HLG-240H-36AB Mean Well 241.2W 36VDC Dimmable LED Driver

$84.65

Mean Well HLG-240H-36AB (HLG240H36AB) 241.2W 36VDC 6.7A CV+CC dimmable LED driver, 90-305VAC input, featuring IP65 housing, pots, 3-in-1 dimming, and UL8750 Type HL.

SKU: HLG-240H-36AB Category: Brand:

Description

Mean Well HLG-240H-36AB (also known as HLG240H36AB) is an industrial-grade 241.2W dual-mode Constant Voltage and Constant Current (CV+CC) LED driver from the flagship HLG-240H series. In Mean Well’s nomenclature, 36 denotes the 36 VDC nominal output channel, while the AB suffix specifies the hybrid functional configuration combining built-in Vo/Io potentiometers (A-Type) with an isolated 3-in-1 dimming cable (B-Type) in an IP65-rated enclosure. Operating across an ultra-wide 90 to 305 VAC (or 127 to 431 VDC) input range with active power factor correction (PF ≥ 0.98 at 115 VAC) and a 100 kHz switching topology, it delivers up to 6.7 A across an 18 to 36 VDC constant-current compliance window. High conversion efficiency of 92.5% pairs with tight ±1.0% voltage tolerance, ±0.5% line and load regulation, and a low maximum output ripple of 250 mVp-p.

Housed in a rugged extruded aluminum Case No. 994C chassis measuring 244.2 × 68.0 × 38.8 mm (9.61 × 2.68 × 1.53 in) and weighing 1.3 kg (2.87 lbs), the unit relies on silent fanless free-air convection across a -40 °C to +90 °C (-40 °F to +194 °F) case temperature range. Pre-wired 300 mm rubberized leads provide color-coded AC input, DC output, and 1–10 VDC / 10V PWM / 100kΩ resistance dimming connections alongside accessible external potentiometers for fine-tuning voltage (33.5–38.5 VDC) and current (3.3–6.7 A). Comprehensive fault protection includes 95–108% constant-current limiting, hiccup short-circuit recovery, auto-recovering overtemperature shutdown, and latching overvoltage protection at 43–49 VDC. Reinforced 3.75 kVAC primary-to-secondary galvanic isolation, 4 kV line-to-earth surge immunity, and UL 8750 Type HL hazardous-location approvals ensure long-term reliability exceeding 62,000 hours.

Key Features

  • Dual-Mode CV+CC Output & Potentiometer Trimming: Delivers 36 VDC nominal at 6.7 A (241.2 W) with an 18 to 36 VDC constant-current region, plus on-chassis potentiometers to trim output voltage (33.5–38.5 VDC) and current (3.3–6.7 A).
  • Integrated 3-in-1 Dimming Control Interface: Supports smooth constant-current dimming from 10% to 100% via dedicatedDIM+/DIM- leads using additive 1–10 VDC voltage, 10V PWM signals (100 Hz to 3 kHz), or 10kΩ–100kΩ/N resistance.
  • Wide 90–305 VAC Universal Input & Active PFC: Accepts 90 to 305 VAC (47–63 Hz) or 127 to 431 VDC line power, achieving PF ≥ 0.98 at 115 VAC, PF ≥ 0.95 at 230 VAC, and THD below 20%.
  • 92.5% High Efficiency & Fanless Thermal Design: Achieves 92.5% typical efficiency in a potted Case 994C metal enclosure, operating under natural convection up to a +90 °C (+194 °F) maximum case temperature.
  • IP65 Ingress Protection & 5G Vibration Immunity: Sealed aluminum housing with weather-resistant SJOW/H05RN-F rubber cables protects against dust and water jets while withstanding 5G vibration from 10 to 500 Hz across all axes.
  • Comprehensive Protection & Latching OVP Suite: Features 95–108% constant-current overload limiting, auto-recovering hiccup short-circuit protection, thermal shutdown, and latching overvoltage shutdown triggered between 43 and 49 VDC.
  • 3.75 kVAC SELV Isolation & 4 kV Surge Immunity: Engineered with 3.75 kVAC I/P-to-O/P, 2.0 kVAC I/P-to-FG, and 1.5 kVAC O/P-to-FG dielectric strength alongside EN 61000-4-5 4 kV line-to-earth and 2 kV line-to-line surge immunity.
  • UL 8750 Type HL & Global Lighting Compliance: Certified to UL 8750 Type HL for Class I Division 2 hazardous locations, UL 1012, EN 61347-1/-2-13, and EN 55015 Class B emissions with a 7-year OEM warranty.

