Description
TDK-Lambda DRL30-24-1 (also known as DRL30241) is a 30W single-phase, low-profile step-shape DIN rail AC-DC power supply from the DRL10-100 Series, engineered for space-constrained building automation and industrial distribution panels. The MPN decodes the 30W power frame (DRL30), 24VDC nominal output voltage adjustable via front potentiometer from 24 to 28VDC, and standard terminal block configuration (-1). Delivering up to 1.25A continuous output current from a universal 85 to 264VAC (47–63Hz) or 120 to 373VDC input, it achieves up to 90% efficiency at 230VAC (88% at 115VAC) and consumes less than 0.3W under no-load conditions. Safety Class II double-insulated construction eliminates the need for a protective earth ground wire while maintaining low 240mV ripple and noise.
Comprehensive protection safeguards downstream loads with hiccup-mode auto-recovery overcurrent protection above 105% rated load and latching/auto-recovering overvoltage protection between 29 and 35VDC. Reinforced galvanic isolation provides 3,000VAC input-to-output withstand voltage and greater than 100MΩ insulation resistance. Convection-cooled in a compact 2-SU (36mm wide) UL94 V-0 flame-retardant polycarbonate enclosure measuring 36 × 91 × 55.6 mm (1.42 × 3.58 × 2.19 in), it supports -25°C cold start-up and full-load operation up to +55°C (derating linearly to 60% at +71°C). Certified to UL 508 Listed, UL 1310 NEC Class 2, and IEC/UL/CSA/EN 62368-1, it mounts directly onto TS-35/7.5 or TS-35/15 DIN rails.
Key Features
- High Conversion Efficiency & Low Standby Draw: Achieves 90% efficiency at 230VAC (88% at 115VAC) with under 0.3W no-load consumption, minimizing enclosure heat dissipation and continuous energy waste.
- Safety Class II Double-Insulated Input: Operates across 85–264VAC (47–63Hz) and 120–373VDC without requiring a protective earth ground connection, simplifying two-wire residential and commercial panel wiring.
- UL 1310 NEC Class 2 Compliant Output: Delivers 24VDC (adjustable 24–28VDC) at 1.25A (30W) with inherent fault-current limiting, meeting strict NEC Class 2 building automation and low-voltage safety codes.
- Ultra-Slim 36mm Low-Profile Step Housing: Compact 36 × 91 × 55.6 mm (2-SU modular width) UL94 V-0 polycarbonate case fits shallow wall-mounted breaker boxes and standard TS-35 DIN rails.
- Wide Operating Temperature & Cold Start: Supports -25°C cold start-up and full 30W output from -20°C to +55°C under natural convection, linearly derating to 60% load up to +71°C.
- Comprehensive Fault Protection & 3kVAC Isolation: Features >105% hiccup auto-recovery overcurrent protection, 29–35VDC overvoltage protection, and 3,000VAC reinforced input-to-output dielectric withstand.
- Industrial EMC & SEMI F47 Immunity: Complies with EN 55032 Class B conducted emissions, IEC 61000-4-2 through -11 Class 3 industrial immunity, and SEMI F47 line-dip ride-through above 200VAC.
Technical Specifications
| Manufacturer | TDK-Lambda |
|---|---|
| Manufacturer Part Number (MPN) | DRL30-24-1 |
| Alternate Part Number | DRL30241 |
| Product Series | DRL10-100 Series (DRL30 Frame) |
| Product Category | Low-Profile DIN Rail |
| Component Type | Single-Phase Step-Shape AC-DC DIN Rail Power Supply |
| Circuit Topology | Isolated Flyback / Quasi-Resonant Switched-Mode (Class II Double Insulated) |
| Nominal Output Voltage | 24 VDC |
| Output Voltage Adjustment Range | 24 to 28 VDC (via front-panel potentiometer) |
| Rated Output Current | 1.25 A |
| Output Current Range | 0 to 1.25 A (No minimum load required) |
| Rated Output Power | 30 W |
| Output Ripple & Noise (Max) | 240 mVp-p |
| Line Regulation | 240 mV |
| Load Regulation | 240 mV |
| Temperature Coefficient | < ±0.02 %/°C |
| Hold-Up Time (at 115 VAC) | 20 ms (Typical) |
| Parallel & Series Operation | Series operation possible (see manual); Parallel operation not available |
| Input Voltage Range (AC) | 85 to 264 VAC (Single-Phase, Safety Certified) |
| Input Voltage Range (DC) | 120 to 373 VDC (Not safety certified for DC input) |
| Input Frequency Range | 47 to 63 Hz |
| Input Surge Withstand | 300 VAC for 5 seconds |
| Efficiency (at 115 VAC) | 88 % |
| Efficiency (at 230 VAC) | 90 % |
| Average Active Efficiency | 83.6 % (Measured at 25%, 50%, 75%, and 100% load) |
| AC Input Current (at 110 VAC) | 0.6 A |
| AC Input Current (at 230 VAC) | 0.4 A |
| Inrush Current (Cold Start at 230 VAC) | 50 A (Typical) |
| Power Factor (at 115 VAC) | 0.6 |
| Power Factor (at 230 VAC) | 0.4 |
| No-Load Power Consumption | < 0.3 W |
| Switching Frequency (at 230 VAC, 100% Load) | 96.9 to 103.8 kHz |
| Overload / Overcurrent Protection (OLP) Threshold | > 105 % of rated output current |
| Overload / Overcurrent Protection (OLP) Mode | Hiccup mode with automatic recovery |
