Description
TDK-Lambda CUS800M-48 (also known as CUS800M48) is an 801.6W enclosed medical and industrial AC-DC power supply from the ultra-compact, low-profile CUS800M series, where the 800M prefix designates the 800W medical-grade chassis platform and the -48 suffix specifies a regulated 48VDC single output. Built around a high-efficiency LLC resonant primary-to-secondary converter operating at 50 kHz to 300 kHz with active power factor correction (0.99 at 115 VAC, 0.95 at 230 VAC), it accepts a wide universal input from 85 to 265 VAC (47–63 Hz) and delivers 16.7A continuous current across an adjustable 46.8 to 51.8 VDC trim range. Conversion efficiency reaches 92.2% at 115 VAC and 94.0% at 230 VAC, while maintaining tight line regulation within 240 mV, load regulation within 480 mV, ripple and noise below 480 mVp-p, and less than 0.6 W no-load power consumption when inhibited.
Engineered for Type B and BF patient-connected clinical systems as well as space-constrained instrumentation, the CUS800M-48 provides full 2xMOPP galvanic isolation rated at 4,000 VAC (input-to-output), 2,000 VAC (input-to-ground, 1xMOPP), and 1,500 VAC (output-to-ground, 1xMOPP), alongside ultra-low earth leakage current under 250 µA at 265 VAC. Comprehensive circuit protections include hiccup-mode overcurrent protection above 17.6A, overvoltage protection tripping between 55.2 V and 64.8 V, and latching overtemperature shutdown, complemented by an always-on 5 V / 2 A standby rail, 0.5 V total remote sense compensation, opto-isolated remote on/off, and an opto-isolated Power Good (AC Fail / DC OK) signal. Housed in a 1.67-inch (42.5 mm) high chassis measuring 171 × 85 × 42.5 mm (810 g) with an acoustic-optimized variable-speed cooling fan (30 dBA at 20% load, 42 dBA at full load), it operates from -20 °C to +70 °C (-25 °C cold start-up, linear derating to 60% load above +40 °C) up to 5,000 m altitude and carries IEC/EN/ES/CSA 60601-1, IEC/EN/UL/CSA 62368-1, EN 55011/55032 Class B, EN 60601-1-2:2015 (Ed. 4), CE, and UKCA approvals.
Key Features
- Medical 2xMOPP Safety & Ultra-Low Leakage: Certified to IEC/EN/ES/CSA 60601-1 and 62368-1 with 4,000 VAC input-to-output isolation and under 250 µA leakage current at 265 VAC for Type B and BF medical equipment.
- High-Density 801.6W Output & 94% Efficiency: Delivers 48 VDC (adjustable 46.8–51.8 V) at 16.7 A continuous using a 50–300 kHz LLC resonant topology achieving 92.2% efficiency at 115 VAC and 94.0% at 230 VAC.
- Ultra-Low 1.67-Inch Profile & Quiet Variable Fan: Compact 171 × 85 × 42.5 mm (6.73 × 3.35 × 1.67 in) chassis features an intelligent variable-speed fan generating just 30 dBA at 20% load and 42 dBA at full load.
- Comprehensive Auxiliary & Supervisory Controls: Includes an isolated 5 V / 2 A standby supply, 0.5 V total remote sense, opto-isolated remote on/off inhibit, and combined AC Fail / DC OK Power Good telemetry.
- Class B EMI & 4th-Edition Medical EMC Immunity: Complies natively with EN 55011-B, EN 55032-B, and FCC Class B emissions plus EN 60601-1-2:2015 (Ed. 4), IEC 61000-4-2 through -11, and SEMI F47 line-dip standards.
- High-Altitude & Wide-Temperature Reliability: Supports -25 °C cold start-up, full-load operation to +40 °C (linear derating to 60% at +70 °C), 5,000 m operating altitude, and a 452,227-hour Telcordia SR-332 MTBF backed by a 5-year warranty.
