Description
WAGO 787-1602 (also known as 7871602) is an industrial single-phase switched-mode DIN rail power supply from the EPSITRON® Classic (787-16xx) series, engineered for high-density control cabinets requiring NEC Class 2 / Limited Power Source (LPS) compliance. Operating across a universal input range of 85 to 264 VAC (44 to 66 Hz) and 120 to 300 VDC, the unit delivers a tightly regulated 24 VDC nominal output (adjustable from 23 to 28.5 VDC) at 1 A rated current (up to 1.2 A below 24 VDC) for 24 W of continuous power. Its primary-switched conversion topology achieves 86% typical efficiency with low power dissipation (≤ 4 W at 230 VAC nominal load and ≤ 1 W at no-load), maintaining output voltage deviation within ≤ 1% and residual ripple below 20 mVp-p. Integrated bounce-free active DC OK signaling (24 VDC, 20 mA) and a front-panel green status LED provide immediate diagnostics to PLC inputs.
Housed in an ultra-slim 22.5 × 90 × 107.5 mm (0.886 × 3.543 × 4.232 in) encapsulated IP20 enclosure weighing just 128 g (4.52 oz), the 787-1602 mounts directly onto standard DIN-35 rails and utilizes pluggable WAGO 721 Series CAGE CLAMP® terminals (28 to 12 AWG) for vibration-proof maintenance. Comprehensive circuit protection includes constant-current overload limiting (1.1 × Io nom typ.), secondary overvoltage protection clamped at ≤ 39 VDC, continuous short-circuit and open-circuit immunity, and reverse-feed resistance up to 35 VDC for safe series or parallel operation. The supply features 4.242 kVDC primary-to-secondary galvanic isolation (Protection Class II, SELV/PELV) and operates from -25 °C to +70 °C (-13 °F to +158 °F) with type-tested cold startup at -40 °C (-40 °F) and full-load convection cooling up to +50 °C (+122 °F). Global compliance spans UL 508, UL 60950-1, EN 61010-1 / -2-201, SEMI F47, and DNV marine certification.
Key Features
- NEC Class 2 Regulated 24 VDC Output: Delivers 24 VDC nominal (adjustable 23 to 28.5 VDC) at 1 A continuous current (24 W) with ≤1% deviation and ultra-low ≤20 mVp-p residual ripple for sensitive automation loads.
- Wide Universal AC & DC Input Range: Accepts 85 to 264 VAC (44 to 66 Hz) and 120 to 300 VDC input with 86% typical efficiency, passive PFC, and up to 120 ms hold-up time at 230 VAC.
- Active Bounce-Free DC OK Signal: Provides an integrated 24 VDC / 20 mA active transistor status output alongside a high-visibility green LED indicator for direct PLC power monitoring and rapid fault diagnostics.
- Pluggable WAGO 721 CAGE CLAMP® Terminals: Equipped with maintenance-free spring pressure connectors accommodating 0.08 to 2.5 mm² (28 to 12 AWG) solid or fine-stranded conductors for fast pre-wiring and tool-assisted replacement.
- Ultra-Slim 22.5 mm Encapsulated Footprint: Occupies just 22.5 mm (0.886 in) of horizontal DIN-35 rail width and 107.5 mm (4.232 in) cabinet depth, maximizing panel density in compact junction boxes and distributed I/O stations.
- Reinforced 4.242 kVDC Class II Isolation: Features double/reinforced primary-to-secondary galvanic isolation rated at 4.242 kVDC without requiring a protective earth connection, satisfying SELV (UL 60950-1) and PELV (EN 60204) safety mandates.
- Extreme -40 °C Cold-Start & Thermal Resilience: Rated for -25 °C to +70 °C ambient operation with verified -40 °C cold-start capability, delivering 100% rated load up to +50 °C and linear -3%/K derating above +50 °C.
- Industrial, Semiconductor & Marine Approvals: Certified to UL 508, UL 60950-1, EN 61010-2-201, SEMI F47 voltage sag immunity, and DNV marine standards (EMC 1 capable with WAGO 787-980 filter module).
