HWS100A-48/A TDK-Lambda 101W 48VDC Chassis Power Supply

$137.37

TDK-Lambda HWS100A-48/A (HWS100A48A) 101W 48VDC 2.1A enclosed chassis power supply, 85-265VAC input, active PFC, remote sense, UL 508 & IEC 62368-1.

SKU: HWS100A-48/A Category: Brand:

Description

TDK-Lambda HWS100A-48/A (also known as HWS100A48A) is an ultra-reliable 101W (100.8W) single-output enclosed AC-DC chassis power supply from the flagship industrial HWS-A Series, engineered with conservatively rated electrolytic capacitors to support an industry-unique Limited Lifetime Warranty. Decoding the manufacturer nomenclature, HWS100A denotes the fourth-generation 100W high-reliability industrial platform, -48 specifies the nominal 48 VDC output delivering up to 2.1 A continuous current (front-panel potentiometer adjustable from 38.4 to 52.8 VDC), and the /A suffix designates the factory-installed protective perforated metal cover. Powered by a dual-stage active PFC converter switching at 65 kHz (PFC) / 120 kHz (DC-DC), it accepts a universal 85 to 265 VAC (47–63 Hz) or 120 to 370 VDC input with 300 VAC 5-second surge withstand. The supply achieves up to 90% efficiency at 230 VAC (88% at 115 VAC), tight 192 mV line regulation, 200 mV load regulation, and low 200 mVp-p maximum ripple and noise.

Housed in a slim, convection-cooled aluminum chassis measuring 33.5 × 83 × 160.5 mm (1.32 × 3.27 × 6.32 in) and weighing 470 g (1.04 lbs), the HWS100A-48/A integrates a 7-position M3.5 screw terminal block with dedicated +S / -S remote sense terminals and a green DC OK LED indicator. Comprehensive protection circuits safeguard automation buses via constant-current plus hiccup overload protection (>105% rating) with automatic recovery and latching overvoltage protection (55.2 to 64.8 VDC). Reinforced galvanic isolation withstands 3,000 VAC input-to-output, 2,000 VAC input-to-ground, and 500 VAC output-to-ground while maintaining earth leakage current below 0.5 mA. Certified to UL 508, IEC/EN/UL/CSA 62368-1, SEMI F47, and EN 55011 / EN 55032 Class B EMI, it operates across -10 °C to +70 °C (+14 °F to +158 °F) with 100% full-load output up to +50 °C (+122 °F).

Key Features

  • Precision 48 VDC / 2.1 A Regulated Output: Delivers 100.8 W (101 W rated) continuous power with a wide 38.4 to 52.8 VDC potentiometer trim range, 192 mV line regulation, 200 mV load regulation, and 200 mVp-p max ripple.
  • Active PFC & High Conversion Efficiency: Built-in active power factor correction achieves 0.98 PF at 100 VAC and 0.93 PF at 200 VAC per IEC 61000-3-2 Class A, reaching 88% efficiency at 115 VAC and 90% at 230 VAC.
  • Universal AC/DC Input & Surge Resilience: Operates across 85 to 265 VAC (47–63 Hz) or 120 to 370 VDC, surviving 300 VAC line surges for 5 seconds and delivering a 20 ms typical hold-up time.
  • Remote Voltage Sensing & CC/Hiccup Protection: Standard +S and -S remote sense terminals compensate for cable voltage drops, paired with >105% constant-current/hiccup overload recovery and 55.2–64.8 VDC latching OVP.
  • 3,000 VAC Galvanic Isolation & Industrial Approvals: Provides 3,000 VAC input-to-output and 2,000 VAC input-to-ground dielectric strength, certified to UL 508 industrial control, IEC/EN/UL 62368-1, and SEMI F47 voltage dip standards.
  • Class B EMI Filtering & High-Immunity Design: Meets EN 55011, EN 55032, FCC, and VCCI Class B conducted and radiated emissions without external filters, alongside EN 61000-4-5 ±4 kV surge immunity.
  • Slim 33.5 mm Aluminum Chassis & Lifetime Warranty: Compact 33.5 × 83 × 160.5 mm (1.32 × 3.27 × 6.32 in) enclosed package features side and base M3 mounting points, 2,963,512-hour Telcordia MTBF, and a Limited Lifetime Warranty.

