Description
WAGO 787-1601 (also known as 7871601) is an industrial 24 W single-phase switched-mode DIN rail power supply from the EPSITRON® CLASSIC series, engineered for high-reliability 12 VDC control and sensor distribution. Within WAGO’s 787-16xx nomenclature, the 787-1601 designates the ultra-slim 12 VDC / 2 A NEC Class 2 Limited Power Source (LPS) model with pluggable connection technology. Powered by a universal 85 to 264 VAC (44 to 66 Hz) or 120 to 300 VDC input stage with passive power factor correction, the unit delivers a tightly regulated 12 VDC nominal output (front-panel adjustable from 11.5 to 14.5 VDC) at 2 A continuous current (up to 2.1 A at lower voltage settings). It achieves 82% typical efficiency with ultra-low residual ripple of ≤ 20 mV p-p, ≤ 1% output voltage deviation, and an extended mains failure hold-up time of ≥ 120 ms at 230 VAC (≥ 15 ms at 100 VAC).
Housed in an encapsulated, ultra-narrow 22.5 × 90 × 107.5 mm (0.886 × 3.543 × 4.232 in) IP20 enclosure for DIN-35 rail mounting, the 787-1601 utilizes vibration-proof WAGO 721 Series CAGE CLAMP® pluggable female connectors accepting 28 to 12 AWG (0.08 to 2.5 mm²) conductors and provides both a green DC OK LED and a bounce-free 12 VDC / 40 mA active DC OK signal output. Its comprehensive protection suite includes constant-current overload limiting at 1.1 × Io nom, continuous short-circuit and open-circuit protection, primary varistor transient suppression, secondary overvoltage clamping at ≤ 35 VDC, and ≤ 25 VDC reverse-feed resistance for parallel or series operation. Reinforced 4.242 kVDC primary-to-secondary galvanic isolation (Protection Class II, SELV/PELV) is paired with a wide -25 °C to +70 °C (-13 °F to +158 °F) operating envelope (type-tested cold start at -40 °C, full load up to +50 °C with -3 %/K derating above), backed by UL 508, UL 60950-1, NEC Class 2, EN 61010-1, EN 61010-2-201, SEMI F47, and DNV marine certifications.
Key Features
- NEC Class 2 & LPS Regulated 12VDC Output: Delivers 24 W continuous power (12 VDC at 2 A, adjustable 11.5–14.5 VDC) with ≤ 20 mV p-p ripple and ≤ 1% deviation, certified as an NEC Class 2 Limited Power Source.
- Wide Universal AC/DC Input & Hold-Up Reserve: Operates across 85–264 VAC (44–66 Hz) and 120–300 VDC inputs, maintaining ≥ 120 ms hold-up time at 230 VAC (≥ 15 ms at 100 VAC) and SEMI F47 voltage sag immunity.
- Active Bounce-Free DC OK Telemetry: Integrates a front-panel green Uo status LED and an active 12 VDC / 40 mA bounce-free DC OK switching output for direct PLC digital input power-health diagnostics.
- Ultra-Slim 22.5 mm Encapsulated DIN Housing: Compact 22.5 × 90 × 107.5 mm (0.886 × 3.543 × 4.232 in) footprint saves DIN-35 rail space while using WAGO 721 Series CAGE CLAMP® pluggable connectors for rapid pre-wired maintenance.
- 4.242 kVDC Protection Class II Isolation: Provides reinforced 4,242 VDC primary-to-secondary galvanic isolation (SELV per UL 60950-1, PELV per EN 60204) without requiring a protective earth ground connection.
- Constant-Current Overload & Parallel/Series Capability: Features 1.1 × Io nom constant-current overload behavior, ≤ 35 VDC secondary overvoltage clamping, and ≤ 25 VDC reverse-feed resistance supporting redundant parallel or series wiring.
- Extreme -40 °C Cold Start & Marine Approvals: Type-tested for cold start at -40 °C with continuous operation from -25 °C to +70 °C (-3 %/K derating above +50 °C), certified to UL 508, EN 61010-2-201, and DNV marine standards.
