Description
TDK-Lambda DBM20 is an industrial 24 VDC, 20 A (448 W) DIN rail capacitive hold-up module from the DBM20 series, where the base MPN specifies heavy-duty M3 screw terminals (as opposed to the DBM20/E spring-clamp variant). Instead of electrochemical batteries that require periodic replacement, the unit utilizes maintenance-free internal electrolytic bulk capacitors managed by a dual-stage 100 kHz buck charging converter and 70 kHz boost discharging converter. It provides a typical 250 ms buffer hold-up time at full 448 W load (and up to 14 seconds at lighter currents) after a 40-second typical recharge cycle, drawing just 0.8 A during charging and 0.2 A in standby ready mode. Engineers can switch-select on the front panel between Fixed Mode (23–30 VDC input, buffering at 22.4 VDC ±2%) and Dynamic VIN-1 Mode (24–30 VDC input, triggering whenever the bus drops by 1 V) while maintaining output ripple and noise below 240 mVpp.
Housed in a slim, convection-cooled metal enclosure measuring 49 × 123.6 × 115.4 mm (1.93 × 4.87 × 4.54 in) and weighing 740 g (1.63 lbs), the module snaps directly onto standard TS-35/7.5 or TS-35/15 DIN rails. Its front interface integrates top M3 screw terminals for parallel-capable 24 V bus connections alongside a bottom signal terminal block providing a PhotoMOS DC OK relay (30 VDC / 0.2 A), photocoupled Ready and Buffer status outputs, and a remote Inhibit (On/Off) input to prevent unsafe capacitor discharge during servicing. Built-in safety mechanisms include overcurrent protection (>105% buffer current), 35 VDC input overvoltage protection, reverse-flow protection, and 500 VAC input/output-to-ground dielectric isolation (>100 MΩ at 500 VDC). Rated for continuous operation across -25 °C to +70 °C (-13 °F to +158 °F) up to 5,000 m altitude, the DBM20 holds UL 508, IEC/UL/CSA/EN 62368-1, and EN 55032 Class B certifications alongside a Telcordia TR-332 MTBF exceeding 1,026,962 hours.
Key Features
- Maintenance-Free Capacitive Energy Storage: Replaces service-intensive VRLA batteries with long-life internal electrolytic capacitors, delivering 250 ms of hold-up time at 448 W (20 A) and up to 14 s at low loads.
- Selectable Fixed & Dynamic Buffer Modes: Front-panel selector switch configures Fixed Mode (triggers at 22.4 VDC ±2% across 23–30 VDC input) or Dynamic VIN-1 Mode (triggers on a 1 V bus drop).
- Bi-Directional Buck-Boost Conversion Topology: Combines a 100 kHz buck charging stage (40 s typical recharge at 0.8 A) and a 70 kHz boost discharge converter with <240 mVpp output ripple and noise.
- Scalable Parallel Hold-Up Expansion: Multiple DBM20 modules can be wired in parallel across the 24 VDC distribution bus to multiply backup duration or support higher peak surge loads.
- Comprehensive Remote Telemetry & Inhibit Control: Features a 30 V / 0.2 A PhotoMOS DC OK relay, photocoupled Ready (charged) and Buffer (discharging) signals, dual status LEDs, and remote discharge Inhibit.
- Compact 49 mm DIN Rail Footprint: Narrow 49 × 123.6 × 115.4 mm (1.93 × 4.87 × 4.54 in) chassis with M3 screw terminals saves valuable cabinet rail space on TS-35/7.5 and TS-35/15 mounts.
- Industrial Approvals & High Reliability: Certified to UL 508, IEC/UL/CSA/EN 62368-1, and EN 55032 Class B EMI with a 1,026,962-hour Telcordia TR-332 MTBF and a 5-year OEM warranty.
Technical Specifications
| Manufacturer | TDK-Lambda |
|---|---|
| Manufacturer Part Number (MPN) | DBM20 |
| Compatible Equipment / Series | TDK-Lambda DRB15–480, DRF120–960 24 VDC DIN Rail Power Supplies, and DRM40 Redundancy Modules |
| Product Series | DBM20 Series |
| Product Category | Redundancy Modules |
| Component Type | Electrolytic Capacitor Hold-Up / Buffer DIN Rail Module |
| Circuit Topology | Bidirectional Buck Charging (100 kHz) / Boost Discharging (70 kHz) Capacitive Buffer |
| Nominal System / Output Voltage | 24 VDC (Fixed Mode Output: 22.4 VDC; Dynamic Mode Output: Vin – 1 VDC) |
| Operating Voltage Range | Fixed Mode: 23 to 30 VDC; Dynamic (VIN-1) Mode: 24 to 30 VDC (Max. Input Limit: 35 VDC) |
| Rated Output Current | 20 A Max. |
| Rated Output Power | 448 W Average Buffer Power |
| Buffer Hold-Up Time | 250 ms Typical at 448 W / 20 A full load (extendable up to 2–14 s at smaller buffer currents or via parallel modules) |
| Output Voltage Tolerance | Fixed Mode: ±2%; Dynamic (VIN-1) Mode: +3% to -4% (at load > 5%) |
| Output Ripple & Noise (Max.) | < 240 mVpp |
| Minimum Load Current | 0 A (No minimum load required) |
| DC Input Current (Full Load / No Load) | Charging Mode: 0.8 A Typical; Ready / Standby Mode: 0.2 A Typical |
| Buffer Charging Time | 40 s Typical |
| Switching Frequency | Buck Charging Converter: 100 kHz Typical; Boost Discharging Converter: 70 kHz Typical |
| Parallel / Redundant Operation | Parallel connection supported for extended hold-up time (Series operation not supported) |