Technical Specifications
| Manufacturer | WAGO |
|---|---|
| Manufacturer Part Number (MPN) | 787-1602 |
| Alternate Part Number | 7871602 |
| Compatible Equipment / Series | WAGO I/O System 750/753, WAGO 787-980 Filter Module, WAGO 721 Series Connectors |
| Product Series | EPSITRON® Classic (787-16xx Series) |
| Product Category | Single-Phase DIN Rail |
| Component Type | AC-DC Single-Phase DIN Rail Switched-Mode Power Supply (NEC Class 2 / LPS) |
| Circuit Topology | Switched-Mode Power Supply (SMPS), Primary-Switched, Protection Class II, SELV / PELV |
| Nominal Output Voltage | 24 VDC (Default Setting: 24 VDC, SELV / PELV) |
| Output Voltage Adjustment Range | 23 to 28.5 VDC (via front-panel potentiometer) |
| Rated Output Current | 1 A (at 24 VDC); 1.2 A (at < 24 VDC) |
| Rated Output Power | 24 W (NEC Class 2 Limited Power Source) |
| Number of Outputs | 1 (Single Output, Series & Parallel Operation Capable) |
| Output Ripple & Noise (Max.) | ≤ 20 mVp-p (Residual Ripple) |
| Output Voltage Tolerance | ≤ 1 % (Total Deviation) |
| Hold-Up Time (at 115 VAC) | ≥ 20 ms (at 100 VAC full load) |
| Hold-Up Time (at 230 VAC) | ≥ 120 ms (at 230 VAC full load) |
| AC Input Voltage Range | 85 to 264 VAC (Single-Phase) |
| DC Input Voltage Range | 120 to 300 VDC (External DC pre-fuse required) |
| Nominal Input Voltage | 100 to 240 VAC |
| Input Frequency Range | 44 to 66 Hz; 0 Hz (DC operation) |
| Efficiency | 86 % (Typical); Power Loss: ≤ 4 W (at 230 VAC nominal load), 5 W Max. (at 100 VAC / 24 VDC, 1 A) |
| AC Input Current (at 115 VAC) | ≤ 0.49 A (at 100 VAC) |
| AC Input Current (at 230 VAC) | ≤ 0.28 A (at 240 VAC) |
| Inrush Current (Cold Start at 230 VAC) | ≤ 30 A (across full input range) |
| Power Factor Correction (PFC) | Passive |
| No-Load Power Consumption | ≤ 1 W |
| Mounting Style | DIN-35 Rail (EN 60715 Horizontal Mounting) |
| Cooling Method | Natural Free Air Convection (when horizontally mounted) |
| Overall Width (W) | 22.5 mm (0.886 in) |
| Overall Height (H) | 90 mm (3.543 in) |
| Overall Depth (D) | 107.5 mm (4.232 in) from upper-edge of DIN rail |
| Net Weight | 128 g (0.282 lbs / 4.52 oz) |
| Termination / Connector Style | Pluggable WAGO 721 Series CAGE CLAMP® Spring Pressure Connectors |
| Input Terminal Pinout | Front Pluggable Terminal Block: L (Line), N (Neutral) |
| Output & Signal Terminal Pinout | Front Pluggable Terminal Block: DC+ (Positive Output), DC- (Negative Output), DC OK (Active Signal Output) |
| Control & Monitoring Signals | 1 × Active Bounce-Free DC OK Signal Output (24 VDC, 20 mA Max.) |
| Status Indicator | 1 × Green LED (Uo / DC OK Operation Status) |
| Terminal Wire Gauge Range | 0.08 to 2.5 mm² / 28 to 12 AWG (Solid and Fine-Stranded Conductors); Strip Length: 8 to 9 mm (0.31 to 0.35 in) |
| Enclosure / Potting Material | Encapsulated Industrial Control Cabinet Housing |
| Overload Protection (OLP) Threshold | 1.1 × Io nom (Typical); Internal Primary Fuse: T 2 A / 250 VAC; Recommended Backup MCB: 6 A, 10 A, or 16 A (Type B or C) |
| Overload Protection (OLP) Mode | Constant Current Limiting with Automatic Recovery |
| Overvoltage Protection (OVP) Threshold | ≤ 39 VDC (Secondary Internal Protective Circuit in Event of Fault); Primary Varistor Transient Suppression |
| Short Circuit Protection (SCP) | Continuous Short-Circuit Protected and Open-Circuit Proof |
| Reverse Polarity Protection | Resistance to Reverse Feed ≤ 35 VDC |
| Withstand Isolation Voltage (I/P to O/P) | 4.242 kVDC (Protection Class II, Overvoltage Category II, Pollution Degree 2) |
