Description
XP Power HPL5K0TS048 is a high-density 5000 W (5 kW) three-phase enclosed chassis-mount AC-DC switching power supply from the HPL5K0 series, where the nomenclature denotes high-power low-profile 5 kW output (HPL5K0), three-phase delta/3-wire input (T), single main output channel (S), and a nominal 48 VDC output (048). Engineered for both constant voltage (CV) and constant current (CC) operation across a delta 3-wire plus earth input range of 180 to 264 VAC (47–63 Hz), the unit delivers up to 104.0 A of continuous output current alongside an always-on 5 V / 2 A auxiliary standby rail. It supports wide-range analog (0–5 V) and digital output programming from 0% to 105% nominal voltage (0 to 50.4 VDC) and 0% to 110% rated current (0 to 114.4 A) via built-in I²C PMBus, CANopen, RS485, MODBUS, and SCPI interfaces. Active power factor correction (0.98 PF at 40–50 kHz) paired with a variable-frequency main converter (40–250 kHz) achieves 92% to 93% conversion efficiency, ±0.5% line regulation, 1% load regulation, and 1% maximum output ripple and noise (480 mVp-p).
Housed in a compact 330.2 × 127.0 × 127.0 mm (13.00 × 5.00 × 5.00 in) chassis weighing 5.7 kg (12.5 lbs), the supply utilizes intelligent temperature-controlled forced-air cooling via an integrated 120 × 120 mm fan and facilitates active current sharing across up to 5 parallel units (up to 25 kW). Heavy-duty power connections are handled via three M4 AC input screw terminals, an M4 earth stud, and four M5 DC output busbar screw terminals, complemented by a 30-pin JST S30B-PHDSS signal header for remote sense, remote inhibit, AC OK, DC OK, fan fail/temp warning, and synchronization. Comprehensive internal safeguards include F25A/250V fusing in each phase, phase-loss shutdown (0.5 s with auto-recovery), constant-current overload protection (108% ±3%), latching overvoltage protection (120%), and auto-resetting thermal protection. Certified to both IEC/UL/EN 60601-1 Ed. 3.1 (2×MOPP primary-to-secondary at 4000 VDC) and IEC/UL/EN 62368-1 with SEMI F47 voltage sag compliance, it operates reliably from -20 °C to +70 °C (-4 °F to +158 °F) with full 5 kW output up to +50 °C (+122 °F).
Key Features
- 5 kW Three-Phase Delta Input Architecture: Operates from a 3-phase, 3-wire plus earth 180–264 VAC (47–63 Hz) supply without requiring a neutral conductor, drawing 18 A per phase at 180 VAC with 0.98 power factor.
- 0–105% Voltage & 0–110% Current Programming: Supports full-range CV and CC output programming from 0 to 50.4 VDC and 0 to 114.4 A via 0–5 V analog signals or digital bus commands with <40 ms slew rate.
- Multi-Protocol Digital Control Suite: Integrates native I²C PMBus, CANopen, and full/half-duplex RS485 interfaces supporting MODBUS and SCPI protocols, offering ±1% voltage and ±2% current telemetry and setting accuracy.
- Scalable 5-Unit Active Current Sharing: Single-wire current share bus (Pin 23 ISHARE) and turn-on synchronization (Pin 18 SYNC) enable up to 5 units to operate in parallel with ±3% load-sharing accuracy.
- Dual Medical 2xMOPP & ITE Safety Approvals: Certified to IEC/UL/EN 60601-1 Ed. 3.1 with 4000 VDC (2xMOPP) input-to-output and 2500 VDC (1xMOPP) input-to-ground isolation alongside IEC/UL/EN 62368-1 and SEMI F47 compliance.
- Comprehensive Fault & Phase-Loss Protection: Equipped with F25A/250V fuses per phase, 0.5-second phase-loss shutdown with auto-recovery, 120% latching OVP, 108% constant-current OLP, and 10-second pre-shutdown fan/temperature warning.
- Auxiliary Standby & Remote Sense Control: Provides a continuous 5 V / 2 A standby output whenever AC mains are present, plus remote sense compensation for up to 1% per lead (2% total) line drop.
- High Power Density & Wide Thermal Window: Delivers 15.38 W/in³ in a 330.2 × 127.0 × 127.0 mm enclosure, sustaining 100% 5 kW load from -20 °C to +50 °C and derating linearly to 50% at +70 °C.
