6EP13215BA00 Siemens 24W 12VDC DIN Rail Power Supply

$136.08

Siemens 6EP13215BA00 24W 12VDC 2A SITOP PSU100C DIN rail power supply, 85-264VAC/110-300VDC input, featuring 0.75W low no-load loss, cULus UL 508 & DNV approvals.

SKU: 6EP13215BA00 Category: Brand:

Description

Siemens 6EP13215BA00 is an industrial-grade 24W 12VDC 2A single-phase stabilized switching power supply belonging to the compact SITOP PSU100C series (`SITOP PSU100C/1ACDC/12VDC/2A`). Engineered for space-critical distribution boards and machinery control panels, its wide-range primary stage accepts both 85 to 264 VAC (47 to 63 Hz) and 110 to 300 VDC inputs, allowing seamless deployment across global single-phase AC mains and centralized DC battery buses. The regulated output delivers a clean 12 VDC at up to 2 A with front-panel potentiometer adjustment from 10.5 to 12.9 VDC, achieving 82% typical efficiency while restricting maximum no-load power consumption to just 0.75 W. High closed-loop stability ensures 0.5% static line regulation, 1.0% static load regulation, and a low typical residual ripple of 40 mVpp (200 mVpp maximum).

Housed in a slim, side-by-side mountable IP20 enclosure measuring 30 mm (1.18 in) wide by 80 mm (3.15 in) high by 100 mm (3.94 in) deep, the unit snaps directly onto standard EN 60715 TS-35/7.5 or TS-35/15 DIN rails with zero lateral clearance required between adjacent modules. Field wiring is simplified via pluggable screw terminals accommodating 0.5 to 2.5 mm² conductors (one `+` and two `-` output terminals for easy load distribution), alongside a front green Output OK LED. Comprehensive self-protection includes internal overvoltage limiting below 60 VDC and electronic short-circuit shutdown at 2.4 A typical with automatic restart, plus reinforced SELV / ES1 (IEC 62368-1) galvanic isolation. Certified to cULus UL 508, CE, CB, ABS, and DNV marine standards, it operates reliably from -20 °C to +70 °C (-4 °F to +158 °F) with full load up to +60 °C (+140 °F).

Key Features

  • Wide-Range AC & DC Input Capability: Operates across an extended 85 to 264 VAC (100 to 230 VAC nominal, 47 to 63 Hz) or 110 to 300 VDC input window with 2.3x Vin surge immunity for 1.3 ms.
  • Tightly Regulated 12VDC 2A Output: Delivers 24W continuous power with front potentiometer adjustment from 10.5 to 12.9 VDC, maintaining 0.5% line regulation, 1% load regulation, and 40 mVpp typical ripple.
  • Ultra-Low Standby Power & Energy Efficiency: Achieves 82% full-load conversion efficiency with only 5.8 W typical heat dissipation and cuts no-load standby consumption to a maximum of 0.75 W.
  • Ultra-Slim 30mm Zero-Clearance Footprint: Compact 30 x 80 x 100 mm housing requires zero left/right spacing on EN 60715 35 mm DIN rails, maximizing cabinet density in shallow industrial enclosures.
  • Pluggable Screw Terminal Wiring: Equipped with removable screw terminal blocks accepting 0.5 to 2.5 mm² wire gauges, providing L, N, PE inputs and dual negative output terminals for rapid daisy-chaining.
  • Electronic Overload & Short-Circuit Protection: Features overvoltage protection below 60 VDC and electronic current limiting at 2.4 A typical with automatic restart, plus parallel operation support for up to 2 units.
  • Extended -20°C to +70°C Thermal Rating: Sustains 100% rated 2 A output up to +60 °C (+140 °F) under natural convection and derates linearly at 2%/K to 1.6 A at +70 °C (+158 °F).
  • Global Industrial & Marine Certifications: Fully compliant with cULus UL 508, IEC/EN 62368-1 SELV/ES1, EN 55022 Class B emissions, EN 61000-6-2 industrial immunity, and ABS/DNV marine approvals with 3.73M-hour MTBF.

