Description
TDK-Lambda D1SE480-48-A4 (also known as D1SE48048A4) is an industrial single-phase DIN rail AC-DC power supply from the D1SE480 series, where the -48 suffix specifies a regulated 48 VDC output and -A4 designates the integrated green DC-OK status LED and isolated DC-OK relay contact option without conformal board coating. Engineered with a high-efficiency active PFC and load-dependent resonant switching topology (114 to 209 kHz), it accepts a wide 85 to 264 VAC single-phase input (90 to 264 VAC safety certified, 300 VAC surge withstand for 30 seconds) as well as a 110 to 250 VDC nominal DC bus input. The unit delivers a continuous 48 VDC at 10 A (480 W) with a front-panel voltage adjustment range of 45 to 57 VDC, alongside a 125% peak boost capability of 12.5 A (600 W) for up to 200 seconds to absorb high-inrush capacitive and inductive motor or solenoid loads, achieving up to 95.1% conversion efficiency at 240 VAC and ultra-low 45 mVpp ripple and noise.
Comprehensive fault protection includes auto-recovery overcurrent, overvoltage, and overtemperature safeguards, backed by three-zone galvanic isolation rated at 5,000 VDC input-to-output, 3,100 VDC input-to-ground, and 750 VDC output-to-ground. Cooled by natural convection inside a slim 60 × 125 × 129 mm (2.36 × 4.92 × 5.08 in) IP20 aluminum enclosure weighing 900 g, the D1SE480-48-A4 operates reliably from -25 °C to +70 °C (-40 °C cold start-up, full load up to +55 °C above 108 VAC) on standard TS-35/7.5 or TS-35/15 DIN rails. Tool-free push-in wire terminations streamline cabinet assembly, while global safety and EMC compliance—including IEC/UL/EN 61010-2-201, IEC/UL/EN 62368-1 Ed.3, SEMI F47-0706, EN 61000-4-x Criterion A immunity, CE, UKCA, and BIS—ensures seamless deployment across global industrial automation systems.
Key Features
- High-Power 48 VDC Output with 200-Second Peak Boost: Delivers 48 VDC at 10 A (480 W) continuously, adjustable from 45 to 57 VDC, plus 12.5 A (600 W) peak boost for 200 seconds.
- Universal AC & High-Voltage DC Input Flexibility: Operates across 85 to 264 VAC (90 to 264 VAC safety certified, 300 VAC 30 s surge) and 110 to 250 VDC (+20%/-15%) industrial DC buses.
- Up to 95.1% Conversion Efficiency & Active PFC: Achieves 95.1% efficiency at 240 VAC (93.3% at 120 VAC), 0.95 power factor, and 0.8 W no-load power consumption to minimize cabinet heat.
- Ultra-Low Inrush Energy & Push-In Terminations: Limits cold-start inrush energy below 0.6 A²s (20 A at 240 VAC) to prevent upstream MCB tripping while cutting wiring time with tool-free push-in terminals.
- Integrated DC-OK LED & Relay Monitoring (-A4 Option): Features a front green DC-OK indicator LED and isolated normally-open relay contact (rated 24 V / 1 A) for remote PLC fault diagnostics.
- Reinforced 5,000 VDC Isolation & Auto-Recovery Protections: Provides 5,000 VDC input-to-output dielectric withstand alongside auto-recovery overcurrent, overvoltage, and overtemperature protection for unattended industrial uptime.
- Wide -25 °C to +70 °C Industrial Operating Range: Supports -40 °C cold start-up and full-load convection operation up to +55 °C without fans, housed in a compact 60 mm wide IP20 aluminum chassis.
- Global Control Panel & Semiconductor Standards: Certified to IEC/UL/EN 61010-2-201, IEC/UL/EN 62368-1 Ed.3, BIS, CE, UKCA, EN 61000-4-x Criterion A immunity, and SEMI F47-0706 voltage sag compliance.