Technical Specifications

Manufacturer Mean Well
Manufacturer Part Number (MPN) HLG-240H-36AB
Alternate Part Number HLG240H36AB
Product Series HLG-240H Series
Product Category Dimmable LED Drivers
Component Type AC-DC Constant Voltage + Constant Current (CV+CC) Dimmable LED Driver
Circuit Topology Two-Stage Active PFC + Isolated Switching Converter (SELV, Class I)
LED Operation Mode Constant Voltage + Constant Current (CV + CC Dual Mode)
Nominal Output Voltage 36 VDC
Constant Current Region Voltage Range 18 to 36 VDC
Output Voltage Adjustment Range 33.5 to 38.5 VDC (via built-in Vo ADJ. potentiometer)
Rated Output Current 6.7 A
Current Adjustment Range 3.3 to 6.7 A via built-in Io ADJ. potentiometer; 10% to 100% via 3-in-1 dimming
Rated Output Power 241.2 W
Output Ripple & Noise (Max.) 250 mVp-p (measured at 20 MHz bandwidth with 0.1 µF & 47 µF parallel capacitor)
Output Voltage Tolerance ±1.0% (includes set-up tolerance, line regulation, and load regulation)
Line Regulation ±0.5%
Load Regulation ±0.5%
Setup Time (at 115 VAC) 1000 ms (at cold start, full load)
Setup Time (at 230 VAC) 500 ms (at cold start, full load)
Rise Time 80 ms (at 115 / 230 VAC full load)
Hold-Up Time 15 ms (typ. at full load, 115 / 230 VAC)
AC Input Voltage Range 90 to 305 VAC (Universal / 277 VAC North American commercial lighting)
DC Input Voltage Range 127 to 431 VDC
Input Frequency Range 47 to 63 Hz
Efficiency 92.5% (typ. at 230 VAC full load)
AC Input Current (at 115 VAC) 4.0 A (typ.)
AC Input Current (at 230 VAC) 2.0 A (typ. at 230 VAC) / 1.2 A (typ. at 277 VAC)
Inrush Current (Cold Start at 230 VAC) 75 A (twidth = 570 µs measured at 50% Ipeak at 230 VAC, per NEMA 410; max. 2 units on 16 A Type B / 4 units on Type C MCB)
Power Factor (PF at 115 VAC) ≥ 0.98 (at full load)
Power Factor (PF at 230 VAC) ≥ 0.95 (at full load)
Power Factor Correction (PFC) Active PFC; Total Harmonic Distortion (THD) < 20% (at load ≥ 50% for 115/230 VAC; ≥ 75% for 277 VAC)
Switching Frequency 100 kHz (fixed PWM & PFC oscillator)
Mounting Style Chassis / Surface Mount (4 × Ø4.2 mm mounting slots)
Cooling Method Free Air Convection (Fanless)
Enclosure Case Number 994C
Overall Width (W) 68.0 mm (2.68 in)
Overall Height (H) 38.8 mm (1.53 in)
Overall Depth (D) 244.2 mm (9.61 in)
Dimensional Tolerance ±1.0 mm (±0.04 in)
Mounting Hole Pitch 220.2 × 34.0 / 34.2 mm (8.67 × 1.34 / 1.35 in) center-to-center
Net Weight 1.30 kg (2.87 lbs / 45.86 oz)
Termination / Connector Style Pre-Wired Flying Cable Leads + Built-In Vo/Io Potentiometers under Rubber Stoppers
Input Terminal Pinout Input Cable (SJOW 17AWG & H05RN-F 1.0 mm² × 3C): AC/L (Brown), AC/N (Blue), FG Protective Earth (Green/Yellow)
Output & Signal Terminal Pinout DC Output Cable (SJOW 17AWG & H05RN-F 1.0 mm² × 2C): +V (Red), -V (Black); Dimming Cable (UL2517 20AWG × 2C): DIM+ (Purple), DIM- (Pink)
Dimming Control Interface 3-in-1 Dimming: 1 to 10 VDC Additive Voltage, 10V PWM Signal (100 Hz to 3 kHz), or 10 kΩ to 100 kΩ/N Resistance (100 µA typ. source current)
Lead Wire Length 300 ± 20 mm (11.81 ± 0.79 in) for AC Input, DC Output, and Dimming Cables
Enclosure / Potting Material Extruded Aluminum Metal Housing (Class I Design), Fully Potted Internal Electronics
Overload Protection (OLP) Threshold 95% to 108% of rated output power
Overload Protection (OLP) Mode Constant Current Limiting, recovers automatically after fault condition is removed
Overvoltage Protection (OVP) Threshold 43 to 49 VDC
Overvoltage Protection (OVP) Mode Shut down and latch off output voltage, re-power on to recover
Overtemperature Protection (OTP) Mode Shut down output voltage, recovers automatically after temperature goes down
Short Circuit Protection (SCP) Hiccup mode, recovers automatically after fault condition is removed
Withstand Isolation Voltage (I/P to O/P) 3.75 kVAC (3750 VAC)
Withstand Isolation Voltage (I/P to FG / Case) 2.0 kVAC (2000 VAC)
Withstand Isolation Voltage (O/P to FG / Case) 1.5 kVAC (1500 VAC)
Isolation Resistance (at 500 VDC) ≥ 100 MΩ (I/P to O/P, I/P to FG, O/P to FG at 500 VDC, 25 °C, 70% RH)
Earth Leakage Current < 0.75 mA (at 277 VAC)
Operating Ambient Temperature Range Tcase: -40 °C to +90 °C (-40 °F to +194 °F); Typical Ambient Ta: -40 °C to +70 °C (-40 °F to +158 °F)
Full-Load Operating Temperature Limit 100% load up to Tcase +75 °C (+167 °F) or Ta +60 °C (+140 °F) at 230 VAC; 100% load up to Tcase +65 °C (+149 °F) or Ta +50 °C (+122 °F) at 100 VAC
High-Temperature Derating Rate Derates linearly from 100% load at Tcase +75 °C (+167 °F) to 50% load at Tcase +90 °C (+194 °F) at 230 VAC
Low-Line Input Derating Derates linearly from 100% load at 100 VAC down to 80% load at 90 VAC input
Altitude Derating 3.5 °C per 1000 m (3280 ft) for operating altitudes above 2000 m (6560 ft)
Storage Temperature Range -40 °C to +80 °C (-40 °F to +176 °F)
Operating Relative Humidity 20% to 95% RH (non-condensing)
Storage Relative Humidity 10% to 95% RH
Temperature Coefficient ±0.03% / °C (0 °C to 50 °C / +32 °F to +122 °F)
Vibration Resistance 10 to 500 Hz, 5G, 12 min/cycle, 72 min each along X, Y, and Z axes
Ingress Protection (IP) IP65 (Dust-tight and protected against water jets for indoor or outdoor installations)
Safety Approvals (UL / North America) UL 8750 Type “HL” (Class I, Division 2 Hazardous Locations), UL 1012, CAN/CSA-C22.2 No. 107.1-01, CSA C22.2 No. 250.0-08
Safety Approvals (IEC / EN / TÜV) BS EN / EN / AS/NZS 61347-1, BS EN / EN / AS/NZS 61347-2-13 Independent, SELV
Safety Approvals (Regional / Global) PSE J61347-1 / J61347-2-13, GB/T 19510.1 / 19510.213 (CCC), EAC TP TC 004, CE, UKCA
EMC Conducted & Radiated Emissions BS EN / EN 55015, BS EN / EN 55032 (CISPR 32) Class B, GB/T 17743, EAC TP TC 020
EMC Harmonic & Flicker Compliance BS EN / EN 61000-3-2 Class C (at load ≥ 50%), BS EN / EN 61000-3-3, GB 17625.1
EMC Immunity Standards BS EN / EN 61000-4-2, -3, -4, -5 (Surge: 4 kV Line-Earth, 2 kV Line-Line), -6, -8, -11, BS EN / EN 61547, BS EN / EN 55024 (Light Industry Level)
MTBF (Telcordia SR-332 / Bellcore) 2,015,100 hours min. (2015.1K hrs)
MTBF (MIL-HDBK-217F) 176,400 hours min. (176.4K hrs at 25 °C)
Environmental Compliance RoHS Compliant, ErP Lighting Directive Ready, Typical Lifetime > 62,000 Hours (at Tcase ≤ 75 °C), 7-Year Manufacturer Warranty

