 mm (1.26 in) wide, 130 mm (5.12 in) high, and 125 mm (4.92 in) deep, this slim IP20 supply snaps onto standard TS-35 DIN rails and allows zero-clearance side-by-side mounting. It features heavy-duty screw terminals for a 3-pole input (L, N, PE) and 8-pole output/signaling array (++, —, 11, 13, 14), incorporating a bi-color LED and floating status relay contact that switches at 21.6 VDC / 20.6 VDC. Comprehensive protection includes >120% IN current limiting, continuous short-circuit protection, internal input fusing, varistor surge suppression, and 30 to 35 VDC reverse-voltage load immunity, backed by 4 kV input-to-output galvanic isolation. The supply operates reliably from -25 °C to +70 °C (cold start from -40 °C) with full 3 A power up to +60 °C, and holds cULus (E258476), cURus (E255651), cULusEX Class I Div 2 (E470829), and EN 55032 Class B approvals.
Key Features
- High-Boost 24 VDC Output Stage: Delivers 72 W (3 A) continuous power at 60 °C, 3.6 A (120% continuous boost) up to 45 °C, and 300% dynamic peak current for high-inrush actuators.
- Wide AC/DC Universal Input Range: Operates across 85 to 277 VAC (45 to 65 Hz) and 80 to 370 VDC inputs with 89% efficiency, 0.9 power factor, and 20 ms hold-up time.
- Ultra-Slim Zero-Clearance Metal Housing: Compact 32 x 130 x 125 mm (1.26 x 5.12 x 4.92 in) corrosion-resistant chassis supports direct side-by-side TS-35 DIN rail mounting without lateral air gaps.
- Active DC-OK Relay & LED Diagnostics: Features a bi-color red/green status LED and floating NO relay contact ( terminals 11, 13, 14; 30 VDC / 1 A) triggering at ≥21.6 VDC and ≤20.6 VDC.
- Parallel Scaling & Backfeed Immunity: Supports passive parallel connection of up to 5 power supplies for load expansion and withstands 30 to 35 VDC reverse voltages from decelerating loads.
- 4.0 kV Reinforced Galvanic Isolation: Provides 4 kV AC input-to-output, 3.5 kV input-to-PE, and 0.5 kV output-to-PE dielectric strength meeting Overvoltage Category III and SELV/PELV safety.
- Extreme Thermal & Vibration Resilience: Guarantees cold start-up at -40 °C and continuous operation from -25 °C to +70 °C, tested to 30 g mechanical shock and 2.3 g vibration.
- Global Hazardous Location & Industrial Approvals: Certified to cULus (E258476), cURus (E255651), cULusEX (E470829), EN 60204-1, EN 61558-2-16, and EN 55032 Class B radiated/conducted EMI.
Technical Specifications
| Manufacturer | Weidmüller |
|---|---|
| Manufacturer Part Number (MPN) | 1478100000 |
| OEM Cross-Reference / Replaced Part | PRO MAX 72W 24V 3A (Weidmüller Type Designation) / GTIN 4050118286021 |
| Compatible Equipment / Series | Weidmüller PROmax DC-UPS, Diode Redundancy Modules, CAP Buffer Modules, TS-35 Control Cabinets |
| Product Series | PROmax Series |
| Product Category | Single-Phase DIN Rail |
| Component Type | Industrial AC-DC DIN Rail Switched-Mode Power Supply (SMPS) |
| Circuit Topology | Switched-Mode Power Supply with Active PFC and Galvanic Transformer Isolation (EN 61558-2-16) |
| Nominal Output Voltage | 24 VDC |
| Output Voltage Adjustment Range | 22.5 to 29.5 VDC (via front-panel potentiometer) |
| Rated Output Current | 3.0 A (at 60 °C) / 3.6 A (120% continuous boost at ≤45 °C) / 2.25 A (at 70 °C) |
| Peak / Surge Output Current | 9.0 A (300% short-term peak load capability) |
| Rated Output Power | 72 W (at 60 °C) / 86.4 W (continuous boost at ≤45 °C) |