Technical Specifications

Manufacturer TDK-Lambda
Manufacturer Part Number (MPN) HWS100A-48/A
Alternate Part Number HWS100A48A
OEM Cross-Reference / Replaced Part HWS100-48/A (Legacy HWS Series Direct Drop-In Replacement)
Product Series HWS-A Series (HWS15A–150A Family)
Product Category Chassis Power Supplies
Component Type Enclosed Single-Output Industrial AC-DC Power Supply (with Cover /A)
Circuit Topology Active PFC Boost + PWM Switching Mode (SMPS)
Nominal Output Voltage 48 VDC
Output Voltage Adjustment Range 38.4 to 52.8 VDC (-20% to +10% via Front Potentiometer)
Rated Output Current 2.1 A
Output Current Range 0 to 2.1 A (No Minimum Load Required)
Rated Output Power 101 W (100.8 W Continuous)
Number of Outputs 1 Output (Single Channel)
Output Ripple & Noise (Max.) 200 mVp-p
Line Regulation 192 mV max. (85 to 265 VAC input variation)
Load Regulation 200 mV max. (0% to 100% load variation)
Hold-Up Time 20 ms typ. (at 115 / 230 VAC)
Max. Capacitive Load 1,000 µF
AC Input Voltage Range 85 to 265 VAC (300 VAC surge withstand for 5 seconds; Safety certified for 90 to 264 VAC)
DC Input Voltage Range 120 to 370 VDC (Safety certified for AC input only)
Nominal Input Voltage 100 to 240 VAC
Input Frequency Range 47 to 63 Hz (Safety certified for 50 to 60 Hz)
Efficiency (at 115 VAC) 88% typ.
Efficiency (at 230 VAC) 90% typ.
AC Input Current (at 115 VAC) 1.3 A typ. (at 100 VAC full load)
AC Input Current (at 230 VAC) 0.65 A typ. (at 200 VAC full load)
Inrush Current (Cold Start at 115 VAC) 14 A typ. (at 100 VAC cold start)
Inrush Current (Cold Start at 230 VAC) 28 A typ. (at 200 VAC cold start)
Power Factor (PF at 115 VAC) 0.98 typ. (at 100 VAC full load)
Power Factor (PF at 230 VAC) 0.93 typ. (at 200 VAC full load)
Power Factor Correction (PFC) Active PFC (Meets IEC/EN 61000-3-2 Class A)
No-Load Power Consumption 0.3 to 4.6 W (Model Dependent)
Switching Frequency 120 kHz typ. (Main DC-DC Converter) / 65 kHz typ. (Active PFC Converter)
Mounting Style Chassis Mount (4x M3 Embossed, Tapped & Countersunk Holes on Base and Side; Max. 6 mm Screw Penetration)
Cooling Method Free Air Convection
Overall Width (W) 33.5 mm (1.32 in)
Overall Height (H) 83.0 mm (3.27 in)
Overall Depth (D) 160.5 mm (6.32 in) (Excluding 10 mm max. terminal block projection)
Dimensional Tolerance ±1.0 mm (±0.039 in) outer envelope; ±0.5 mm (±0.020 in) mounting hole pitch
Mounting Hole Pitch Side Mounting: 125.0 × 20.5 mm (4.92 × 0.81 in); Base Mounting: 135.0 mm (5.31 in) length pitch
Net Weight 470 g (0.47 kg / 1.04 lbs / 16.58 oz)
Termination / Connector Style 7x M3.5 Screw Terminals with Captive Washer Plates (9.5 mm pitch)
Input Terminal Pinout Front Terminal Block (Bottom Pins): FG (Frame Ground), AC(L) (Live), AC(N) (Neutral)
Output & Signal Terminal Pinout Front Terminal Block (Top Pins): +S (+Remote Sense), +V (+DC Output), -V (-DC Output), -S (-Remote Sense); Shipped with +S to +V and -S to -V shorting bars installed
Control & Monitoring Signals Remote Sense (+S / -S standard); Optional Remote On/Off via JST B2B-XH-AM header on /R suffix models
Status Indicator Green LED (DC OK)
Enclosure / Potting Material Perforated Aluminum Chassis and Protective Cover (/A)
Overload Protection (OLP) Threshold >105% of Rated Output Current
Overload Protection (OLP) Mode Constant Current Limiting combined with Hiccup Mode; Automatic Recovery upon fault removal
Overvoltage Protection (OVP) Threshold 55.2 to 64.8 VDC
Overvoltage Protection (OVP) Mode Latching Shutdown (Cycle AC input power to reset)
Short Circuit Protection (SCP) Continuous Constant Current & Hiccup Mode with Automatic Recovery
Withstand Isolation Voltage (I/P to O/P) 3,000 VAC for 1 minute
Withstand Isolation Voltage (I/P to FG / Case) 2,000 VAC for 1 minute
Withstand Isolation Voltage (O/P to FG / Case) 500 VAC for 1 minute
Isolation Resistance (at 500 VDC) >100 MΩ at 25 °C (77 °F) and 70% RH
Earth Leakage Current <0.5 mA max. (0.2 mA typ. at 100 VAC, 0.4 mA typ. at 230 VAC)
Operating Ambient Temperature Range -10 °C to +70 °C (+14 °F to +158 °F)
Full-Load Operating Temperature Limit +50 °C (+122 °F) at 100% Load (with /A cover)
High-Temperature Derating Rate Derate linearly at 4.0% per °C from 100% load at +50 °C (+122 °F) to 20% load at +70 °C (+158 °F)
Altitude Derating Up to 4,000 m (13,123 ft) maximum operating altitude
Storage Temperature Range -30 °C to +85 °C (-22 °F to +185 °F)
Operating Relative Humidity 30% to 90% RH (Non-condensing)
Storage Relative Humidity 10% to 95% RH (Non-condensing)
Temperature Coefficient ±0.02% / °C
Vibration Resistance 10 to 55 Hz (1 min sweep), 19.6 m/s² (2G) constant acceleration along X, Y, Z axes for 1 hour each (Non-operating); Shock <196 m/s² (20G)
Safety Approvals (UL / North America) UL 508 (Industrial Control Equipment), UL 62368-1, CSA C22.2 No. 62368-1
Safety Approvals (IEC / EN / TÜV) IEC/EN 62368-1
Safety Approvals (Regional / Global) CE Mark, UKCA Mark, SEMI F47 Line Dip Compliant (at >200 VAC input)
EMC Conducted & Radiated Emissions EN 55011 Class B, EN 55032 Class B, FCC Part 15 Class B, VCCI Class B
EMC Harmonic & Flicker Compliance IEC/EN 61000-3-2 Class A
EMC Immunity Standards EN 61000-4-2 (ESD: ±8 kV Air, ±6 kV Contact, Criteria B), EN 61000-4-3 (Radiated RF: 10 V/m 80M–1GHz, Criteria A), EN 61000-4-4 (EFT/Burst: ±2 kV, Criteria B), EN 61000-4-5 (Surge: ±4 kV Common Mode, ±2 kV Normal Mode, Criteria B), EN 61000-4-6 (Conducted RF: 10 Vrms, Criteria A), EN 61000-4-8 (Magnetic Field: 30 A/m, Criteria A), EN 61000-4-11 (Voltage Dips), SEMI F47
MTBF (Telcordia SR-332 / Bellcore) 2,963,512 Hours (Telcordia SR-332 Issue 3, 24V reference model at +55 °C ambient, full load, 230 VAC input)
Environmental Compliance RoHS Compliant, Limited Lifetime Warranty (Americas & EMEA) / 5-Year Warranty (APAC)