Technical Specifications
| Manufacturer | TDK-Lambda |
|---|---|
| Manufacturer Part Number (MPN) | D1SE480-48-A4 |
| Alternate Part Number | D1SE48048A4 |
| Product Series | D1SE480 Series (D1SE120 – D1SE480 Family) |
| MPN Option Suffix Decoding | -48: 48 VDC Output; -A4: Green DC-OK Status LED & Closed Contact Relay (No Conformal Coating) |
| Product Category | Redundancy Modules |
| Component Type | Single-Phase AC-DC / DC-DC DIN Rail Power Supply |
| Circuit Topology | Active PFC + Variable-Frequency Resonant Switching Converter (114 to 209 kHz) |
| Nominal Output Voltage | 48 VDC |
| Output Voltage Adjustment Range | 45 to 57 VDC (via Front-Panel Potentiometer) |
| Rated Output Current | 10 A |
| Output Current Range | 0 to 10 A (No Minimum Load Required) |
| Rated Output Power | 480 W |
| Peak (Boost) Output Current | 12.5 A (for up to 200 seconds) |
| Peak (Boost) Output Power | 600 W (125% Boost for up to 200 seconds) |
| Output Ripple & Noise | 45 mVpp max (-10 °C to +70 °C ambient) |
| Line Regulation | 0.02% |
| Load Regulation | 0.25% |
| Maximum Capacitive Load | 7,670 µF continuous (20,000 µF start-up) |
| Hold-Up Time (at 230 VAC) | 25 ms (at 25 °C ambient, full load) |
| AC Input Voltage Range | 85 to 264 VAC (100 to 240 VAC nominal; 90 to 264 VAC safety certified) |
| Input Surge Voltage Withstand | 300 VAC for 30 seconds |
| AC Input Frequency | 50 / 60 Hz (Safety Certified) |
| DC Input Voltage Range | 110 to 250 VDC nominal (+20% / -15%, 93.5 to 300 VDC; external DC fuse required) |
| Maximum AC Input Current | 5.6 A max |
| Cold-Start Inrush Current (at 100 VAC) | 9 A (Peak Inrush Energy less than 0.6 A²s) |
| Cold-Start Inrush Current (at 120 VAC) | 11 A (Peak Inrush Energy less than 0.6 A²s) |
| Cold-Start Inrush Current (at 240 VAC) | 20 A (Peak Inrush Energy less than 0.6 A²s) |
| Efficiency (at 100 VAC) | 92.0% (at 25 °C ambient, full load) |
| Efficiency (at 120 VAC) | 93.3% (at 25 °C ambient, full load) |
| Efficiency (at 240 VAC) | 95.1% (at 25 °C ambient, full load) |
| Power Factor (at 230 VAC) | 0.95 |
| No-Load Power Consumption | 0.8 W |
| Output Converter Switching Frequency | 114 to 209 kHz (load dependent) |
| Overcurrent / Overload Protection (OLP) Threshold | 12.5 A min (125% peak boost current threshold) |
| Overcurrent / Overload Protection (OLP) Mode | Auto-Recovery |
| Overvoltage Protection (OVP) Mode | Auto-Recovery |
| Overtemperature Protection (OTP) Mode | Auto-Recovery |
| Protection Insulation Class | Class I (with Protective Earth Ground Connection) |
| Withstand Isolation Voltage (Input to Output) | 5,000 VDC (for 1 minute) |
| Withstand Isolation Voltage (Input to Ground / FG) | 3,100 VDC (for 1 minute) |
| Withstand Isolation Voltage (Output to Ground & Signals) | 750 VDC (for 1 minute) |
| Maximum Earth Leakage Current | 0.55 mA max |
| Operating Ambient Temperature Range | -25 °C to +70 °C (-13 °F to +158 °F); Cold Start-Up down to -40 °C (-40 °F) |
| Full-Load Operating Temperature Limit | +55 °C (+131 °F) at greater than 108 VAC input |
| Thermal & Low-Line Derating Conditions | Linear output power derating required above +55 °C (+131 °F) up to +70 °C (+158 °F) and below 108 VAC input |
| Storage Temperature Range | -40 °C to +85 °C (-40 °F to +185 °F) |
| Operating & Storage Humidity | Up to 95% RH max (non-condensing) |
| Operating Altitude | 3,000 m (9,842 ft) nominal; 6,000 m (19,685 ft) max without UL certification |
| Vibration Resistance (Non-Operating) | IEC 60068-2-6: 2g, 10 to 500 Hz, 1 hour per axis (X, Y, Z) |
| Shock Resistance (Non-Operating) | 30g / 11 ms (±5 ms), 3 bumps per direction, 9 bumps total |
| Safety Certifications & Agency Approvals | IEC/UL/EN 61010-2-201, IEC/UL/EN 62368-1 Ed.3, BIS, CE Mark, UKCA Mark |
| Conducted & Radiated EMI Environment | Residential, Commercial, and Light-Industrial Environments |