Technical Specifications
| Manufacturer | WAGO |
|---|---|
| Manufacturer Part Number (MPN) | 787-1601 |
| Alternate Part Number | 7871601 |
| Compatible Equipment / Series | WAGO 787-980 Filter Module (for DNV EMC 1 compliance), WAGO 721 Series Pluggable Connectors, WAGO I/O System 750/753 |
| Product Series | EPSITRON® CLASSIC (787-16xx Series) |
| Product Category | Single-Phase DIN Rail |
| Component Type | Switched-Mode DIN Rail Power Supply (NEC Class 2 / LPS) |
| Circuit Topology | Primary Switched-Mode Regulated AC-DC Converter (SELV / PELV Isolated, Protection Class II) |
| Nominal Output Voltage | 12 VDC (SELV / PELV) |
| Output Voltage Adjustment Range | 11.5 to 14.5 VDC (Front-panel potentiometer, default setting 12 VDC) |
| Rated Output Current | 2 A (at 12 VDC); up to 2.1 A (at lower adjusted output voltage) |
| Rated Output Power | 24 W |
| Number of Outputs | 1 (Single Output, parallel and series operation supported) |
| Output Ripple & Noise (Max.) | ≤ 20 mV p-p (Residual ripple) |
| Output Voltage Tolerance | ≤ ±1% (Total static/dynamic deviation) |
| Hold-Up Time (at 115 VAC) | ≥ 15 ms (at 100 VAC nominal load) |
| Hold-Up Time (at 230 VAC) | ≥ 120 ms (at 230 VAC nominal load) |
| AC Input Voltage Range | 85 to 264 VAC (Single-phase) |
| DC Input Voltage Range | 120 to 300 VDC (External DC fuse required) |
| Nominal Input Voltage | 1 x 100 to 240 VAC |
| Input Frequency Range | 44 to 66 Hz; 0 Hz (DC operation) |
| Efficiency | 82% (Typical); Power loss ≤ 5.3 W at 230 VAC nominal load, 5.7 W max. at 100 VAC / 12 VDC 2 A |
| AC Input Current (at 115 VAC) | ≤ 0.5 A (at 100 VAC) |
| AC Input Current (at 230 VAC) | ≤ 0.29 A (at 240 VAC) |
| Inrush Current (Cold Start at 230 VAC) | ≤ 30 A ( across 100 to 240 VAC input range) |
| Power Factor Correction (PFC) | Passive |
| No-Load Power Consumption | ≤ 0.7 W |
| Mounting Style | DIN-35 Rail (EN 60715) |
| Cooling Method | Natural Free Air Convection (when horizontally mounted) |
| Overall Width (W) | 22.5 mm (0.886 in) |
| Overall Height (H) | 90.0 mm (3.543 in) |
| Overall Depth (D) | 107.5 mm (4.232 in) from upper-edge of DIN rail |
| Net Weight | 128 g (0.282 lbs / 4.52 oz) |
| Termination / Connector Style | WAGO 721 Series Pluggable Female Connectors with CAGE CLAMP® Spring Pressure Technology |
| Input Terminal Pinout | Input Connector: L (Line), N (Neutral) — Protection Class II (No PE terminal required) |
| Output & Signal Terminal Pinout | Output/Signal Connector: + (Positive Output), – (Negative Output), DC OK (Active +12 VDC, 40 mA signal output) |
| Control & Monitoring Signals | 1 x Active bounce-free DC OK switching output (12 VDC, max. 40 mA) |
| Status Indicator | 1 x Green LED (Uo / DC OK operation status indicator) |
| Terminal Wire Gauge Range | Solid: 0.08 to 2.5 mm² (28 to 12 AWG); Fine-stranded: 0.08 to 2.5 mm² (28 to 12 AWG); Strip length: 8 to 9 mm (0.31 to 0.35 in) |
| Enclosure / Potting Material | Encapsulated industrial housing for control cabinet installation |
| Overload Protection (OLP) Threshold | 1.1 x Io nom (Typical, approx. 2.2 A) |
| Overload Protection (OLP) Mode | Constant current limitation with automatic recovery |
| Overvoltage Protection (OVP) Threshold | ≤ 35 VDC (Secondary internal protective circuit in the event of a fault) |
| Overvoltage Protection (OVP) Mode | Internal secondary voltage limitation circuit; Primary varistor transient suppression |
| Short Circuit Protection (SCP) | Yes (Continuous short-circuit-protected and open-circuit-proof) |
| Reverse Polarity Protection | Resistance to reverse feed ≤ 25 VDC; Internal input fuse T 2 A / 250 VAC; Recommended external backup MCB: 6 A, 10 A, or 16 A (Type B or C) |
| Withstand Isolation Voltage (I/P to O/P) | 4.242 kVDC (4,242 VDC primary to secondary; Protection Class II, Overvoltage Category II) |
| Earth Leakage Current | ≤ 0.25 mA (Discharge current) |