Industrial Applications & Compatible Systems

The TDK-Lambda HWS100A-48/A is purpose-built for continuous-duty 48 VDC industrial, semiconductor, and telecom subsystems requiring ultra-long capacitor service life and Class B EMI performance:

  • Factory Automation & UL 508 Control Panels: Powers 48 VDC stepper and brushless DC servo drives, distributed I/O blocks, and PLC backplanes inside high-density industrial machinery cabinets.
  • Semiconductor Fabrication & Wafer Processing Equipment: Certified to SEMI F47 line-dip ride-through standards (at >200 VAC), safeguarding cleanroom metrology, lithography, and robotic wafer-handling controllers against AC grid sags.
  • Telecommunications, PoE & Optical Networking: Provides a low-noise 48 VDC (adjustable 38.4–52.8 VDC) bus for industrial Power-over-Ethernet (PoE) switches, base station transceivers, and fiber-optic distribution frames.
  • Test, Measurement & Automated Inspection Systems: Supplies tightly regulated power with remote voltage sensing to precision ATE racks, vision inspection illuminators, and laboratory instrumentation.

Installation, Thermal Management & MRO Guidelines

Follow these engineering best practices during cabinet integration and MRO replacement of the HWS100A-48/A:

  • Chassis Screw Penetration & Mounting Clearance: Secure the aluminum chassis using the embossed M3 tapped holes on the side (125 × 20.5 mm pitch) or bottom (135 mm pitch), ensuring customer M3 mounting screws never protrude more than 6.0 mm (0.24 in) into the power supply enclosure.
  • Convection Thermal Derating Above +50 °C: Maintain unrestricted airflow around the perforated /A cover for 100% full-load operation (2.1 A / 101 W) up to +50 °C (+122 °F); above +50 °C, derate continuous output load linearly at 4.0% per °C down to 20% load (0.42 A) at +70 °C (+158 °F).
  • Remote Sense Wiring & Parallel Prohibition: Leave the factory-mounted shorting links between +S/+V and -S/-V installed for local voltage regulation, or remove them to connect twisted-pair sense leads directly at the load terminals; never wire multiple HWS100A-48/A outputs directly in parallel without external ORing diodes.