Description
TDK-Lambda HWS3000GT-24 (also known as HWS3000GT24) is a 3,000W programmable chassis-mount AC-DC power supply from the HWS3000GT Series, where the -24 suffix denotes a 24 VDC nominal output rail and the blank option code indicates standard commercial cooling without /HD ruggedization or /RF reverse airflow. Engineered with a high-frequency switching topology operating at 120 kHz primary and 240 kHz secondary frequencies, it accepts a three-phase 170 to 265 VAC input (200–240 VAC nominal, 0.95 power factor) and delivers 0 to 125 A at 91% conversion efficiency. Output voltage is adjustable from 19.2 to 28.8 VDC via onboard potentiometer or fully programmable across 0 to 28.8 VDC and 0 to 125 A in constant-voltage/constant-current (CV/CC) mode via RS-485 Modbus RTU or 1–5 V / 4–20 mA analog control, maintaining 96 mV line regulation, 192 mV load regulation, and 300 mVp-p ripple and noise.
Comprehensive system protection includes constant-current overload protection (>131.2 A with automatic recovery and 30-second shutdown latch) and overvoltage protection (30.4 to 31.5 VDC), backed by 3,000 VAC input-to-output, 2,000 VAC input-to-ground, and 1,500 VAC output-to-ground galvanic isolation. Housed in a low-profile 270 × 150 × 61 mm (10.63 × 5.91 × 2.4 in) chassis with variable-speed rear-exhaust fan cooling and user-configurable vertical or horizontal output screw terminals, the unit supports -40 °C cold start-up and full-load operation up to +50 °C (+122 °F) before linear derating to 50% at +70 °C (+158 °F). The power supply carries IEC/EN/UL/CSA 62368-1, IEC/EN 62477-1 (OVC III up to 2,000 m), SEMI F47, CE, and UKCA approvals, alongside a 7-year manufacturer warranty in the Americas and EMEA.
Key Features
- High-Density 3-Phase 3,000W Output: Delivers 24 VDC nominal at 0 to 125 A (3,000 W continuous) from a 3-phase 170–265 VAC input at 91% efficiency and 0.95 power factor.
- Full Digital & Analog CV/CC Programmability: Adjusts output voltage from 0 to 28.8 VDC and current from 0 to 125 A via RS-485 Modbus RTU (4,000-step resolution) or 1–5 V / 4–20 mA signals.
- Scalable Series & Parallel Architecture: Connects up to 10 units in parallel for 30 kW high-current bus expansion or up to 3 units in series for higher system voltages.
- Integrated Telemetry, Auxiliary Rail & Control I/O: Provides an always-on 5 V / 2 A standby output, 0.3 V remote sense compensation, Remote ON/OFF, 1–5 V V/I monitors, and AC Fail / V&I Good / Fan Fail signals.
- 3-Zone Reinforced Isolation & Protection Suite: Features 3,000 VAC I/P-O/P, 2,000 VAC I/P-FG, and 1,500 VAC O/P-FG isolation alongside 30.4–31.5 V OVP and >131.2 A CC overload protection.
- Wide Thermal Envelope with -40 °C Cold Start: Starts reliably at -40 °C (-40 °F) and operates from -20 °C to +70 °C (-4 °F to +158 °F) with full 3,000 W output up to +50 °C (+122 °F).
- Ultra-Compact 61 mm Chassis & Flexible Terminals: Measures just 270 × 150 × 61 mm (10.63 × 5.91 × 2.4 in) at 2.3 kg (5.07 lbs) with reversible vertical/horizontal output busbars.
- Global Industrial & Semiconductor Compliance: Certified to IEC/EN/UL/CSA 62368-1, IEC/EN 62477-1 OVC III, EN 55032/55011 Class A, IEC 61000-6-2, and SEMI F47 line-dip immunity.
