HWS100A-15/A TDK-Lambda 105W 15VDC Chassis Power Supply

$134.67

TDK-Lambda HWS100A-15/A (HWS100A15A) 105W 15VDC 7A covered chassis power supply, 85-265VAC input, featuring active PFC, UL 508, and Class B EMI compliance.

SKU: HWS100A-15/A Category: Brand:

Description

TDK-Lambda HWS100A-15/A (also known as HWS100A15A) is a heavy-duty 105W single-output enclosed AC-DC industrial power supply from the ultra-reliable HWS-A series. In TDK-Lambda’s nomenclature, HWS100A denotes the 100W-class second-generation high-reliability frame, -15 specifies the 15 VDC nominal output rail, and the /A suffix designates the factory-installed protective metal cover with standard M3.5 screw terminals. Engineered with an active power factor correction (PFC) front end switching at 65 kHz and a main converter stage operating at 120 kHz, the unit accepts a universal 85 to 265 VAC (47–63 Hz) or 120 to 370 VDC input while withstanding 300 VAC line surges for 5 seconds. It delivers up to 7 A continuous current (105 W rated power) with a wide 12.0 to 18.0 VDC potentiometer adjustment range, tight 60 mV line regulation, 150 mV load regulation, 150 mVp-p maximum ripple and noise, and up to 88% conversion efficiency at 230 VAC.

Housed in a compact, corrosion-resistant aluminum chassis measuring 33.5 × 83.0 × 160.5 mm (1.32 × 3.27 × 6.32 in) and weighing 470 g (1.04 lbs), the HWS100A-15/A features a front-facing 7-pole M3.5 screw terminal block with dedicated remote sense terminals (+S, -S) pre-fitted with removable shorting links. Comprehensive internal protection circuits safeguard mission-critical loads against overload and short-circuit faults (>105% constant current combined with automatic-recovery hiccup mode) as well as overvoltage events (18.8 to 21.8 VDC latching shutdown). Reinforced galvanic isolation is rated at 3,000 VAC input-to-output and 2,000 VAC input-to-ground, paired with natural convection cooling from -10 °C to +70 °C (100% full load up to +50 °C) and full certification to UL 508, IEC/EN/UL 62368-1, SEMI F47, and EN 55032 Class B.

Key Features

  • Precision 15 VDC / 7 A Industrial Output: Delivers 105 W continuous power with a wide 12.0 to 18.0 VDC front-panel voltage trim range, 60 mV maximum line regulation, 150 mV load regulation, and 150 mVp-p low-ripple output.
  • Wide Universal AC/DC Input & Surge Resilience: Operates seamlessly across 85 to 265 VAC (47–63 Hz) and 120 to 370 VDC inputs while enduring severe 300 VAC line transients for up to 5 seconds.
  • Active PFC & High Conversion Efficiency: Integrates a 65 kHz active power factor correction stage achieving 0.98/0.93 PF, IEC 61000-3-2 Class A harmonic compliance, and 86% to 88% efficiency to minimize cabinet heat.
  • Remote Sense Voltage Drop Compensation: Equipped with dedicated +S and -S remote sensing terminals (shipped with removable factory shorting bars) to automatically compensate for wiring voltage drops across long load cables.
  • Industrial Protection & 3,000 VAC Isolation: Combines >105% constant-current and auto-recovery hiccup overload protection with 18.8–21.8 VDC latching OVP and 3,000 VAC input-to-output galvanic isolation.
  • Conservative Electrolytic Design & High MTBF: Built with conservatively rated electrolytic capacitors to achieve a 2,963,512-hour Telcordia SR-332 MTBF and industry-unique limited lifetime warranty coverage in EMEA and the Americas.
  • UL 508, SEMI F47 & Class B EMI Compliance: Certified to UL 508 industrial control equipment standards, IEC/EN/UL 62368-1, SEMI F47 sag immunity (>200 VAC), and EN 55011 / EN 55032 Class B radiated and conducted emissions.