| Number of Outputs | 1 Single Output (with parallel capability up to 5 units) |
| Output Ripple & Noise (Max.) | < 50 mVpp (residual ripple and switching spikes at nominal voltage, full load) |
| Output Voltage Tolerance | ± 1 % |
| Hold-Up Time | ≥ 20 ms (at nominal load, 115 / 230 VAC) |
| AC Input Voltage Range | 85 to 277 VAC |
| DC Input Voltage Range | 80 to 370 VDC |
| Nominal Input Voltage | 100 to 240 VAC |
| Input Frequency Range | 45 to 65 Hz |
| Efficiency | 89 % (typical at 230 VAC, nominal load; 8.9 W nominal power loss) |
| AC Input Current (at 230 VAC) | 1.0 A (Nominal apparent power consumption: 80.9 VA) |
| DC Input Current (Full Load / No Load) | 1.5 A (at 120 VDC full load) |
| Inrush Current (Cold Start at 115 VAC) | 15 A max. (internal input fuse and varistor surge protection included) |
| Inrush Current (Cold Start at 230 VAC) | 15 A max. (Recommended backup breaker: 6 A Char. B or 3 to 5 A Char. C) |
| Power Factor (PF at 230 VAC) | 0.9 typical (at 230 VAC, 25 °C, 72 W load) |
| No-Load Power Consumption | 1.0 W (idling power loss) |
| Mounting Style | DIN Rail TS-35 (Horizontal mounting, zero side-by-side clearance required) |
| Cooling Method | Free Air Convection (50 mm top and bottom vertical clearance required) |
| Overall Width (W) | 32 mm (1.26 in) |
| Overall Height (H) | 130 mm (5.12 in) |
| Overall Depth (D) | 125 mm (4.92 in) |
| Net Weight | 650 g (1.43 lbs / 22.93 oz) |
| Termination / Connector Style | Cage-Clamp Screw Terminals |
| Input Terminal Pinout | 3-Pole Screw Terminal Block: L (Line), N (Neutral / -DC), PE (Protective Earth) — Screwdriver blade 0.8 x 4.0 mm / PZ 1 |
| Output & Signal Terminal Pinout | 8-Pole Screw Terminal Block: ++ (2x Positive 24 VDC), — (3x Negative Return), 11, 13, 14 (Floating Status Relay Contact) — Screwdriver blade 0.6 x 3.5 mm |
| Control & Monitoring Signals | Floating Status Relay Contact (Terminals 11/13/14, NO contact rated max. 30 VDC / 1 A; closes at ≥21.6 VDC, opens at ≤20.6 VDC) |
| Status Indicator | Bi-Color Green/Red LED (Green: Output ≥ 21.6 VDC; Red: Output ≤ 20.6 VDC) |
| Terminal Wire Gauge Range | Input: 26 to 10 AWG (0.18 to 6.0 mm² rigid, 0.22 to 4.0 mm² flexible) / Output: 26 to 12 AWG (0.5 to 6.0 mm² rigid, 0.5 to 4.0 mm² flexible) |
| Terminal Tightening Torque | 0.5 to 0.6 Nm (4.4 to 5.3 lb-in) for Input and Output Terminals |
| Enclosure / Potting Material | Corrosion-Resistant Metal Housing |
| Overload Protection (OLP) Threshold | > 120 % IN (Continuous current limiting) |
| Overload Protection (OLP) Mode | Constant Current Limiting with automatic recovery |
| Short Circuit Protection (SCP) | Yes (Continuous short-circuit protection) |
| Reverse Polarity Protection | Yes (Internal inverse voltage protection; 30 to 35 VDC reverse feedback voltage immunity from load) |
| Withstand Isolation Voltage (I/P to O/P) | 4.0 kV AC |
| Withstand Isolation Voltage (I/P to FG / Case) | 3.5 kV AC (Protection Class I with PE connection) |
| Withstand Isolation Voltage (O/P to FG / Case) | 0.5 kV AC |
| Earth Leakage Current | 3.5 mA max. |
| Operating Ambient Temperature Range | -25 °C to +70 °C (-13 °F to +158 °F) with Cold Start-Up down to -40 °C (-40 °F) |
| Full-Load Operating Temperature Limit | +60 °C (+140 °F) at 100% load (3.0 A) / +45 °C (+113 °F) at 120% boost load (3.6 A) |
| High-Temperature Derating Rate | 2.5 %/°C above +60 °C (Delivers 75% load / 2.25 A at +70 °C) |