Technical Specifications
| Manufacturer | XP Power |
|---|---|
| Manufacturer Part Number (MPN) | HPL5K0TS048 |
| Product Series | HPL5K0 Series |
| Product Category | Medical Enclosed PSUs |
| Component Type | Three-Phase Programmable Enclosed Chassis-Mount AC-DC Power Supply |
| Circuit Topology | Fixed-Frequency Active PFC (40–50 kHz) + Variable-Frequency Isolated Main Converter (40–250 kHz) |
| Nominal Output Voltage | 48 VDC (Main Output V1) ; 5 VDC (Auxiliary Standby Output) |
| Output Voltage Adjustment Range | 0 to 50.4 VDC (0% to 105% via Analog 0–5 V or Digital Programming ; ±10% via Onboard Potentiometer up to 105% max.) |
| Rated Output Current | 104.0 A (Main 48 VDC Output) ; 2.0 A (5 VDC Standby Output) |
| Output Current Range | 0.0 to 104.0 A (0% to 110% Programmable Current Limit up to 114.4 A ; 0 A Minimum Load Required) |
| Rated Output Power | 5000 W (5 kW Continuous) |
| Number of Outputs | 2 Outputs (1 Main 48 VDC / 104 A Output + 1 Auxiliary 5 VDC / 2 A Standby Output) |
| Output Ripple & Noise (Max.) | 1% of Nominal Voltage / 480 mVp-p (Main 48 VDC Output) ; 2.5% / 125 mVp-p (5 V Standby), measured at 20 MHz bandwidth (0–50 °C) |
| Output Voltage Tolerance | ±0.5% of Nominal Voltage (Main Output) ; ±3% (5 V / 2 A Standby Output) |
| Line Regulation | ±0.5% of Nominal Voltage (Main Output) ; ±0.5% (5 V / 2 A Standby Output) |
| Load Regulation | 1% (Main Output, 0–100% or 100–0% load) ; 2% (5 V / 2 A Standby Output) |
| Transient Recovery Time & Deviation | 3% Max. Deviation with 50%–75%–50% load step ; recovers to within 1% in <500 µs (Turn-on/Turn-off overshoot: 5%) |
| Setup Time | 1.8 s typ. / 2.3 s max. (Start-up delay under all line and load conditions) |
| Rise Time | 40 ms max. (Start-up rise time) ; <40 ms Voltage Programming Slew Rate (10%–105% and 105%–10%) |
| Hold-Up Time (at 230 VAC) | 20 ms min. / 22 ms typ. (Measured at 208 VAC, 5000 W full load, 25 °C) |
| Remote Sense Compensation | Compensates up to 1% max. of nominal voltage per lead (0.48 V/lead), 2% total nominal voltage drop (0.96 V total) |
| Parallel / Current Sharing Operation | Active Single-Wire Current Sharing up to 5 Units in Parallel (Pin 23 ISHARE 0–2.6 V, ±3% full-load accuracy) with Turn-On Sync (Pin 18) |
| AC Input Voltage Range | 180 to 264 VAC, Three-Phase 3-Wire + Earth (No Neutral Required) |
| Input Frequency Range | 47 to 63 Hz |
| Efficiency | 92% min. (at 180 VAC, full load) ; 93% typ. (180 to 264 VAC, full load) |
| AC Input Current (at 230 VAC) | 18 A max. per phase (Measured at 180 VAC, 5 kW output) |
| Inrush Current (Cold Start at 230 VAC) | 60 A max. per phase (Measured at 264 VAC, 5 kW, cold start at 25 °C) |
| Power Factor (PF at 230 VAC) | 0.98 typ. (Complies with EN 61000-3-2 Class A) |
| Power Factor Correction (PFC) | Active Three-Phase PFC (Fixed 40–50 kHz switching frequency) |
| Input Fuse & Phase-Loss Protection | Internal F25A / 250V Fast-Acting Fuse fitted in each of the 3 phases ; Phase-loss shuts down output after 0.5 s with auto-recovery |
| Switching Frequency | 40 to 50 kHz (45 kHz typ. Fixed-Frequency PFC) ; 40 to 250 kHz (Variable-Frequency Main Converter) |
| Power Density | 15.38 W/in³ |
| Mounting Style | Chassis Mount (4 × M4 bottom mounting holes and 4 × M4 side mounting holes, 4.0 mm max. screw penetration) |
| Cooling Method | Forced Air Cooling via Integrated 120 × 120 mm Fan with Intelligent Fan Speed Control (Acoustic Noise: <70 dB(A) Lw) |
| Overall Width (W) | 127.0 mm (5.00 in) |
| Overall Height (H) | 127.0 mm (5.00 in) |
| Overall Depth (D) | 330.2 mm (13.00 in) chassis length (356.9 mm / 14.05 in including 26.7 mm / 1.05 in DC busbar terminal projection) |
| Mounting Hole Pitch | 212.6 × 101.6 mm (8.37 × 4.00 in) bottom pattern ; 152.4 × 76.2 mm (6.00 × 3.00 in) side pattern |