Technical Specifications

Manufacturer TDK-Lambda
Manufacturer Part Number (MPN) HWS100A-15/A
Alternate Part Number HWS100A15A
Product Series HWS-A Series (HWS100A 100W Class)
Product Category Chassis Power Supplies
Component Type Enclosed Single-Output Industrial AC-DC Power Supply with Cover (/A)
Circuit Topology Switched-Mode Power Supply (SMPS) with Active Power Factor Correction (PFC)
Nominal Output Voltage 15 VDC
Output Voltage Adjustment Range 12.0 to 18.0 VDC (±20% via front-panel potentiometer)
Rated Output Current 7.0 A
Output Current Range 0 to 7.0 A (No minimum load required)
Rated Output Power 105 W
Number of Outputs 1 (Single Output)
Output Ripple & Noise (Max.) 150 mVp-p
Line Regulation 60 mV max.
Load Regulation 150 mV max.
Hold-Up Time 20 ms typ. (at 115 / 230 VAC)
Max. Capacitive Load 5,000 µF
AC Input Voltage Range 85 to 265 VAC operating (90 to 264 VAC safety certified; 300 VAC surge withstand for 5 s)
DC Input Voltage Range 120 to 370 VDC (Safety certified for AC input only)
Nominal Input Voltage 100 to 240 VAC
Input Frequency Range 47 to 63 Hz (Safety certified for 50 to 60 Hz)
Efficiency (at 115 VAC) 86% typ.
Efficiency (at 230 VAC) 88% typ.
AC Input Current (at 115 VAC) 1.3 A typ. (at 100 VAC full load)
AC Input Current (at 230 VAC) 0.65 A typ. (at 200 VAC full load)
Inrush Current (Cold Start at 115 VAC) 14 A typ. (at 100 VAC cold start)
Inrush Current (Cold Start at 230 VAC) 28 A typ. (at 200 VAC cold start)
Power Factor (PF at 115 VAC) 0.98 typ. (at 100 VAC)
Power Factor (PF at 230 VAC) 0.93 typ. (at 200 VAC)
Power Factor Correction (PFC) Active PFC (Meets IEC/EN 61000-3-2 Class A)
No-Load Power Consumption 0.3 W to 4.6 W (Series range)
Switching Frequency 120 kHz (Main DC-DC converter) / 65 kHz (Active PFC converter)
Mounting Style Chassis Mount (4 × M3 embossed, tapped, and countersunk holes on base and side faces; max. 6 mm screw penetration)
Cooling Method Natural Free Air Convection
Overall Width (W) 33.5 mm (1.32 in)
Overall Height (H) 83.0 mm (3.27 in)
Overall Depth (D) 160.5 mm (6.32 in) (Excluding 19 mm max. terminal block projection)
Dimensional Tolerance ±1.0 mm (±0.039 in) on outer envelope; ±0.5 mm (±0.020 in) on mounting pitches
Mounting Hole Pitch Side Mounting: 135.0 × 73.5 mm (5.31 × 2.89 in); Base Mounting: 125.0 mm (4.92 in) length center-to-center
Net Weight 470 g (0.47 kg / 1.04 lbs / 16.58 oz)
Termination / Connector Style 7 × M3.5 Screw Terminals with Cover (/A Suffix); Optional JST B2B-XH-AM 2-pin header for /R Remote On/Off
Input Terminal Pinout Front Terminal Block (Bottom Section): AC(L) Live, AC(N) Neutral, Protective Earth Ground (FG)
Output & Signal Terminal Pinout Front Terminal Block (Top Section, Top-to-Bottom): +S (Remote Sense +), +V (Positive Output), -V (Negative Output), -S (Remote Sense -); factory shorting links installed between +S/+V and -S/-V
Control & Monitoring Signals Remote Sense (+S, -S standard); Remote On/Off available via optional /R suffix
Status Indicator Green LED (DC OK)
Enclosure / Potting Material Ventilated Aluminum Chassis and Protective Cover (/A)
Overload Protection (OLP) Threshold >105% of rated output current
Overload Protection (OLP) Mode Constant current limiting combined with hiccup mode and automatic recovery
Overvoltage Protection (OVP) Threshold 18.8 to 21.8 VDC
Overvoltage Protection (OVP) Mode Latching shutdown (Recycle AC input power to reset)
Short Circuit Protection (SCP) Continuous constant current & hiccup mode with automatic recovery
Withstand Isolation Voltage (I/P to O/P) 3,000 VAC for 1 minute
Withstand Isolation Voltage (I/P to FG / Case) 2,000 VAC for 1 minute
Withstand Isolation Voltage (O/P to FG / Case) 500 VAC for 1 minute
Isolation Resistance (at 500 VDC) >100 MΩ at 25 °C (77 °F) and 70% RH
Earth Leakage Current <0.5 mA max. (Typically 0.2 mA at 100 VAC, 0.4 mA at 230 VAC)
Operating Ambient Temperature Range -10 °C to +70 °C (+14 °F to +158 °F)
Full-Load Operating Temperature Limit +50 °C (+122 °F) at 100% load with /A cover
High-Temperature Derating Rate Derate linearly at 4.0%/°C from 100% load at +50 °C (+122 °F) to 20% load (21 W / 1.4 A) at +70 °C (+158 °F)
Altitude Derating Up to 4,000 m (13,123 ft) max. operating altitude
Storage Temperature Range -30 °C to +85 °C (-22 °F to +185 °F)
Operating Relative Humidity 30% to 90% RH (Non-condensing)
Storage Relative Humidity 10% to 95% RH (Non-condensing)
Temperature Coefficient ±0.02%/°C
Vibration Resistance 10 to 55 Hz (1 min sweep), 19.6 m/s² (2G) constant along X, Y, Z axes for 1 hour each (Non-operating); Shock <196 m/s² (20G)
Safety Approvals (UL / North America) UL 62368-1, CSA C22.2 No. 62368-1, UL 508 Industrial Control Equipment
Safety Approvals (IEC / EN / TÜV) IEC/EN 62368-1, CE Mark, UKCA Mark
Safety Approvals (Regional / Global) SEMI F47 Line Dip Immunity (at input voltages >200 VAC)
EMC Conducted & Radiated Emissions EN 55011 / EN 55032 Class B, FCC Part 15 Class B, VCCI Class B
EMC Harmonic & Flicker Compliance IEC/EN 61000-3-2 Class A Harmonic Current Emissions
EMC Immunity Standards EN 61000-4-2 (ESD ±8 kV air / ±6 kV contact, Criteria B), EN 61000-4-3 (Radiated 10 V/m 80M-1GHz, Criteria A), EN 61000-4-4 (EFT ±2 kV, Criteria B), EN 61000-4-5 (Surge ±4 kV common / ±2 kV normal, Criteria B), EN 61000-4-6 (Conducted 10 Vrms, Criteria A), EN 61000-4-8 (Magnetic 30 A/m, Criteria A), EN 61000-4-11 (Voltage Dips), SEMI F47
MTBF (Telcordia SR-332 / Bellcore) 2,963,512 Hours (Telcordia SR-332 Issue 3, 24V model at +55 °C ambient, full load, 230 VAC input)
Environmental Compliance RoHS Compliant; Limited Lifetime Warranty (Americas & EMEA) / 5-Year Warranty (Other Regions)