| Earth Leakage Current | ≤ 0.25 mA (Discharge Current) |
| Operating Ambient Temperature Range | -25 °C to +70 °C (-13 °F to +158 °F); Cold-Start Type-Tested at -40 °C (-40 °F) |
| Full-Load Operating Temperature Limit | +50 °C (+122 °F) |
| High-Temperature Derating Rate | -3 %/K above +50 °C (+122 °F) up to +70 °C (+158 °F) |
| Low-Line Input Derating | -2.5 %/V below 95 VAC (85 to 95 VAC) |
| Storage Temperature Range | -25 °C to +85 °C (-13 °F to +185 °F) |
| Operating Relative Humidity | 5 % to 96 % RH (Non-Condensing) |
| Climatic Category (IEC 60068-1) | 3K3 (per EN 60721) |
| Ingress Protection (IP) | IP20 (per EN 60529) |
| Safety Approvals (UL / North America) | UL 508 (File E255817), UL 60950-1 (UR File E255815), NEC Class 2 / Limited Power Source (LPS) |
| Safety Approvals (IEC / EN / TÜV) | EN 61010-1, EN 61010-2-201, EN 60335-1, PELV (per EN 60204) |
| Safety Approvals (Regional / Global) | DNV Marine (DNVGL-CG-339, Certificate TAA00002YC), SEMI F47, EAC (TP TC 004/2011, TP TC 020/2011), CE |
| EMC Conducted & Radiated Emissions | EN 61204-3; DNV Marine EMC 1 Compliant (in conjunction with WAGO 787-980 Filter Module) |
| EMC Immunity Standards | EN 61204-3 Low-Voltage Power Supply EMC Immunity, SEMI F47 Voltage Sag Immunity |
| MTBF (MIL-HDBK-217F) | > 500,000 Hours (per IEC 61709) |
| Environmental Compliance | RoHS Compliant (No Exemption), Country of Origin: Germany (DE), GTIN: 4055143060417 |
Industrial Applications & Compatible Systems
The WAGO 787-1602 is purpose-built for space-constrained industrial automation panels, marine bridge systems, and NEC Class 2 low-voltage control loops:
- Distributed PLC & Fieldbus I/O Nodes: Powers WAGO I/O System 750/753 couplers, remote Ethernet/IP and PROFINET fieldbus nodes, and compact micro-PLCs requiring NEC Class 2 current-limited 24 VDC rails.
- Semiconductor Wafer & Cleanroom Equipment: Meets SEMI F47 AC voltage sag immunity and ≥120 ms hold-up time (at 230 VAC) to prevent process controller resets during utility power dips.
- Marine, Offshore & Shipboard Automation: Certified to DNV (DNVGL-CG-339) standards for engine room monitoring panels, and upgradeable to bridge-zone EMC 1 compliance when paired with the WAGO 787-980 filter module.
- Sensor, Actuator & Safety Relay Loops: Supplies low-ripple (≤20 mVp-p) SELV/PELV power to photoelectric sensors, inductive proximity switches, HMI displays, and bounce-free PLC diagnostic inputs.
Installation, Thermal Management & MRO Guidelines
Ensure long-term reliability and code compliance in control cabinet installations by observing these engineering best practices:
- Thermal Convection & Derating Management: Mount horizontally on a standard DIN-35 rail to support natural convection cooling; maintain full 1 A (24 W) load up to +50 °C (+122 °F) and derate output load by -3%/K from +50 °C to +70 °C (+158 °F) and -2.5%/V below 95 VAC.
- Upstream Branch & DC Input Protection: Protect the AC input using an external 6 A, 10 A, or 16 A circuit breaker (Type B or C tripping characteristic) sized for the ≤30 A cold-start inrush current, and install an external DC-rated pre-fuse when operating from a 120 to 300 VDC bus.
- Pluggable CAGE CLAMP® Wiring Protocol: Strip 28 to 12 AWG (0.08 to 2.5 mm²) solid or fine-stranded conductors to 8–9 mm (0.31–0.35 in) and terminate into the pluggable WAGO 721 Series connectors using a 3.5 × 0.5 mm operating tool (WAGO 210-720) for rapid MRO swap-outs.