| Mounting Style | DIN Rail TS-35/7.5 or TS-35/15 |
| Cooling Method | Natural Free Air Convection |
| Overall Width (W) | 49.0 mm (1.93 in) |
| Overall Height (H) | 123.6 mm (4.87 in) |
| Overall Depth (D) | 115.4 mm (4.54 in) |
| Net Weight | 740 g (0.74 kg / 1.63 lbs / 26.1 oz) |
| Termination / Connector Style | M3 Screw Terminals (Heavy-duty input/output and signal blocks) |
| Input Terminal Pinout | Top Power Terminal Block: V+ (Bidirectional 24 VDC Input/Output Bus), V- (DC Return) |
| Output & Signal Terminal Pinout | Bottom Signal Terminal Block: DC OK Relay, Inhibit Input, Ready Output, Buffer Output, +V / Signal Common |
| Control & Monitoring Signals | PhotoMOS DC OK Relay (closed when DC OK, rated 30 VDC / 0.2 A), Photocoupled Ready & Buffer Status Outputs, Remote On/Off (Inhibit) Input |
| Status Indicator | Green LED (Charging / Ready Status) and Red LED (Discharging / Buffering Mode) |
| Terminal Tightening Torque | M3 Screw Terminals: 0.4 to 0.5 N·m (4.1 to 5.1 kgf·cm, 7 mm wire strip length) |
| Overload Protection (OLP) Threshold | > 105% of rated buffer current (Overcurrent Protection) |
| Overvoltage Protection (OVP) Threshold | 35 VDC Input Overvoltage Protection |
| Reverse Polarity Protection | Internal reverse flow protection circuit |
| Withstand Isolation Voltage (I/P to FG / Case) | 500 VAC for 1 minute (Input and Output bridged to Ground) |
| Isolation Resistance (at 500 VDC) | > 100 MΩ at 25 °C, 70% RH (Input and Output to Ground) |
| Operating Ambient Temperature Range | -25 °C to +70 °C (-13 °F to +158 °F) |
| Storage Temperature Range | -25 °C to +85 °C (-13 °F to +185 °F) |
| Operating Relative Humidity | 30% to 90% RH (Non-condensing) |
| Storage Relative Humidity | 10% to 90% RH (Non-condensing) |
| Operating Altitude (Max.) | 5,000 m (16,404 ft) |
| Vibration Resistance | 10 to 55 Hz (1 min sweep), 19.6 m/s² (2G) constant along X, Y, Z axes for 1 hour each (Non-operating); Shock < 196.1 m/s² (20G) |
| Safety Approvals (UL / North America) | UL 508 Industrial Control Equipment, UL 62368-1, CSA C22.2 No. 62368-1 |
| Safety Approvals (IEC / EN / TÜV) | IEC 62368-1, EN 62368-1, CE Mark, UKCA Mark |
| EMC Conducted & Radiated Emissions | EN 55032 Class B, CISPR 32 Class B |
| EMC Immunity Standards | EN 61000-4-2 (ESD Level 4: 16 kV air / 8 kV contact, Criteria B), EN 61000-4-3 (Radiated Level 3, Criteria A), EN 61000-4-4 (EFT Level 1–3, Criteria B), EN 61000-4-5 (Surge Level 1–2, Criteria B), EN 61000-4-6 (Conducted Level 3, Criteria A) |
| MTBF (Telcordia SR-332 / Bellcore) | 1,026,962 Hours (Telcordia TR-332 Issue 5 at 25 °C) |
| Manufacturer Warranty | 5 Years |
Industrial Applications & Compatible Systems
The TDK-Lambda DBM20 is engineered to bridge transient AC mains dropouts, voltage sags, and brief brownouts on 24 VDC industrial control buses without the maintenance overhead of chemical batteries:
- PLC, IPC & HMI Controlled Shutdown: Provides 250 ms of full-load 448 W ride-through (or several seconds for logic-only loads) so programmable logic controllers and industrial PCs can save critical process recipes and execute safe shutdown routines during power interruptions.
- Automated Packaging & Material Handling Lines: Stabilizes 24 VDC sensor, solenoid, and relay networks paired with TDK-Lambda DRB or DRF DIN rail power supplies during momentary utility transfer switches or heavy motor-start voltage dips.
- Semiconductor & Process Control Instrumentation: Satisfies battery-free cleanroom and high-reliability cabinet mandates by storing backup energy purely in long-life electrolytic capacitors.
- High-Availability Redundant 24 V Architectures: Integrates downstream of DRM40 redundancy modules and RSMN/RSEV EMI filters to eliminate single points of failure and absorb sudden peak load transients.
Installation, Thermal Management & MRO Guidelines
Follow these engineering guidelines when integrating the DBM20 into industrial control enclosures:
- Fixed vs. Dynamic (VIN-1) Mode Selection: Use the front-panel selector switch to set Fixed Mode (triggers at 22.4 VDC) when your primary 24 V PSU is adjusted between 23 V and 24 V, or select VIN-1 Dynamic Mode (24–30 VDC input) when you want immediate buffering whenever the regulated bus drops by 1 V.
- Parallel Expansion & Discharge Inhibit Safety: Wire multiple DBM20 modules in parallel across the V+ and V- bus terminals to linearly increase hold-up duration, and always engage the remote Inhibit terminal during cabinet lockout/tagout (LOTO) maintenance to prevent accidental discharge of stored capacitor energy.
- Terminal Torque & Convection Mounting: Mount vertically on a grounded TS-35 DIN rail with adequate top and bottom airflow clearance for natural convection cooling across -25 °C to +70 °C, and torque all M3 screw terminals to 0.4–0.5 N·m using 7 mm stripped conductors.