Industrial Applications & Compatible Systems

The TDK-Lambda HWS100A-15/A is engineered for long-lifecycle industrial, semiconductor, and automation architectures requiring ultra-stable 15 VDC power:

  • Semiconductor Wafer Fabrication & Test Equipment: Provides SEMI F47 compliant 15 VDC rails for wafer handling robotics, vacuum gauge controllers, and cleanroom metrology tools operating on 200–240 VAC lines.
  • Precision Analog Instrumentation & Sensor Buses: Powers low-noise 15 V operational amplifier rails, conditioning transducers, mass flow controllers, and Hall-effect current sensors requiring ≤150 mVp-p ripple.
  • Factory Automation & UL 508 Control Panels: Supplies continuous 7 A current to PLC analog I/O racks, pneumatic proportional valves, and servo brake circuits inside enclosed machinery cabinets.
  • Broadcast, Telecom & Automated Test Equipment (ATE): Delivers Class B EMI-compliant power with remote voltage sensing for rack-mounted RF transceivers, signal generators, and automated PCB test fixtures.

Installation, Thermal Management & MRO Guidelines

Follow these engineering best practices during panel integration and preventive MRO replacement to preserve long-term thermal and electrical reliability:

  • Chassis Screw Penetration Depth Limit: When securing the enclosure via the four M3 tapped base or side mounting holes, ensure mounting screws do not protrude more than 6.0 mm (0.24 in) into the chassis to maintain internal creepage and prevent PCB damage.
  • Convection Thermal Management & Derating: Allow unrestricted airflow around the ventilated aluminum cover and apply a linear 4.0%/°C load derating above +50 °C (+122 °F), limiting continuous output to 20% (21 W / 1.4 A) at +70 °C.
  • Remote Sense Wiring Configuration: Keep the factory-installed shorting bars connected between +S/+V and -S/-V for local loads, or wire twisted-pair sense leads directly to the remote load terminals to compensate for cable voltage drops.