787-1601 WAGO 24W 12VDC Single-Phase DIN Rail Power Supply

$140.04

WAGO 787-1601 (7871601) 24W 12VDC 2A single-phase DIN rail power supply, 85-264VAC/120-300VDC input, featuring NEC Class 2 LPS, active DC OK output, and UL 508.

SKU: 787-1601 Category: Brand:

Description

WAGO 787-1601 (also known as 7871601) is an industrial 24 W single-phase switched-mode DIN rail power supply from the EPSITRON® CLASSIC series, engineered for high-reliability 12 VDC control and sensor distribution. Within WAGO’s 787-16xx nomenclature, the 787-1601 designates the ultra-slim 12 VDC / 2 A NEC Class 2 Limited Power Source (LPS) model with pluggable connection technology. Powered by a universal 85 to 264 VAC (44 to 66 Hz) or 120 to 300 VDC input stage with passive power factor correction, the unit delivers a tightly regulated 12 VDC nominal output (front-panel adjustable from 11.5 to 14.5 VDC) at 2 A continuous current (up to 2.1 A at lower voltage settings). It achieves 82% typical efficiency with ultra-low residual ripple of ≤ 20 mV p-p, ≤ 1% output voltage deviation, and an extended mains failure hold-up time of ≥ 120 ms at 230 VAC (≥ 15 ms at 100 VAC).

Housed in an encapsulated, ultra-narrow 22.5 × 90 × 107.5 mm (0.886 × 3.543 × 4.232 in) IP20 enclosure for DIN-35 rail mounting, the 787-1601 utilizes vibration-proof WAGO 721 Series CAGE CLAMP® pluggable female connectors accepting 28 to 12 AWG (0.08 to 2.5 mm²) conductors and provides both a green DC OK LED and a bounce-free 12 VDC / 40 mA active DC OK signal output. Its comprehensive protection suite includes constant-current overload limiting at 1.1 × Io nom, continuous short-circuit and open-circuit protection, primary varistor transient suppression, secondary overvoltage clamping at ≤ 35 VDC, and ≤ 25 VDC reverse-feed resistance for parallel or series operation. Reinforced 4.242 kVDC primary-to-secondary galvanic isolation (Protection Class II, SELV/PELV) is paired with a wide -25 °C to +70 °C (-13 °F to +158 °F) operating envelope (type-tested cold start at -40 °C, full load up to +50 °C with -3 %/K derating above), backed by UL 508, UL 60950-1, NEC Class 2, EN 61010-1, EN 61010-2-201, SEMI F47, and DNV marine certifications.

Key Features

  • NEC Class 2 & LPS Regulated 12VDC Output: Delivers 24 W continuous power (12 VDC at 2 A, adjustable 11.5–14.5 VDC) with ≤ 20 mV p-p ripple and ≤ 1% deviation, certified as an NEC Class 2 Limited Power Source.
  • Wide Universal AC/DC Input & Hold-Up Reserve: Operates across 85–264 VAC (44–66 Hz) and 120–300 VDC inputs, maintaining ≥ 120 ms hold-up time at 230 VAC (≥ 15 ms at 100 VAC) and SEMI F47 voltage sag immunity.
  • Active Bounce-Free DC OK Telemetry: Integrates a front-panel green Uo status LED and an active 12 VDC / 40 mA bounce-free DC OK switching output for direct PLC digital input power-health diagnostics.
  • Ultra-Slim 22.5 mm Encapsulated DIN Housing: Compact 22.5 × 90 × 107.5 mm (0.886 × 3.543 × 4.232 in) footprint saves DIN-35 rail space while using WAGO 721 Series CAGE CLAMP® pluggable connectors for rapid pre-wired maintenance.
  • 4.242 kVDC Protection Class II Isolation: Provides reinforced 4,242 VDC primary-to-secondary galvanic isolation (SELV per UL 60950-1, PELV per EN 60204) without requiring a protective earth ground connection.
  • Constant-Current Overload & Parallel/Series Capability: Features 1.1 × Io nom constant-current overload behavior, ≤ 35 VDC secondary overvoltage clamping, and ≤ 25 VDC reverse-feed resistance supporting redundant parallel or series wiring.
  • Extreme -40 °C Cold Start & Marine Approvals: Type-tested for cold start at -40 °C with continuous operation from -25 °C to +70 °C (-3 %/K derating above +50 °C), certified to UL 508, EN 61010-2-201, and DNV marine standards.

