DRL100-24-1 TDK-Lambda 100.8W 24VDC DIN Rail Power Supply

$66.49

TDK-Lambda DRL100-24-1 (DRL100241) 100.8W 24VDC 4.2A low-profile DIN rail power supply, 85-264VAC Class II input, 90% efficiency, UL508 & IEC 62368-1 listed.

SKU: DRL100-24-1 Category: Brand:

Description

TDK-Lambda DRL100-24-1 (also known as DRL100241) is a 100.8 W low-profile industrial DIN rail AC-DC power supply from the DRL10-100 series, where the MPN denotes the 100 W power class, 24 VDC nominal output, and standard non-Class-2 full-power configuration. Engineered with a high-frequency switching topology operating between 84.4 kHz and 95.5 kHz, it accepts a universal 85–264 VAC (47–63 Hz) or 120–373 VDC input and delivers a user-adjustable 24 to 28 VDC output at up to 4.2 A continuous current. The unit achieves up to 88% efficiency at 115 VAC and 90% at 230 VAC while keeping no-load standby consumption below 0.5 W and output ripple and noise within 240 mVp-p.

Designed with double-insulated Safety Class II construction, the DRL100-24-1 eliminates the need for a protective earth ground connection while maintaining 3,000 VAC reinforced input-to-output isolation. Comprehensive protection includes >105% hiccup-mode overcurrent protection with automatic recovery and 29–35 V overvoltage shutdown, paired with a front-panel green DC OK LED indicator. Housed in a compact 72 × 91 × 55.6 mm (2.83 × 3.58 × 2.19 in) UL94 V-0 flame-retardant polycarbonate enclosure for TS-35/7.5 or TS-35/15 DIN rails, it operates via convection cooling from -20 °C to +71 °C (-25 °C cold start) and carries UL508, IEC/UL/CSA/EN 62368-1, and CE certifications.

Key Features

  • High Conversion Efficiency & Low Standby: Delivers 88% efficiency at 115 VAC and 90% at 230 VAC with under 0.5 W no-load power draw, minimizing cabinet heat dissipation and energy waste.
  • Safety Class II Double Insulation: Reinforced 3,000 VAC input-to-output isolation eliminates protective earth wiring requirements, simplifying installation in two-wire building automation and control panels.
  • Adjustable 24–28 VDC Output Rail: Provides 100.8 W continuous power at 4.2 A with a front-accessible potentiometer adjustable from 24 V to 28 V to compensate for long cable voltage drops.
  • Low-Profile EN 43880 Step Enclosure: Compact 72 mm (4SU) width and 55.6 mm depth in UL94 V-0 flame-retardant polycarbonate fits shallow wall-mounted consumer units and distribution boards.
  • Wide-Range Input & Surge Tolerance: Operates across 85–264 VAC (47–63 Hz) or 120–373 VDC and withstands 300 VAC input surges for up to 5 seconds without damage.
  • Heavy Industrial EMC Immunity & SEMI F47: Certified to EN 55032 Class B conducted emissions, EN 61000-4-4 Level 4 EFT, EN 61000-4-5 Level 3 surge, and SEMI F47 line dip compliance above 200 VAC.
  • Global Industrial & IT Safety Approvals: Listed to UL508 for industrial control equipment and certified to IEC/UL/CSA/EN 62368-1 and 60950-1 with a 437,110-hour Telcordia SR-332 MTBF.