Technical Specifications
| Manufacturer | TDK-Lambda |
|---|---|
| Manufacturer Part Number (MPN) | HWS3000GT-24 |
| Alternate Part Number | HWS3000GT24 |
| Product Series | HWS3000GT Series |
| Product Category | Chassis Power Supplies |
| Component Type | Three-Phase Programmable CV/CC Chassis-Mount Power Supply |
| Option Code Configuration | Standard (Blank — No /HD Conformal Coating or /RF Reverse Fan) |
| Circuit Topology & Switching Frequency | Active PFC + Isolated High-Frequency Switching (Primary: 120 kHz, Secondary: 240 kHz) |
| Nominal Output Voltage | 24 VDC |
| Output Voltage Adjustment Range (Potentiometer) | 19.2 to 28.8 VDC |
| Output Voltage Programming Range (Digital / Analog) | 0 to 28.8 VDC |
| Rated Output Current | 125 A |
| Output Current Programming Range | 0 to 125 A |
| Rated Output Power | 3,000 W (at 3-phase 170–265 VAC input) |
| Minimum Load Requirement | No minimum load required (0 A) |
| Output Ripple & Noise (Max) | 300 mVp-p |
| Constant Voltage (CV) Line Regulation | 96 mV |
| Constant Voltage (CV) Load Regulation | 192 mV |
| Constant Current (CC) Line Regulation | 500 mA |
| Constant Current (CC) Load Regulation | 1,000 mA |
| Temperature Coefficient | ±0.02 %/°C |
| Hold-Up Time (at 1,500 W / 50% Load) | 20 ms (typical) |
| Hold-Up Time (at 3,000 W / 100% Load) | 10 ms (typical) |
| Auxiliary Standby Output | 5 VDC at 2 A |
| Remote Voltage Sense Compensation | Up to 0.3 V per load line |
| Parallel Operation Capability | Up to 10 units in parallel (up to 30 kW total) |
| Series Operation Capability | Up to 3 units in series |
| Operating Input Voltage Range (AC) | 3-Phase 170 to 265 VAC |
| Nominal Input Voltage Range (AC) | 3-Phase 200 to 240 VAC (Safety certified for 180 to 264 VAC) |
| Input Frequency Range | 47 to 63 Hz (Safety certified for 50 to 60 Hz) |
| Efficiency (at 220 / 230 VAC Input) | 91 % (typical) |
| AC Input Current (at 200 / 230 VAC Input) | 10 A per phase |
| Inrush Current (Cold Start at 200 VAC) | 80 A (at 2nd inrush) |
| Power Factor (at 200 VAC Input) | 0.95 (Active PFC) |
| Overcurrent Protection (OCP) Threshold | > 131.2 A (> 105% of rated current) |
| Overcurrent Protection (OCP) Mode | Constant current limiting with automatic recovery; shuts down output if overload exceeds 30 seconds |
| Overvoltage Protection (OVP) Threshold | 30.4 to 31.5 VDC |
| Insulation Class | Class I (Protective Earth Grounded) |
| Withstand Isolation Voltage (Input to Output) | 3,000 VAC (for 1 minute) |
| Withstand Isolation Voltage (Input to Ground / FG) | 2,000 VAC (for 1 minute) |
| Withstand Isolation Voltage (Output to Ground / FG) | 1,500 VAC (for 1 minute) |
| Isolation Resistance (at 500 VDC) | > 100 MΩ (at 25 °C, 70% RH) |
| Earth Leakage Current | < 3 mA (at 240 VAC, 60 Hz) |
| Operating Ambient Temperature Range | -20 °C to +70 °C (-4 °F to +158 °F); supports -40 °C (-40 °F) cold start-up |
| Full-Load Operating Temperature Limit | +50 °C (+122 °F) at 100% load (3,000 W) |
| High-Temperature Derating Rate | Linear derating of 2.5 %/°C from +50 °C to +70 °C (50% / 1,500 W load at +70 °C) |
| Storage Temperature Range | -40 °C to +85 °C (-40 °F to +185 °F) |
| Operating Humidity Range | 20% to 90% RH (non-condensing) |
| Storage Humidity Range | 10% to 95% RH (non-condensing) |
| Maximum Operating & Storage Altitude | 5,000 m / 16,404 ft (2,000 m / 6,562 ft for IEC/EN 62477-1 OVC III) |
| Vibration Resistance (Non-Operating) | 10 to 55 Hz (1 min sweep), max 19.6 m/s² (2 G), 1 hour per axis |
| Shock Resistance | < 196 m/s² (< 20 G) |
| MTBF (Telcordia SR-332 at +25 °C) | 825,678 hours (at 24V, 125A, 230 VAC input) |
| MTBF (Telcordia SR-332 at +40 °C) | 527,785 hours (at 24V, 125A, 230 VAC input) |
| Safety Certifications & Standards | IEC/EN/UL/CSA 62368-1, IEC/EN 62477-1 (OVC III, 2,000 m), CE Mark, UKCA Mark |
| Conducted & Radiated EMI Emissions | EN 55032 Class A, EN 55011 Class A, FCC Part 15 Class A |
| Harmonic Current Compliance | IEC 61000-3-2 |
| EMC Immunity Overview Standard | IEC 61000-6-2 (Industrial Environment) |