| Altitude Derating | Full load up to 2000 m; derates linearly for higher altitudes up to 6000 m per thermal curve |
| Storage Temperature Range | -40 °C to +85 °C (-40 °F to +185 °F) |
| Operating Relative Humidity | 5 % to 95 % RH (non-condensing) |
| Vibration Resistance | 2.3 g (per IEC 60068-2-6) / Shock Resistance: 30 g in all directions (per IEC 60068-2-27) |
| Ingress Protection (IP) | IP20 |
| Safety Approvals (UL / North America) | cULus Listed (UL 508, File E258476), cURus Recognized (File E255651), cULusEX Hazardous Locations (File E470829) |
| Safety Approvals (IEC / EN / TÜV) | IEC 60950-1 (SELV), EN 60204-1 (PELV / Electrical Machine Equipment), EN 61558-2-16 (Safety Transformers), Surge Category III, Pollution Severity 2 |
| EMC Conducted & Radiated Emissions | EN 55032 Class B |
| EMC Harmonic & Flicker Compliance | IEC / EN 61000-3-2, IEC / EN 61000-3-3 |
| EMC Immunity Standards | EN 55024, IEC / EN 61000-4-2 (ESD), 61000-4-3 (Radiated RF), 61000-4-4 (EFT/Burst), 61000-4-5 (Surge), 61000-4-6 (Conducted RF), 61000-4-8 (Magnetic Field), 61000-4-11 (Voltage Dips) |
| Environmental Compliance | RoHS Compliant (with Exemption 7a, 7cI), REACH SVHC (Lead 7439-92-1, SCIP: 6d8cdf22-8230-4af8-86c8-3558c716666d), ETIM EC002540, ECLASS 27-04-07-01 |
Industrial Applications & Compatible Systems
The Weidmüller 1478100000 (PRO MAX 72W 24V 3A) is engineered for mission-critical 24 VDC control distribution where high peak currents, elevated cabinet temperatures, and compact rail footprints are required:
- PLC & Distributed I/O Control Cabinets: Powers programmable logic controllers, remote fieldbus couplers, and sensor networks requiring clean <50 mVpp SELV/PELV 24 VDC power and integrated DC-OK relay monitoring.
- Motor Starters, Solenoid Valves & Inductive Actuators: Leverages 120% continuous power boost (3.6 A at ≤45 °C) and 300% short-term peak current capability to absorb heavy inrush surges without voltage droop.
- Modular Redundant & Buffered DC Power Architectures: Combines seamlessly with up to 5 parallel PROmax units, Weidmüller diode redundancy modules, CAP buffer modules, or DC-UPS controllers for zero-downtime process automation.
- Harsh Industrial & Hazardous Area Machinery: Certified under cULusEX (E470829) with -40 °C cold start-up and 30 g shock / 2.3 g vibration ratings for oil, gas, packaging, and machine tool installations.
Installation, Thermal Management & MRO Guidelines
Follow these engineering practices to maximize thermal reliability and electrical safety during panel integration:
- DIN Rail Clearance & Zero-Gap Side Mounting: Snap the unit horizontally onto a TS-35 rail using WEW 35/1 or WEW 35/2 end brackets; while adjacent modules can be mounted side-by-side with zero lateral gap, maintain at least 50 mm (1.97 in) vertical clearance above and below for natural convection.
- Upstream Circuit Breaker & DC Input Polarity: Protect the AC supply line with a 6 A Characteristic B or 3 to 5 A Characteristic C circuit breaker to coordinate with the 15 A max cold-start inrush, and strictly observe DC polarity when operating from 80 to 370 VDC battery buses.
- High-Temperature Derating & Torque Specification: Operate up to 3.6 A below 45 °C and 3.0 A up to 60 °C, applying a 2.5 %/°C linear derating down to 2.25 A at 70 °C; tighten all input and output screw terminals to 0.5–0.6 Nm using 0.8×4.0 mm / PZ1 and 0.6×3.5 mm insulated blades.