Industrial Applications & Compatible Systems

Mean Well HLG-240H-36AB is engineered for rugged commercial, industrial, and hazardous-location LED lighting installations requiring both local current calibration and remote dimming control:

  • High-Bay Industrial & Warehouse Luminaires: Powers 240W-class 36 VDC LED arrays in manufacturing plants, logistics distribution centers, and cold-storage facilities operating on 120V, 208V, 240V, or 277V branch circuits.
  • Outdoor Street, Tunnel & Parking Structure Lighting: Provides IP65 weather-sealed power with 4 kV line-to-earth surge immunity and -40 °C cold-start capability for municipal roadways, highway overpasses, and multi-deck parking garages.
  • Horticultural Greenhouse & Commercial Fishing Lamps: Enables precise photosynthetic photon flux density (PPFD) tuning via both on-body Io/Vo potentiometers and centralized 1–10V / PWM climate controllers in high-humidity agricultural and marine environments.
  • Class I Division 2 Hazardous Location Fixtures: Carries UL 8750 Type HL approval for integration into enclosed vapor-tight luminaires deployed across petrochemical processing zones, paint booths, and grain handling facilities.

Installation, Thermal Management & MRO Guidelines

Follow these critical field engineering practices during installation, dimming integration, and preventive MRO replacement:

  • Dimming Polarity Isolation & Zero-Brightness Switching: Never connect the pink DIM- wire to the black -V DC output negative, as doing so damages the internal 100 µA dimming current source; because 3-in-1 dimming scales down to a 10% minimum threshold, install an upstream AC relay and switch on the mains input whenever complete 0% dark turn-off is required.
  • Thermal Case Point (tc) Monitoring & Low-Line Derating: Verify that the central enclosure tc measurement point remains at or below +75 °C (+167 °F) to achieve the rated >62,000-hour service life, and apply a 20% load derating whenever AC line voltage drops between 100 VAC and 90 VAC.
  • Inrush Breaker Sizing & Waterproof Splice Protection: Account for the 75 A (570 µs) cold-start inrush pulse by limiting each 230 VAC 16 A circuit breaker to a maximum of 2 drivers on Type B or 4 drivers on Type C MCBs, and seal field cable splices using IP68-rated M12/M15 waterproof connectors or Mean Well CJ04 cable joiners.