Technical Specifications
| Manufacturer | TDK-Lambda |
|---|---|
| Manufacturer Part Number (MPN) | CUS800M-48 |
| Alternate Part Number | CUS800M48 |
| Product Series | CUS800M / CUS1000M / CUS1200M Series |
| Product Category | Medical Enclosed PSUs |
| Component Type | Enclosed Single-Output Medical & Industrial AC-DC Power Supply |
| Circuit Topology | Active PFC + LLC Resonant Primary-to-Secondary Converter (50 kHz to 300 kHz) |
| Nominal Output Voltage | 48 VDC |
| Output Voltage Adjustment Range | 46.8 VDC to 51.8 VDC (via onboard potentiometer) |
| Rated Output Current | 16.7 A |
| Output Current Range | 0 A to 16.7 A (No minimum load required) |
| Rated Output Power | 801.6 W |
| Standby Output Rating | 5 VDC / 2 A (10 W auxiliary standby rail) |
| Output Ripple & Noise (Max) | 480 mVp-p |
| Line Regulation (Max) | 240 mV |
| Load Regulation (Max) | 480 mV |
| Maximum External Load Capacitance | 7,000 µF |
| Temperature Coefficient | ±0.02 %/°C |
| Hold-Up Time (Typical at 115 VAC) | 11 ms |
| Parallel Operation Capability | Not supported (Parallel operation not possible) |
| Operating AC Input Voltage Range | 85 VAC to 265 VAC (Safety certified for 90 VAC to 264 VAC) |
| Nominal AC Input Voltage Range | 100 VAC to 240 VAC |
| Input Line Frequency | 47 Hz to 63 Hz |
| Efficiency (at 115 VAC) | 92.2 % |
| Efficiency (at 230 VAC) | 94.0 % |
| AC Input Current (at 115 VAC) | 8.0 A |
| AC Input Current (at 230 VAC) | 4.0 A |
| Inrush Current (Cold Start at 115 VAC) | 25.0 A |
| Inrush Current (Cold Start at 230 VAC) | 50.0 A |
| Power Factor (PF at 115 VAC) | 0.99 |
| Power Factor (PF at 230 VAC) | 0.95 |
| No-Load Power Consumption (at 230 VAC) | < 0.6 W typical (with Remote Off active and no load on 5 Vsb) |
| Overcurrent / Overload Protection (OCP/OLP) Threshold | > 17.6 A |
| Overcurrent / Overload Protection (OCP/OLP) Mode | Hiccup mode with automatic recovery (AC power reset may be required if output is dead-shorted) |
| Overvoltage Protection (OVP) Threshold | 55.2 VDC to 64.8 VDC |
| Overvoltage Protection (OVP) Mode | Output shutdown (latched; cycle AC input power to reset) |
| Overtemperature Protection (OTP) Mode | Latching unit shutdown; cycle AC input power to reset |
| Withstand Isolation Voltage (Input to Output) | 4,000 VAC for 1 minute (2 x MOPP medical isolation) |
| Withstand Isolation Voltage (Input to Ground / FG) | 2,000 VAC for 1 minute (1 x MOPP medical isolation) |
| Withstand Isolation Voltage (Output to Ground / FG) | 1,500 VAC for 1 minute (1 x MOPP medical isolation) |
| Insulation Protection Class | Class I (Protective earth connection required) |
| Isolation Resistance (at 500 VDC) | > 100 MΩ (at 25 °C, 70% RH, 500 VDC) |
| Earth Leakage Current | < 250 µA (at 265 VAC, 60 Hz) |
| Operating Ambient Temperature Range | -20 °C to +70 °C (-4 °F to +158 °F); capable of -25 °C (-13 °F) cold start-up |
| Full-Load Operating Temperature Limit | +40 °C (+104 °F) at 100% rated load |
| High-Temperature Derating Rate | Linear derating from 100% load at +40 °C (+104 °F) to 60% load at +70 °C (+158 °F) (1.33 %/°C) |
| Low-Line Input Derating | Linear derating from 100% load at 90 VAC to 90% load at 85 VAC |
| Storage Temperature Range | -40 °C to +75 °C (-40 °F to +167 °F) |
| Operating & Storage Relative Humidity | 10% to 95% RH (non-condensing) |
| Operating & Storage Altitude | Up to 5,000 m (16,404 ft) |
| Vibration Resistance (Non-Operating) | 10 Hz to 55 Hz (1 min sweep), max. 19.6 m/s² (2 G), 1 hour per axis |
| Mechanical Shock Resistance | < 196 m/s² (20 G) |
| MTBF (Telcordia SR-332) | 452,227 hours (24V model baseline at full load, 115 VAC input, +40 °C ambient) |
| Manufacturer Warranty | 5 Years |
| Medical Safety Certifications | IEC 60601-1, EN 60601-1, ANSI/AAMI ES 60601-1, CSA C22.2 No. 60601-1 (2 x MOPP) |
| ITE / Industrial Safety Certifications | IEC 62368-1, EN 62368-1, UL 62368-1, CSA C22.2 No. 62368-1 |
| Regional Compliance Markings | CE Mark, UKCA Mark |
| Conducted & Radiated EMI Emissions | EN 55032 Class B, EN 55011 Class B, FCC Part 15 Class B |
| Harmonic Current Emissions (EN 61000-3-2) | IEC / EN 61000-3-2 Class A |