| Electrostatic Discharge (ESD) Immunity | EN 61000-4-2: Contact Discharge Levels 1, 2 (Criteria B); Air Discharge Levels 1, 2, 3 (Criteria B) |
| Radiated RF Immunity | EN 61000-4-3: Level 3 at 80 MHz–1.0 GHz (Criteria A); Level 2 at 1.4–6.0 GHz (Criteria A) |
| Electrical Fast Transient / Burst (EFT) Immunity | EN 61000-4-4: Levels 1, 2, 3 (Criteria B) |
| Surge Immunity | EN 61000-4-5: Common Mode Levels 1, 2, 3 (Criteria B); Normal Mode Levels 1, 2 (Criteria B) |
| Conducted RF Susceptibility | EN 61000-4-6: Levels 1, 2, 3 (Criteria A) |
| Power Frequency Magnetic Field Immunity | EN 61000-4-8: Levels 1, 2, 3, 4 (Criteria A) |
| Voltage Dips & Short Interruptions Immunity | EN 61000-4-11: 30% 500 ms (Criteria A), 60% 200 ms (Criteria A), 100% 20 ms (Criteria A), 100% 5,000 ms (Criteria C on L1-L2/L2-L3, Criteria A on L3-L1) |
| Semiconductor Line Dip Compliance | SEMI F47 (at input voltages > 200 VAC) |
| Digital Communication Interface | RS-485 Modbus RTU (controls Vout/Iout 0–4,000 counts, status, product life, OCP/OVP/AC Fail logs) |
| Analog Voltage & Current Programming (CV / CC) | External 1–5 VDC or 4–20 mA applied to CV and CC terminals (0% to 100% output scaling) |
| Analog Voltage & Current Monitor Outputs | VB terminal (1–5 VDC for 0–100% Vout); CB terminal (1–5 VDC for 0–100% Iout) |
| Status & Control Signals | Remote ON/OFF, AC Fail, Voltage & Current Good, Fan Fail (Open-collector outputs) |
| Input & Output Terminal Configuration | Screw terminals with protective covers (Output busbars user-configurable for vertical or horizontal orientation) |
| Cooling Method & Acoustic Noise | Internal variable-speed fan (rear air exhaust); 45 dBA typical at +25 °C and 70% load |
| Mounting Style & Chassis Fasteners | Chassis Mount via 9-M4 bottom/side mounting holes (6 mm max screw penetration depth) |
| Overall Width (W) | 150 mm (5.91 in) |
| Overall Height (H) | 61 mm (2.40 in) |
| Overall Length / Depth (L) | 270 mm (10.63 in) |
| Overall Dimensions (L × W × H) | 270 × 150 × 61 mm (10.63 × 5.91 × 2.40 in) |
| Net Weight | 2,300 g / 2.30 kg (5.07 lbs) |
| Manufacturer Warranty | 7 Years ( and EMEA regions; 5 years in other regions) |
Industrial Applications & Compatible Systems
TDK-Lambda HWS3000GT-24 provides high-current, programmable 24 VDC power across demanding three-phase industrial automation, test, and process systems:
- Semiconductor Fabrication & Wafer Processing Equipment: Supplies SEMI F47-compliant 24 VDC bulk power for chamber heaters, robot handlers, and load-port actuators in 200–240 VAC three-phase fab tools.
- Automated Test Equipment (ATE) & Burn-In Racks: Enables closed-loop voltage (0–28.8 VDC) and constant-current (0–125 A) sweeps via RS-485 Modbus RTU or 4–20 mA PLC analog outputs.
- Industrial Laser & Additive Manufacturing Systems: Drives high-wattage 24 VDC diode laser drivers, galvanometer scanners, and motion stages with parallel scalability up to 30 kW (10 units).
- Electroplating, Electrolysis & Battery Formation Lines: Operates in constant-current mode with real-time 1–5 V VB/CB telemetry and fault logging for repeatable electrochemical processing.
- Heavy Factory Automation & Robotic Welding Cells: Powers high-current 24 VDC valve manifolds, servo brakes, and industrial controllers inside compact 3-phase 200/208 VAC machine cabinets.
Installation, Thermal Management & MRO Guidelines
Installation & Engineering Guidelines: Verify that the incoming three-phase supply falls within 180–264 VAC (50/60 Hz) for UL/IEC safety compliance, and protect each phase with a 15 A to 20 A industrial thermal-magnetic breaker (D-curve recommended to ride through the 80 A second cold-start inrush). Maintain unobstructed front-to-rear airflow across the variable-speed cooling fan and derate output load linearly at 2.5%/°C above +50 °C (+122 °F) down to 1,500 W at +70 °C (+158 °F). When mounting to an equipment chassis via the 9-M4 mounting holes, limit screw penetration strictly to 6 mm maximum to prevent internal PCB clearance violations, and keep factory shorting jumpers installed on CN41 (-R to AG) and CN61 (+L to +S, -L to -S) unless wiring external Remote ON/OFF or 0.3 V remote sense lines.