| Overvoltage Protection (OVP) Threshold | 29 to 35 VDC |
| Safety Insulation Class | Class II Double Insulation (No protective earth connection required) |
| Withstand Isolation Voltage (I/P to O/P) | 3,000 VAC (for 1 minute) |
| Isolation Resistance (at 500 VDC) | > 100 MΩ (at 25 °C, 70% RH, 500 VDC) |
| Operating Ambient Temperature | -20 °C to +71 °C (-4 °F to +159.8 °F) |
| Cold Start-Up Temperature | -25 °C (-13 °F) |
| Full-Load Operating Temperature Limit | +55 °C (+131 °F) at 100% load (30 W) |
| High-Temperature Derating Rate | Linear derating from +55 °C to +71 °C down to 60% load (18 W / 2.5 %/°C) |
| Storage Temperature Range | -40 °C to +85 °C (-40 °F to +185 °F) |
| Operating Humidity Range | 5 % to 95 % RH (Non-condensing) |
| Operating Altitude | Up to 3,000 m (9,842 ft) |
| Vibration Resistance (Operating) | IEC 60068-2-6, Sine wave 10–500 Hz, 19.6 m/s² (2G peak), 10 min/cycle, 60 min across X, Y, Z axes |
| Mechanical Shock Resistance | IEC 60068-2-27, Half-sine wave 39.2 m/s² (4G), 22 ms duration, 3 shocks per axis (9 total) |
| MTBF (Telcordia SR-332 Issue 3) | 704,390 Hours (at +55 °C ambient, full load, 230 VAC input) |
| Safety Approvals (North America) | UL 508 Listed, UL 1310 NEC Class 2, UL/CSA 62368-1, UL/CSA 60950-1 |
| Safety Approvals (International / Europe) | IEC/EN 62368-1, IEC/EN 60950-1, CE Mark |
| EMC Conducted Emissions | EN 55032 Class B |
| EMC Radiated Emissions | EN 55032 Class A |
| EMC Harmonic Current Emissions | IEC 61000-3-2 Class A |
| EMC ESD Immunity (EN 61000-4-2) | Level 3, Performance Criteria A (8 kV air discharge) |
| EMC Radiated RF Immunity (EN 61000-4-3) | Level 3, Performance Criteria A |
| EMC EFT / Burst Immunity (EN 61000-4-4) | Level 4, Performance Criteria A |
| EMC Surge Immunity (EN 61000-4-5) | Level 3, Performance Criteria A |
| EMC Conducted RF Immunity (EN 61000-4-6) | Level 3, Performance Criteria A |
| EMC Magnetic Field Immunity (EN 61000-4-8) | Level 4, Performance Criteria A |
| EMC Voltage Dips & Interruptions (EN 61000-4-11) | Class 3 Industrial: 0% for 1 cycle (Criteria A); 40% for 10/12 cycles, 70% for 25/30 cycles, 80% for 250/300 cycles (Criteria B) |
| Semiconductor Voltage Sag Immunity | SEMI F47 Compliant (at > 200 VAC input) |
| Status Indicators | Front-panel Green LED (DC OK) |
| Terminal Screw Type & Torque | M2.5 – M2.6 captive screw terminals, 0.56 N·m (5.0 lb·in) recommended torque |
| Recommended Wire Gauge & Strip Length | 24 to 12 AWG solid/stranded wire; 4 to 5 mm (5 mm max) strip length |
| Cooling Method | Natural Free-Air Convection |
| Mounting Style | DIN Rail Mount (TS-35/7.5 or TS-35/15) |
| Overall Width (W) | 36 mm (1.42 in / 2 SU modular width) |
| Overall Height (H) | 91 mm (3.58 in) |
| Overall Depth (D) | 55.6 mm (2.19 in) |
| Overall Dimensions (W × H × D) | 36 × 91 × 55.6 mm (1.42 × 3.58 × 2.19 in) |
| Net Weight | 120 g (4.23 oz / 0.265 lbs) |
| Enclosure Material & Flammability | Flame-Retardant Polycarbonate, UL 94 V-0 |
| Manufacturer Warranty | 3 Years |
Industrial Applications & Compatible Systems
TDK-Lambda DRL30-24-1 provides compact, NEC Class 2 compliant 24VDC auxiliary power across commercial building panels and industrial automation enclosures:
- Building Automation & HVAC Distribution Panels: Powers DDC controllers, smart thermostats, damper actuators, and access control hubs inside shallow DIN distribution cabinets where its 2-SU step profile and Class II double insulation eliminate protective earth wiring.
- UL 508A Industrial Control Cabinets & Micro-PLCs: Supplies regulated 24VDC bus power to compact programmable logic controllers, remote I/O slices, photoelectric sensors, and panel-mount pilot relays.
- Semiconductor Wafer Handling & Metrology Tools: Delivers SEMI F47 compliant 24VDC control power (at >200VAC input) for auxiliary valve manifolds, interlock relays, and status indicators in fab sub-panels.
- Security, Intercom & PoE-Adjacent Edge Nodes: Feeds low-voltage door strikes, card readers, and industrial Ethernet media converters requiring UL 1310 Class 2 current-limited fault protection.
Installation, Thermal Management & MRO Guidelines
Installation & Engineering Guidelines: Mount the DRL30-24-1 vertically on standard TS-35/7.5 or TS-35/15 DIN rails with input terminals at the bottom and output terminals at the top to preserve natural convection airflow, leaving at least 25 mm clearance above and below the vented polycarbonate housing. Because the unit has a 50A typical cold-start inrush current at 230VAC, protect the upstream AC line with a 2A to 6A Type C miniature circuit breaker (MCB) or slow-blow fuse. For enclosure ambient temperatures exceeding +55°C, linearly derate continuous output power by 2.5%/°C down to 18W (0.75A) at the +71°C maximum limit.