Technical Specifications

Manufacturer WAGO
Manufacturer Part Number (MPN) 787-1601
Alternate Part Number 7871601
Compatible Equipment / Series WAGO 787-980 Filter Module (for DNV EMC 1 compliance), WAGO 721 Series Pluggable Connectors, WAGO I/O System 750/753
Product Series EPSITRON® CLASSIC (787-16xx Series)
Product Category Single-Phase DIN Rail
Component Type Switched-Mode DIN Rail Power Supply (NEC Class 2 / LPS)
Circuit Topology Primary Switched-Mode Regulated AC-DC Converter (SELV / PELV Isolated, Protection Class II)
Nominal Output Voltage 12 VDC (SELV / PELV)
Output Voltage Adjustment Range 11.5 to 14.5 VDC (Front-panel potentiometer, default setting 12 VDC)
Rated Output Current 2 A (at 12 VDC); up to 2.1 A (at lower adjusted output voltage)
Rated Output Power 24 W
Number of Outputs 1 (Single Output, parallel and series operation supported)
Output Ripple & Noise (Max.) ≤ 20 mV p-p (Residual ripple)
Output Voltage Tolerance ≤ ±1% (Total static/dynamic deviation)
Hold-Up Time (at 115 VAC) ≥ 15 ms (at 100 VAC nominal load)
Hold-Up Time (at 230 VAC) ≥ 120 ms (at 230 VAC nominal load)
AC Input Voltage Range 85 to 264 VAC (Single-phase)
DC Input Voltage Range 120 to 300 VDC (External DC fuse required)
Nominal Input Voltage 1 x 100 to 240 VAC
Input Frequency Range 44 to 66 Hz; 0 Hz (DC operation)
Efficiency 82% (Typical); Power loss ≤ 5.3 W at 230 VAC nominal load, 5.7 W max. at 100 VAC / 12 VDC 2 A
AC Input Current (at 115 VAC) ≤ 0.5 A (at 100 VAC)
AC Input Current (at 230 VAC) ≤ 0.29 A (at 240 VAC)
Inrush Current (Cold Start at 230 VAC) ≤ 30 A ( across 100 to 240 VAC input range)
Power Factor Correction (PFC) Passive
No-Load Power Consumption ≤ 0.7 W
Mounting Style DIN-35 Rail (EN 60715)
Cooling Method Natural Free Air Convection (when horizontally mounted)
Overall Width (W) 22.5 mm (0.886 in)
Overall Height (H) 90.0 mm (3.543 in)
Overall Depth (D) 107.5 mm (4.232 in) from upper-edge of DIN rail
Net Weight 128 g (0.282 lbs / 4.52 oz)
Termination / Connector Style WAGO 721 Series Pluggable Female Connectors with CAGE CLAMP® Spring Pressure Technology
Input Terminal Pinout Input Connector: L (Line), N (Neutral) — Protection Class II (No PE terminal required)
Output & Signal Terminal Pinout Output/Signal Connector: + (Positive Output), – (Negative Output), DC OK (Active +12 VDC, 40 mA signal output)
Control & Monitoring Signals 1 x Active bounce-free DC OK switching output (12 VDC, max. 40 mA)
Status Indicator 1 x Green LED (Uo / DC OK operation status indicator)
Terminal Wire Gauge Range Solid: 0.08 to 2.5 mm² (28 to 12 AWG); Fine-stranded: 0.08 to 2.5 mm² (28 to 12 AWG); Strip length: 8 to 9 mm (0.31 to 0.35 in)
Enclosure / Potting Material Encapsulated industrial housing for control cabinet installation
Overload Protection (OLP) Threshold 1.1 x Io nom (Typical, approx. 2.2 A)
Overload Protection (OLP) Mode Constant current limitation with automatic recovery
Overvoltage Protection (OVP) Threshold ≤ 35 VDC (Secondary internal protective circuit in the event of a fault)
Overvoltage Protection (OVP) Mode Internal secondary voltage limitation circuit; Primary varistor transient suppression
Short Circuit Protection (SCP) Yes (Continuous short-circuit-protected and open-circuit-proof)
Reverse Polarity Protection Resistance to reverse feed ≤ 25 VDC; Internal input fuse T 2 A / 250 VAC; Recommended external backup MCB: 6 A, 10 A, or 16 A (Type B or C)
Withstand Isolation Voltage (I/P to O/P) 4.242 kVDC (4,242 VDC primary to secondary; Protection Class II, Overvoltage Category II)
Earth Leakage Current ≤ 0.25 mA (Discharge current)
Operating Ambient Temperature Range -25 °C to +70 °C (-13 °F to +158 °F); Type-tested cold start down to -40 °C (-40 °F)
Full-Load Operating Temperature Limit +50 °C (+122 °F) at 100% load under natural convection
High-Temperature Derating Rate -3.0 %/K above +50 °C (+122 °F) up to +70 °C (+158 °F)
Low-Line Input Derating -2.5 %/V below 95 VAC (from 95 VAC down to 85 VAC)
Storage Temperature Range -25 °C to +85 °C (-13 °F to +185 °F)
Operating Relative Humidity 5% to 96% RH (Non-condensing, Pollution Degree 2)
Climatic Category (IEC 60068-1) 3K3 (per EN 60721)
Ingress Protection (IP) IP20 (per EN 60529)
Safety Approvals (UL / North America) UL 508 Listed (File E255817), UL 60950-1 Recognized (UR File E255815), NEC Class 2 Limited Power Source (LPS)
Safety Approvals (IEC / EN / TÜV) EN 61010-1, EN 61010-2-201, EN 60335-1, SELV (per UL 60950-1), PELV (per EN 60204), CE
Safety Approvals (Regional / Global) DNV Marine Approval (DNVGL-CG-339, Certificate TAA00002YC), SEMI F47 Semiconductor Sag Immunity, EAC (TP TC 004/2011 CoC 03078, TP TC 020/2011 CoC 03081)
EMC Conducted & Radiated Emissions EN 61204-3 Low-Voltage Power Supplies EMC Standard; DNV EMC 1 compliant when used with WAGO 787-980 Filter Module
EMC Immunity Standards EN 61204-3 Industrial EMC Immunity, SEMI F47 Voltage Sag Immunity, EAC TP TC 020/2011
MTBF (IEC 61709 / SN 29500) > 500,000 hours (per IEC 61709)
Environmental Compliance RoHS Compliant (No Exemption), Country of Origin: Germany (DE), GTIN: 4055143060400