| Harmonic Current Emissions | EN 61000-3-2 Class A |
| ESD Immunity (EN 61000-4-2) | Criterion A: 4 kV Contact Discharge / 8 kV Air Discharge |
| Radiated RF Immunity (EN 61000-4-3) | Criterion A: 10 V/m (80 MHz to 1 GHz), 3 V/m (1.4 GHz to 6 GHz) |
| EFT / Burst Immunity (EN 61000-4-4) | Criterion A: 2 kV Input, 1 kV Output, 1 kV Signal |
| Surge Immunity (EN 61000-4-5) | Criterion A: 2 kV Symmetrical (L-L) & 4 kV Asymmetrical (L-PE) Input/Output; 1 kV Signal-PE |
| Conducted RF Immunity (EN 61000-4-6) | Criterion A: 10 V/m (80 MHz to 1 GHz) |
| Power Frequency Magnetic Field Immunity (EN 61000-4-8) | Criterion A: 30 A/m at 50 Hz, 60 s per axis (X, Y, Z) |
| Voltage Dips & Interruptions (EN 61000-4-11 / -4-34) | Criterion A: 500 ms, 200 ms, 20 ms; Criterion C: 5,000 ms |
| Semiconductor Voltage Sag Immunity (SEMI F47-0706) | Criterion A: 1,000 ms, 500 ms, 200 ms, 20 ms |
| DC Good (DC-OK) Signal Output | Isolated Closed-Contact Relay Output (Rated 24 VDC / 1 A max) |
| Front-Panel Status Indicator | Green LED Indicates DC Output is OK |
| Remote Sense / Remote On-Off / Parallel Operation | None (Parallel Operation Not Supported; Use External DRM40 Redundancy Module) |
| Input Terminal Pinout & Style | Tool-Free Push-In Spring Terminals: L / +, N / -, Protective Earth (PE) |
| Output & Signal Terminal Pinout & Style | Tool-Free Push-In Spring Terminals: Dual +V, Dual -V, and 2-Pin DC-OK Relay Contact |
| Cooling Method | Natural Convection (Fanless) |
| Mounting Style | DIN Rail Mount (TS-35/7.5 or TS-35/15 Standard Rails) |
| Ingress Protection Rating | IP20 |
| Overall Width (W) | 60.0 mm (2.36 in) |
| Overall Height (H) | 125.0 mm (4.92 in) |
| Overall Depth / Length (D) | 129.0 mm (5.08 in) nominal; 129.2 mm (5.09 in) max including DIN rail latch |
| Overall Dimensions (W × H × D) | 60 × 125 × 129 mm (2.36 × 4.92 × 5.08 in) |
| Net Weight | 900 g (1.98 lbs / 31.75 oz) |
| Enclosure Material | Aluminum |
| Manufacturer Warranty | 3 Years |
Industrial Applications & Compatible Systems
TDK-Lambda D1SE480-48-A4 provides high-efficiency 48 VDC bus power and 600 W peak boost capacity for space-constrained industrial control cabinets and automated machinery:
- Industrial Automation & Factory Control Panels: Powers 48 VDC distributed I/O manifolds, stepper and brushless DC servo drives, and solenoid valve banks requiring 12.5 A peak start-up current.
- Semiconductor Wafer Fabrication & Process Tools: Meets SEMI F47-0706 voltage sag immunity (Criterion A down to 20 ms) for sensitive 48 VDC wafer-handling robotics, mass flow controllers, and chamber instrumentation.
- Telecom, PoE++ & Industrial Networking Cabinets: Supplies low-ripple (45 mVpp) 48 VDC power with front-panel adjustment up to 57 VDC for industrial PoE++ switches, wireless base stations, and optical transport nodes.
- Building Management, HVAC & Security Systems: Supports residential, commercial, and light-industrial EMC requirements for 48 VDC motorized dampers, access control panels, and emergency lighting controllers.
Installation, Thermal Management & MRO Guidelines
Installation & Engineering Guidelines: Mount the D1SE480-48-A4 vertically onto a standard TS-35/7.5 or TS-35/15 DIN rail with unobstructed top and bottom airflow clearances to maintain natural convection cooling. For full 480 W continuous output without derating, keep ambient cabinet temperature at or below +55 °C (+131 °F) and AC line voltage above 108 VAC; derate output power linearly when operating between +55 °C and +70 °C or under low-line conditions (85 to 108 VAC). Although cold-start inrush energy is limited below 0.6 A²s (20 A peak at 240 VAC), protect the AC line with a 10 A B-curve or C-curve MCB (or install an external DC-rated fuse when feeding from a 110 to 250 VDC bus). Do not wire outputs directly in parallel; use an external TDK-Lambda DRM40 redundancy module for N+1 fault-tolerant architectures.