Technical Specifications

Manufacturer Siemens
Manufacturer Part Number (MPN) 6EP13215BA00
OEM Cross-Reference / Replaced Part 6EP1321-5BA00, SITOP PSU100C/1ACDC/12VDC/2A
Compatible Equipment / Series Siemens SIMATIC S7-1200, LOGO!, Distributed I/O, 12 VDC Industrial Sensors & Actuators, Removable Spring Terminal Block 6EP1971-5BA00
Product Series SITOP PSU100C
Product Category Single-Phase DIN Rail
Component Type Industrial AC-DC DIN Rail Power Supply
Circuit Topology Stabilized Switched-Mode Power Supply (SMPS), Primary-Switched Regulator with Galvanic Isolation
Nominal Output Voltage 12 VDC
Output Voltage Adjustment Range 10.5 to 12.9 VDC (via front-panel potentiometer; max. 24 W total output power)
Rated Output Current 2 A
Output Current Range 0 to 2 A (full load up to +60 °C; 1.6 A rated at +70 °C)
Peak / Surge Output Current 2.4 A typical (short-circuit / overload shutdown threshold)
Rated Output Power 24 W
Number of Outputs 1 Output (Parallelable up to 2 identical units for power expansion; start-up with single nominal load only)
Output Ripple & Noise (Max.) 200 mVpp max., 40 mVpp typical (Residual ripple); 300 mVpp max., 50 mVpp typical (Switching voltage peaks)
Output Voltage Tolerance ±3.0% (Relative overall voltage tolerance; approx. 5% turn-on Vout overshoot)
Line Regulation 0.5% on slow input voltage fluctuation; 0.1% typical on rapid ±15% input fluctuation
Load Regulation 1.0% on slow ohmic load fluctuation; 3.0% typical on 10%/90%/10% resistive load step (4 ms / 3 ms settling time)
Setup Time 600 ms max. (0.6 s turn-on response delay)
Rise Time 10 ms typical (output voltage increase time)
Hold-Up Time (at 230 VAC) 20 ms min. (at Vin = 230 VAC and rated 2 A output current)
AC Input Voltage Range 85 to 264 VAC wide-range (100 to 230 VAC nominal; 2.3 x Vin rated overvoltage capability for 1.3 ms)
DC Input Voltage Range 110 to 300 VDC
Nominal Input Voltage 100 to 230 VAC (Single-Phase AC or DC network)
Start-Up Voltage 85 VAC
Input Frequency Range 47 to 63 Hz (50 / 60 Hz nominal line frequency)
Efficiency 82.0% typical (5.8 W typical power loss at 12 VDC / 2 A full load)
AC Input Current (at 115 VAC) 0.63 A (at 100 VAC rated input)
AC Input Current (at 230 VAC) 0.31 A (at 230 VAC rated input)
Inrush Current (Cold Start at 230 VAC) 33 A max. (at +25 °C; I²t value: 1.2 A²·s max.; internal input fuse; recommended external feeder MCB: 16 A Char. B or 10 A Char. C)
No-Load Power Consumption 0.75 W max.
Mounting Style DIN Rail Snap-On (EN 60715 TS-35×7.5 / TS-35×15; side-by-side mountable)
Cooling Method Free Air Natural Convection (Requires 50 mm top/bottom vertical clearance; 0 mm left/right horizontal clearance; 30 x 180 mm total installation envelope)
Overall Width (W) 30.0 mm (1.18 in)
Overall Height (H) 80.0 mm (3.15 in)
Overall Depth (D) 100.0 mm (3.94 in)
Net Weight 0.12 kg / 120 g (0.26 lbs / 4.23 oz)
Termination / Connector Style Removable Screw Terminal Blocks (Optional spring-loaded terminal accessory: 6EP1971-5BA00)
Input Terminal Pinout 3-Pole Removable Screw Terminal: L (Line), N (Neutral), PE (Protective Earth)
Output & Signal Terminal Pinout 3-Pole Removable Screw Terminal: 1x + (+12 VDC Positive), 2x – (DC Common / Negative Return)
Status Indicator Green LED for Output Voltage OK (Normal Operation)
Terminal Wire Gauge Range 0.5 to 2.5 mm² (approx. 20 to 14 AWG) per terminal for L, N, PE, +, and –
Overload Protection (OLP) Threshold 2.4 A typical (120% of rated output current)
Overload Protection (OLP) Mode Electronic Shutdown with Automatic Restart
Overvoltage Protection (OVP) Threshold < 60 VDC
Short Circuit Protection (SCP) Continuous Short-Circuit Proof; Electronic Shutdown at 2.4 A typical with Automatic Restart
Withstand Isolation Voltage (I/P to O/P) Galvanic Isolation: SELV, ES1 (per IEC 62368-1), DVC As (per IEC 61204-7), Protection Class I
Earth Leakage Current 3.5 mA max., 0.4 mA typical
Operating Ambient Temperature Range -20 °C to +70 °C (-4 °F to +158 °F)
Full-Load Operating Temperature Limit +60 °C (+140 °F) at 100% load (2.0 A / 24 W)
High-Temperature Derating Rate 2.0% / K from +60 °C to +70 °C (1.6 A / 19.2 W max. continuous output at +70 °C)
Storage Temperature Range -40 °C to +85 °C (-40 °F to +185 °F) (Transport & Storage)
Operating Relative Humidity 5% to 95% RH, non-condensing
Climatic Category (IEC 60068-1) Climate Class 3K3 (per IEC 60721)
Ingress Protection (IP) IP20
Safety Approvals (UL / North America) cULus Listed (UL 508 Industrial Control Equipment, CSA C22.2 No. 107.1), UL File E197259
Safety Approvals (IEC / EN / TÜV) CB Certificate, CE Marking, IEC 62368-1 (ES1), IEC 61204-7 (DVC As)
Safety Approvals (Regional / Global) EAC Approval, ABS (American Bureau of Shipping) & DNV (Det Norske Veritas) Marine Classification
EMC Conducted & Radiated Emissions EN 55022 Class B
EMC Immunity Standards EN 61000-6-2 Generic Industrial Immunity Standard
MTBF (MIL-HDBK-217F) 3,737,060 Hours (at +40 °C ambient temperature)
Environmental Compliance RoHS Compliant, China RoHS, Environmental Product Declaration (EPD Total GWP: 162 kg CO2 eq; ETIM EC002540; eClass 27-04-07-01)