Industrial Applications & Compatible Systems

The WAGO 787-1601 is engineered for space-constrained industrial automation panels, marine consoles, and NEC Class 2 low-voltage distribution networks requiring clean 12 VDC power.

  • NEC Class 2 PLC, I/O & Field Sensor Bus Power: Supplies NEC Class 2 current-limited 12 VDC power to WAGO I/O System 750/753 nodes, proximity sensors, optical encoders, and compact micro-PLCs without requiring complex downstream Class 2 branch circuit breakers.
  • Semiconductor Fab & Process Control Cabinets: Certified to SEMI F47 and offering ≥ 120 ms hold-up time at 230 VAC, ensuring uninterrupted 12 VDC ride-through for process controllers and instrumentation during AC line voltage sags.
  • Marine, Offshore & Shipboard Bridge Consoles: Approved to DNV (DNVGL-CG-339 Certificate TAA00002YC) and compatible with the WAGO 787-980 filter module for EMC 1 bridge/deck zones, ideal for vessel telemetry and navigation sub-panels.
  • Building Automation, Access Control & Industrial Gateways: Powers 12 VDC PoE/industrial Ethernet switches, Modbus/BACnet routers,intercom panels, and motorized damper actuators in commercial HVAC and security enclosures.

Installation, Thermal Management & MRO Guidelines

Follow these engineering best practices during cabinet layout, circuit protection sizing, and preventive maintenance to maximize service life.

  • Thermal Convection & Derating Management: Mount horizontally on a standard DIN-35 rail to enable natural convection cooling; derate continuous output load by 3 %/K when ambient cabinet temperatures exceed +50 °C up to +70 °C, and by 2.5 %/V when AC mains voltage drops below 95 VAC.
  • Upstream Overcurrent & DC Input Fusing: Although protected by an internal T 2 A / 250 VAC fuse, protect the primary supply feed with a 6 A, 10 A, or 16 A miniature circuit breaker (Type B or C tripping curve) to accommodate the ≤ 30 A cold-start inrush; install an external DC-rated fuse when feeding 120–300 VDC.
  • CAGE CLAMP® Wiring & Active DC OK Integration: Strip solid or fine-stranded 28–12 AWG (0.08–2.5 mm²) conductors to 8–9 mm (0.31–0.35 in) for WAGO 721 Series pluggable connectors, and wire the bounce-free 12 VDC (max. 40 mA) active DC OK pin to a PLC digital input for real-time power failure alarming.