| Net Weight | 5.7 kg (12.5 lbs) |
| Termination / Connector Style | AC Input: 3 × M4 Screw Terminals (13.0 mm pitch, 10.0 mm access width) + M4 Earth Stud ; DC Output: 4 × M5 Busbar Screws ; Signals: 30-Pin JST S30B-PHDSS Header (mates with JST PHDR-30VS / SPHD-002T-P0.5) |
| Input Terminal Pinout | Rear AC Barrier Block: 3 × M4 Three-Phase Line Terminals (L1, L2, L3) + Dedicated M4 Chassis Earth Stud (GND) |
| Output & Signal Terminal Pinout | DC Busbars: 4 × M5 Screws (+V1, -V1) ; J1 30-Pin Header: Pins 1–2 DCOK/RTN, Pins 3–4 Remote Inhibit/RTN, Pins 5–7 I²C Addr A0–A2, Pins 8/10 CANH/CANL, Pins 9/11/13/15 RS485 Y/Z/A/B, Pin 12 SGND, Pins 14/16 I²C SDA/SCL, Pin 17 Fan Fail/Temp Warn, Pin 18 SYNC, Pin 19 VPROG, Pins 20–21 RS+/RS-, Pin 22 IPROG, Pin 23 ISHARE, Pin 24 PMBUS_EN, Pins 25–26 ACOK/RTN, Pins 27–30 5VSBY & 5VSBY_RTN |
| Control & Monitoring Signals | V Program (0–5 V for 0–105% Vout, ±1% accuracy), I Program (0–5 V for 0–110% Iout, ±2% accuracy), AC OK (Opto-isolated, 2 ms warning), DC OK (Opto-isolated, >95% Vnom default), Fan Fail / Temp Warning (3.3 V TTL, 10 s shutdown delay), Remote Inhibit, SYNC, Current Share (ISHARE), Remote Sense (±RS) |
| Communication Interface | I²C PMBus, CANopen, and RS485 (Full Duplex default / Half Duplex configurable) supporting MODBUS & SCPI protocols ; compatible with XP PS Manager GUI via I²C-USB host adapter |
| Status Indicator | Dual Front-Panel LEDs: AC OK LED (Green: Solid ON, Blink 0.2 s on PFC/range fault) and DC OK LED (Green: Solid ON, Blink 0.2 s in CC limit, Blink 1.0 s in Remote/PMBus OFF) |
| Terminal Tightening Torque | AC Input M4 Screws: 1.5 Nm ; M4 Earth Stud & M4 Mounting Screws: 1.6 Nm ; DC Output M5 Screws: 3.2 Nm |
| Overload Protection (OLP) Threshold | 108% ±3% of Maximum Rated Current (Programmable Current Limit 0–110% ; 5 V Standby: <5 A max.) |
| Overload Protection (OLP) Mode | Constant Current Limiting Characteristic (5 V Standby: Foldback characteristic <5 A max.) |
| Overvoltage Protection (OVP) Threshold | 120% of Nominal Output Voltage (~57.6 VDC) |
| Overvoltage Protection (OVP) Mode | Latching Shutdown (Recycle AC input power to reset) |
| Overtemperature Protection (OTP) Mode | Auto-Resetting Thermal Shutdown (Asserts Fan Fail / Temp Warning signal 10 seconds prior to output shutdown) |
| Short Circuit Protection (SCP) | Constant Current Limiting on Main 48 V Output ; Foldback Current Limiting (<5 A max.) on 5 V Standby Output |
| Withstand Isolation Voltage (I/P to O/P) | 4000 VDC (2 × MOPP per IEC 60601-1 Ed. 3.1 with M3×12 countersunk HI-POT screw removed ; 2121 VDC max. with screw installed) |
| Withstand Isolation Voltage (I/P to FG / Case) | 2500 VDC (1 × MOPP per IEC 60601-1 Ed. 3.1 with HI-POT screw removed ; 2121 VDC max. with screw installed) |
| Withstand Isolation Voltage (O/P to FG / Case) | 500 VDC |
| Earth Leakage Current | 1.0 mA typ. (Normal condition at 264 VAC / 60 Hz) ; 3.3 mA max. (Single fault condition at 264 VAC / 60 Hz) |
| Medical Isolation Rating | 2 × MOPP (Primary to Secondary) and 1 × MOPP (Primary to Earth) per IEC 60601-1 Ed. 3.1 (Class I Protection) |
| Operating Ambient Temperature Range | -20 °C to +70 °C (-4 °F to +158 °F) |
| Full-Load Operating Temperature Limit | +50 °C (+122 °F) at 100% Rated Load (5000 W) |
| High-Temperature Derating Rate | Derates linearly at 2.5% per °C (125 W/°C) above +50 °C to 50% rated power (2500 W) at +70 °C (+158 °F) |
| Altitude Derating | 5000 m (16,404 ft) Max. Operating Altitude (both Medical and ITE) ; 10,000 m (32,808 ft) Non-Operating Transport Altitude |
| Storage Temperature Range | -40 °C to +85 °C (-40 °F to +185 °F) |
| Operating Relative Humidity | 5% to 95% RH (Non-condensing) |
| Temperature Coefficient | ±0.03% / °C of Maximum Load |