Technical Specifications

Manufacturer TDK-Lambda
Manufacturer Part Number (MPN) DRL100-24-1
Alternate Part Number DRL100241
Product Series DRL10-100 Series (DRL100)
Product Category Low-Profile DIN Rail
Component Type Single-Output Low-Profile AC-DC DIN Rail Power Supply
Circuit Topology Fixed-Range Frequency-Modulated Switching Converter (84.4–95.5 kHz)
Nominal Output Voltage 24 VDC
Output Voltage Adjustment Range 24 – 28 VDC (via front potentiometer)
Rated Output Current 4.2 A
Output Current Range 0 – 4.2 A (No minimum load required)
Rated Output Power 100.8 W
Output Ripple & Noise (Max) 240 mVp-p
Line Regulation 240 mV
Load Regulation 240 mV
Temperature Coefficient < ±0.02 %/°C
Hold-Up Time (at 115 VAC) 15 ms (typical)
Hold-Up Time (at 230 VAC) ≥ 15 ms (typical)
Parallel Operation Not supported
Series Operation Supported (refer to TDK-Lambda DRL installation manual)
Nominal Input Voltage 100 – 240 VAC (Single-Phase)
AC Input Voltage Range 85 – 264 VAC
DC Input Voltage Range 120 – 373 VDC (Safety certified for AC input only)
Input Surge Withstand Voltage 300 VAC for 5 seconds
Input Frequency Range 47 – 63 Hz
Efficiency (at 115 VAC) 88 %
Efficiency (at 230 VAC) 90 %
Average Active Efficiency 87 % (measured at 25%, 50%, 75%, and 100% load)
AC Input Current (at 110 / 115 VAC) 2.0 A
AC Input Current (at 230 VAC) 1.1 A
Inrush Current (Cold Start at 230 VAC) 60 A (typical)
Power Factor (at 115 VAC) 0.50
Power Factor (at 230 VAC) 0.43
Harmonic Current Compliance Meets IEC 61000-3-2 Class A
No-Load Power Consumption < 0.5 W
Switching Frequency 84.4 – 95.5 kHz (at 230 VAC, 100% load)
Overload / Overcurrent Protection (OLP) Threshold > 105 % of rated output current
Overload / Overcurrent Protection (OLP) Mode Hiccup mode with automatic recovery
Overvoltage Protection (OVP) Threshold 29 – 35 VDC
Overvoltage Protection (OVP) Mode Shutdown / clamp protection
Insulation Protection Class Safety Class II
Withstand Isolation Voltage (I/P to O/P) 3,000 VAC (for 1 minute)
Isolation Resistance (at 500 VDC) > 100 MΩ (at 25 °C, 70% RH)
Operating Ambient Temperature Range -20 °C to +71 °C (-4 °F to +159.8 °F), with -25 °C (-13 °F) cold start-up
Full-Load Operating Temperature Limit (115–240 VAC) +51 °C (+123.8 °F) at 100% load
High-Temperature Derating Rate (115–240 VAC) Linearly derate 2.0 %/°C from +51 °C to 60% load at +71 °C
Low-Line Input Temperature Derating (100–115 VAC) Full load up to +40 °C (+104 °F); linearly derate 1.94 %/°C to 40% load at +71 °C
Storage Temperature Range -40 °C to +85 °C (-40 °F to +185 °F)
Operating Relative Humidity 5 % to 95 % RH (non-condensing)
Maximum Operating Altitude 3,000 m (9,842 ft)
Operating Vibration Resistance IEC 60068-2-6, Sine wave, 10–500 Hz, 19.6 m/s² (2G peak), 10 min/cycle, 60 min each X/Y/Z
Operating Shock Resistance IEC 60068-2-27, Half-sine wave, 39.2 m/s² (4G) for 22 ms, 3 shocks in each of 3 axes (9 total)
MTBF (Telcordia SR-332 Issue 3) 437,110 hours (24V model, +55 °C ambient, 100% load, 230 VAC input)
Expected Electrolytic Capacitor Life > 8 years (at +40 °C ambient, 75% load, 230 VAC input)
Safety Agency Approvals (North America) UL 508 Listed (Industrial Control Equipment), UL/CSA 62368-1, 60950-1
Safety Agency Approvals (International / Europe) IEC/EN 62368-1, IEC/EN 60950-1, CE Mark
UL 1310 NEC Class 2 Compliance No (DRL100-24-1 is excluded from UL 1310 Class 2; see DRL100-24-1/C2 for 88W Class 2)
Conducted EMI Emissions EN 55032 Class B
Radiated EMI Emissions EN 55032 Class A
EMC Electrostatic Discharge (ESD) EN 61000-4-2 Level 3 (8 kV air discharge), Criteria A
EMC Radiated RF Susceptibility EN 61000-4-3 Level 3, Criteria A
EMC Electrical Fast Transient / Burst (EFT) EN 61000-4-4 Level 4, Criteria A
EMC Surge Immunity EN 61000-4-5 Level 3, Criteria A
EMC Conducted RF Susceptibility EN 61000-4-6 Level 3, Criteria A
EMC Power Frequency Magnetic Field EN 61000-4-8 Level 4, Criteria A
EMC Voltage Dips & Interruptions EN 61000-4-11 Class 3 Industrial (0% 1 cyc Crit A; 40% 10/12 cyc, 70% 25/30 cyc, 80% 250/300 cyc Crit B)
Semiconductor Line Dip Compliance SEMI F47 compliant (at > 200 VAC input)
Status Indicators Front-panel Green LED (DC OK)
Terminal Screw Size & Torque M2.5 – M2.6 screw terminals; 0.56 N·m (5.0 lb·in) recommended tightening torque
Recommended Wire Gauge & Strip Length 12 – 24 AWG; 4 – 5 mm wire strip length (5 mm maximum)
Cooling Method Natural convection cooling
Mounting Style Standard DIN Rail TS-35/7.5 or TS-35/15
Overall Width (W) 72.0 mm (2.83 in) — 4 DIN Modular Units (4SU)
Overall Height (H) 91.0 mm (3.58 in)
Overall Depth (D) 55.6 mm (2.19 in)
Outer Dimensions (W × H × D) 72.0 × 91.0 × 55.6 mm (2.83 × 3.58 × 2.19 in)
Net Weight 280 g (9.88 oz / 0.62 lbs)
Enclosure Material Flame-retardant polycarbonate (UL94 V-0)
Manufacturer Warranty 3 Years