| Medical EMC Immunity Standard | EN 60601-1-2:2015 (4th Edition) |
| ESD Immunity (EN 61000-4-2) | Levels 1, 2, 3, 4 — Performance Criteria A |
| Radiated RF Immunity (EN 61000-4-3) | Level 3 — Performance Criteria A |
| EFT / Burst Immunity (EN 61000-4-4) | Level 4 — Performance Criteria A |
| Surge Immunity (EN 61000-4-5) | Levels 1, 2, 3, 4 (AC input power port) — Performance Criteria A |
| Conducted RF Immunity (EN 61000-4-6) | Level 3 — Performance Criteria A |
| Power Frequency Magnetic Field Immunity (EN 61000-4-8) | Level 4 — Performance Criteria A |
| Voltage Dips & Interruptions (EN 61000-4-11 & SEMI F47) | EN 61000-4-11 Class 3 & EN 60601-1-2:2015 (Criteria A < 530 W for 0% 1/2 cycle; Criteria A < 330 W at 100 VAC / 200 VAC |
| Remote Sense Compensation | Up to 0.5 V total load-line voltage drop compensation (+S / -S) |
| Remote On / Off Control | Opto-isolated inhibit input (Logic Low = Output ON, Logic High = Output OFF) |
| Power Good / DC OK Telemetry | Combined AC Fail and DC OK opto-isolated open-collector signal (PG) |
| Input Terminal Block & Pinout (TB1) | 3-pin M3 screw terminal block (TIANLI TC25-01-03P-KC): Pin 1 = Live (L), Pin 2 = Neutral (N), Pin 3 = Protective Earth (FG); Torque: 0.5 to 0.8 N·m (5.1 to 8.2 kgf·cm) |
| Output Terminal Busbars & Torque (CN51A / CN51B) | Dual M4 screw busbar terminals (CN51A = +Vout, CN51B = -Vout); Recommended torque: 1.18 N·m (12 kgf·cm) |
| Control Signal Connector & Pinout (CN51) | JST B8B-PHDSS(LF)(SN) 8-pin header (Mating housing: PHDR-08VS, Contacts: SPHD-001T-P0.5) — Pin 1: +5V Standby, Pin 2: 5V Standby GND, Pin 3: -S (Remote Sense -), Pin 4: +S (Remote Sense +), Pin 5: SG (Signal Ground), Pin 6: PG (Power Good), Pin 7: R+ (Remote On/Off +), Pin 8: R- (Remote On/Off -) |
| Cooling Method & Acoustic Noise | Internal variable-speed DC fan (airflow exits across output terminals); 30 dBA typical at 20% load, 42 dBA typical at 100% load |
| Chassis Mounting Provisions | 12 x M3 tapped and standoff mounting holes (bottom & sides); max screw penetration 5 mm, recommended torque 0.49 N·m (5 kgf·cm) |
| Overall Length (L) | 171.0 mm (6.73 in) |
| Overall Width (W) | 85.0 mm (3.35 in) |
| Overall Height (H) | 42.5 mm (1.67 in) |
| Overall Dimensions (L × W × H) | 171.0 × 85.0 × 42.5 mm (6.73 × 3.35 × 1.67 in) |
| Net Weight | 810 g (1.79 lbs / 28.57 oz) |
Industrial Applications & Compatible Systems
TDK-Lambda CUS800M-48 is purpose-built for compact, acoustically sensitive clinical equipment and precision 48 VDC industrial electronics requiring dual medical/ITE safety approvals:
- Diagnostic Imaging & Clinical Treatment Systems: Ultrasound scanners, patient monitors, surgical lasers, dental consoles, and automated laboratory analyzers requiring 2xMOPP isolation and under 250 µA earth leakage.
- Test, Measurement & Semiconductor Fabrication Tools: High-density ATE racks, optical inspection stages, and SEMI F47-compliant wafer handling subsystems operating in 1U/low-profile enclosures.
- Professional Broadcast & Audio/Video Infrastructure: Studio routers, LED wall processors, and acoustic-sensitive control room racks benefiting from 30 dBA idle fan noise and Class B EMI suppression.
- Industrial Automation & 48V Motion Subsystems: Robotics controllers, PoE++ midspan injectors, and 48 VDC servo/actuator bus architectures in high-altitude facilities up to 5,000 m.
Installation, Thermal Management & MRO Guidelines
Installation & Engineering Guidelines: Mount the chassis using all 12 M3 tapped/standoff holes (0.49 N·m torque, strictly limiting screw penetration to 5 mm maximum) to ensure full EMI shielding and 2 G vibration compliance, while maintaining unobstructed airflow exiting across the output terminals. For ambient temperatures above +40 °C, apply linear load derating down to 60% (481 W) at +70 °C, and apply an additional linear derating to 90% load when operating between 90 VAC and 85 VAC. Because the CUS800M-48 does not support parallel current sharing, external ORing diodes are required for redundant N+1 architectures; size upstream branch protection for 8.0 A continuous input current and a 50.0 A cold-start inrush at 230 VAC.