Industrial Applications & Compatible Systems

The Siemens 6EP13215BA00 SITOP PSU100C power supply is engineered for space-constrained industrial automation and building technology applications requiring a dependable 12 VDC auxiliary rail:

  • Compact PLC & Micro-Automation Panels: Powers 12 VDC logic controllers, HMI operator displays, industrial Ethernet switches, and fieldbus gateways inside shallow machine-mount junction boxes.
  • Marine & Offshore Control Consoles: Certified by ABS and DNV classification societies for deployment in shipboard bridge instrumentation, bilge monitoring, and auxiliary vessel control cabinets.
  • Sensor, Relay & Actuator Distribution: Provides low-ripple 12 VDC excitation for optical encoders, proximity transducers, interposing relays, and solenoid valves with dual negative terminals to simplify common-return wiring.
  • Decentralized Building & Energy Management: Minimizes continuous standby energy waste in HVAC dampers, access control panels, and security transceivers thanks to its ultra-low 0.75 W no-load power consumption.

Installation, Thermal Management & MRO Guidelines

Review the following thermal management, circuit protection, and wiring practices to ensure maximum service life in control cabinet installations:

  • DIN Rail Convection Clearance: Maintain a minimum vertical clearance of 50 mm (1.97 in) above and below the unit to guarantee unrestricted natural convection; units can be mounted directly side-by-side (0 mm lateral spacing) along EN 60715 35 mm rails.
  • High-Temperature Derating & Parallel Load Sharing: Operate at up to 2.0 A (24 W) continuously in ambient temperatures up to +60 °C (+140 °F), and apply a 2%/K linear derating slope down to 1.6 A at +70 °C (+158 °F); up to 2 identical modules may be paralleled for power expansion when started into a single nominal load.
  • Upstream Feeder Breaker Coordination: Protect the AC/DC input line using a miniature circuit breaker (MCB) rated from 16 A with Characteristic B or from 10 A with Characteristic C to accommodate the 33 A (1.2 A²·s) maximum cold-start inrush pulse without nuisance tripping.
  • Vibration-Resistant Terminal Upgrade: For high-vibration machinery or rapid MRO cabinet swaps, the pre-installed pluggable screw terminals (0.5 to 2.5 mm²) can be directly replaced with the optional Siemens 6EP1971-5BA00 removable spring-type terminal kit.