| Vibration Resistance | 10 to 500 Hz at 1.5 g single-axis sweep and endurance at resonance in all 3 planes (EN 60068-2-6) ; Shock: ±3 × 30 g (11 ms half-sine, 18 shocks total per EN 60068-2-27 & EN 60068-2-47) |
| Safety Approvals (UL / North America) | UL 62368-1, CSA C22.2 No. 62368-1 (ITE) ; ANSI/AAMI ES60601-1:2005 & CSA C22.2 No. 60601-1:08 (Medical) |
| Safety Approvals (IEC / EN / TÜV) | CB Report IEC 62368-1 Ed. 2 & EN 62368-1 (ITE) ; CB Report IEC 60601-1 Ed. 3.1 (including Risk Management) & EN 60601-1:2006 (Medical) |
| Safety Approvals (Regional / Global) | CE Marked, UKCA Marked, SEMI F47-0706 (at 208 VAC nominal), Protection Class I |
| EMC Conducted & Radiated Emissions | EN 55011 / EN 55032 Class B (Conducted Emissions) ; EN 55011 / EN 55032 Class A (Radiated Emissions) |
| EMC Harmonic & Flicker Compliance | EN 61000-3-2 Class A (Harmonic Currents) |
| EMC Immunity Standards | EN 60601-1-2, EN 61000-4-2 (ESD Level 4: ±8 kV contact / ±15 kV air, Criteria A), EN 61000-4-3 (Radiated Level 3, Criteria A), EN 61000-4-4 (EFT Level 3, Criteria A), EN 61000-4-5 (Surge Installation Class 4, Criteria A), EN 61000-4-6 (Conducted RF Level 3, Criteria A), EN 61000-4-8 (Magnetic Field Level 4, Criteria A), EN 61000-4-11 (Voltage Dips & Interruptions at 200/240 VAC), SEMI F47-0706 (Criteria A) |
| MTBF (Telcordia SR-332 / Bellcore) | 450,000 Hours (450 khrs per Telcordia SR-332 at +25 °C) |
| Manufacturer Warranty | 3 Years Standard OEM Warranty |
Industrial Applications & Compatible Systems
The XP Power HPL5K0TS048 is engineered for mission-critical industrial, semiconductor, and medical platforms requiring programmable 48 VDC high-current power or constant-current control:
- Medical Diagnostic, Imaging & Laser Systems: Certified to IEC/ANSI/AAMI 60601-1 Ed. 3.1 with 2×MOPP patient isolation (4000 VDC), making it directly deployable in surgical lasers, MRI/CT subsystems, and high-power diagnostic imaging racks.
- Semiconductor Wafer Fabrication & Plasma Processing: SEMI F47-0706 voltage-sag immunity at 208 VAC and fast <40 ms programmable voltage/current slewing support semiconductor deposition chambers, ion implanters, and cleanroom automation tools.
- Automated Test Equipment (ATE) & Burn-In Racks: Full 0–50.4 VDC and 0–114.4 A programming over PMBus, CANopen, MODBUS, and SCPI enables precision automated stress testing, DC component profiling, and battery pack cyclers.
- High-Power Industrial Lasers & Electrochemistry: Parallel operation of up to 5 units (up to 25 kW / 520 A) with ±3% current sharing accuracy powers industrial fiber lasers, RF amplifiers, and precision electroplating baths.
Installation, Thermal Management & MRO Guidelines
To maximize service life and operational safety during cabinet integration and MRO replacement, observe the following engineering guidelines:
- Digital vs. Analog Mode Selection (Pin 24 PMBUS_EN): The unit defaults to digital programming when Pin 24 (PMBUS_EN) is left open. To control output voltage and current via 0–5 V analog signals on Pins 19 (VPROG) and 22 (IPROG), pull Pin 24 low to 5VSBY_RTN; note that open-circuit VPROG/IPROG pins in analog mode default the output to 0%.
- Three-Phase Protection & Torque Compliance: Size upstream three-phase circuit breakers to accommodate the 18 A/phase continuous draw and 60 A/phase cold-start inrush at 264 VAC, and torque the M4 AC input screws to 1.5 Nm, M4 earth stud to 1.6 Nm, and M5 DC output busbars to 3.2 Nm.
- Dielectric Hi-Pot Testing & Thermal Derating: Before performing dielectric strength testing above 2121 VDC, remove the M3×12 countersunk HI-POT screw on the chassis side to achieve the full 4000 VDC I/P–O/P rating, and derate load linearly by 125 W/°C when ambient air exceeds +50 °C.