Industrial Applications & Compatible Systems

TDK-Lambda DRL100-24-1 is engineered for space-constrained industrial, commercial, and building distribution enclosures requiring a reliable 24 VDC bus without protective earth wiring:

  • Building Management & HVAC Distribution Boards: Fits shallow EN 43880 modular consumer units to power DDC controllers, damper actuators, motorized valves, and smart metering gateways.
  • UL508A Industrial Control Panels & Compact PLCs: Supplies regulated 24 VDC power to micro-PLCs, distributed I/O modules, photoelectric sensors, and HMI operator panels in tight machine cabinets.
  • Semiconductor Fab & Test Equipment: SEMI F47 voltage-sag immunity above 200 VAC ensures uninterrupted 24 VDC control rail stability during brief facility power dips.
  • Access Control, Security & Lighting Automation: Class II double-insulated architecture simplifies installation in non-metallic wall boxes for door controllers, relays, and DALI/KNX bus interfaces.

Installation, Thermal Management & MRO Guidelines

Installation & Engineering Guidelines: Mount the DRL100-24-1 upright on a horizontal TS-35/7.5 or TS-35/15 DIN rail with at least 25 mm (1 in) top and bottom clearance for unobstructed natural convection cooling. When operating on 115–240 VAC, maintain ambient enclosure temperatures at or below +51 °C for 100% load (100.8 W), or derate linearly by 2.0 %/°C up to 60% load at +71 °C; for low-line 100–115 VAC operation, begin linear derating above +40 °C down to 40% load at +71 °C. Because the unit has a 60 A cold-start inrush current and lacks internal input fuse replacement access, protect the AC line with a C-curve or D-curve miniature circuit breaker (6 A to 10 A) and strip 12–24 AWG conductors to 4–5 mm before torquing terminals to 0.56 N·m (5.0 lb·in).