| Operating Ambient Temperature Range | -25 °C to +70 °C (-13 °F to +158 °F); Type-tested cold start down to -40 °C (-40 °F) |
| Full-Load Operating Temperature Limit | +50 °C (+122 °F) at 100% load under natural convection |
| High-Temperature Derating Rate | -3.0 %/K above +50 °C (+122 °F) up to +70 °C (+158 °F) |
| Low-Line Input Derating | -2.5 %/V below 95 VAC (from 95 VAC down to 85 VAC) |
| Storage Temperature Range | -25 °C to +85 °C (-13 °F to +185 °F) |
| Operating Relative Humidity | 5% to 96% RH (Non-condensing, Pollution Degree 2) |
| Climatic Category (IEC 60068-1) | 3K3 (per EN 60721) |
| Ingress Protection (IP) | IP20 (per EN 60529) |
| Safety Approvals (UL / North America) | UL 508 Listed (File E255817), UL 60950-1 Recognized (UR File E255815), NEC Class 2 Limited Power Source (LPS) |
| Safety Approvals (IEC / EN / TÜV) | EN 61010-1, EN 61010-2-201, EN 60335-1, SELV (per UL 60950-1), PELV (per EN 60204), CE |
| Safety Approvals (Regional / Global) | DNV Marine Approval (DNVGL-CG-339, Certificate TAA00002YC), SEMI F47 Semiconductor Sag Immunity, EAC (TP TC 004/2011 CoC 03078, TP TC 020/2011 CoC 03081) |
| EMC Conducted & Radiated Emissions | EN 61204-3 Low-Voltage Power Supplies EMC Standard; DNV EMC 1 compliant when used with WAGO 787-980 Filter Module |
| EMC Immunity Standards | EN 61204-3 Industrial EMC Immunity, SEMI F47 Voltage Sag Immunity, EAC TP TC 020/2011 |
| MTBF (IEC 61709 / SN 29500) | > 500,000 hours (per IEC 61709) |
| Environmental Compliance | RoHS Compliant (No Exemption), Country of Origin: Germany (DE), GTIN: 4055143060400 |
Industrial Applications & Compatible Systems
The WAGO 787-1601 is engineered for space-constrained industrial automation panels, marine consoles, and NEC Class 2 low-voltage distribution networks requiring clean 12 VDC power.
- NEC Class 2 PLC, I/O & Field Sensor Bus Power: Supplies NEC Class 2 current-limited 12 VDC power to WAGO I/O System 750/753 nodes, proximity sensors, optical encoders, and compact micro-PLCs without requiring complex downstream Class 2 branch circuit breakers.
- Semiconductor Fab & Process Control Cabinets: Certified to SEMI F47 and offering ≥ 120 ms hold-up time at 230 VAC, ensuring uninterrupted 12 VDC ride-through for process controllers and instrumentation during AC line voltage sags.
- Marine, Offshore & Shipboard Bridge Consoles: Approved to DNV (DNVGL-CG-339 Certificate TAA00002YC) and compatible with the WAGO 787-980 filter module for EMC 1 bridge/deck zones, ideal for vessel telemetry and navigation sub-panels.
- Building Automation, Access Control & Industrial Gateways: Powers 12 VDC PoE/industrial Ethernet switches, Modbus/BACnet routers,intercom panels, and motorized damper actuators in commercial HVAC and security enclosures.
Installation, Thermal Management & MRO Guidelines
Follow these engineering best practices during cabinet layout, circuit protection sizing, and preventive maintenance to maximize service life.
- Thermal Convection & Derating Management: Mount horizontally on a standard DIN-35 rail to enable natural convection cooling; derate continuous output load by 3 %/K when ambient cabinet temperatures exceed +50 °C up to +70 °C, and by 2.5 %/V when AC mains voltage drops below 95 VAC.
- Upstream Overcurrent & DC Input Fusing: Although protected by an internal T 2 A / 250 VAC fuse, protect the primary supply feed with a 6 A, 10 A, or 16 A miniature circuit breaker (Type B or C tripping curve) to accommodate the ≤ 30 A cold-start inrush; install an external DC-rated fuse when feeding 120–300 VDC.
- CAGE CLAMP® Wiring & Active DC OK Integration: Strip solid or fine-stranded 28–12 AWG (0.08–2.5 mm²) conductors to 8–9 mm (0.31–0.35 in) for WAGO 721 Series pluggable connectors, and wire the bounce-free 12 VDC (max. 40 mA) active DC OK pin to a PLC digital input for real-time power failure alarming.