Description
TDK-Lambda RWS1000B-24 (also known as RWS1000B24) is an industrial enclosed single-output AC-DC power supply from the RWS1000/1500-B Series, where the 1000B designation specifies the 1000 W-class frame and -24 identifies the 24 VDC nominal output variant (standard configuration without suffix options). Engineered for high reliability at an economical cost of ownership, it operates across a universal 85 to 265 VAC input (with 120–340 VDC capability) utilizing a 65 kHz active power factor correction stage and a 95 kHz main switching converter. The unit delivers 42 A continuous current and 1008 W rated power across a wide 20.4 to 28.8 VDC trim range, achieving 88% typical efficiency at 230 VAC (85% at 115 VAC), tight 96 mV line and 144 mV load regulation, and 180 mVp-p maximum ripple and noise.
Housed in a compact 127 × 63 × 198 mm (5.00 × 2.48 × 7.80 in) ventilated metal chassis weighing 2.00 kg (4.41 lbs), the supply features configurable screw terminal blocks for AC input and DC output alongside a JST S12B-PHDSS signal header and remote sense terminals. Comprehensive protection includes constant-current overload protection above 105% (latching shutdown after 5 seconds) plus latching overvoltage and overtemperature shutdown, backed by reinforced 4,000 VAC input-to-output galvanic isolation. Cooled by an internal fan directing airflow over the terminal end, it operates at full load from -20 °C to +50 °C (derating linearly to 60% at +60 °C) and carries global IEC/UL/CSA/EN 62368-1, EN 62477-1 Overvoltage Category III, and EN 55032 Class B emissions certifications.
Key Features
- High-Power 24 VDC Output Delivery: Supplies 42 A continuous current and 1008 W rated power with a wide 20.4 to 28.8 VDC potentiometer adjustment range and zero minimum load requirement.
- Universal Wide-Range AC Input with Active PFC: Operates from 85 to 265 VAC (47–63 Hz) with 0.98/0.95 power factor, IEC 61000-3-2 harmonic compliance, and 88% typical efficiency at 230 VAC.
- Reinforced 4,000 VAC Isolation & OVC III Rating: Provides 4,000 VAC input-to-output, 2,000 VAC input-to-ground, and 1,500 VAC output-to-ground isolation certified to IEC/UL 62368-1 and EN 62477-1 OVC III.
- Class B Conducted & Radiated EMI Compliance: Meets EN 55011, EN 55032 Class B, FCC Class B, and VCCI-B limits internally without requiring bulky external line filters.
- Comprehensive Fault Protection & Remote Sense: Integrates >105% constant-current overload limiting with 5-second prolonged overload shutdown, latching OVP/OTP, remote voltage sensing, and a green DC-OK LED.
- Compact Chassis with Configurable Terminals: Measures 127 × 63 × 198 mm with 8 M4 chassis mounting holes and reversible-orientation input/output screw terminal blocks for simplified panel wiring.
- Industrial Immunity & SEMI F47 Line-Dip Ride-Through: Complies with EN 61000-4-2 through -4-11, EN 60601-1-2 Ed. 4 voltage dips, and SEMI F47 semiconductor sag immunity above 200 VAC.
Technical Specifications
| Manufacturer | TDK-Lambda |
|---|---|
| Manufacturer Part Number (MPN) | RWS1000B-24 |
| Alternate Part Number | RWS1000B24 |
| Product Series | RWS1000/1500-B Series |
| Product Category | Chassis Power Supplies |
| Component Type | Enclosed Single-Output AC-DC Power Supply |
| Circuit Topology | Active PFC + Isolated High-Frequency Switching Converter |
| Nominal Output Voltage | 24 VDC |
| Output Voltage Adjustment Range | 20.4 to 28.8 VDC (via onboard trimmer potentiometer) |
| Rated Output Current | 42 A |
| Output Current Range | 0 to 42 A (no minimum load required) |
| Rated Output Power | 1008 W |
| Number of Outputs | 1 (Single Isolated Output) |
| Output Ripple & Noise (Max.) | 180 mVp-p |
| Line Regulation | 96 mV max. |
| Load Regulation | 144 mV max. |
| Hold-Up Time | 20 ms typ. (at 115 / 230 VAC) |
| Max. Capacitive Load | 100,000 µF |
| AC Input Voltage Range | 85 to 265 VAC (safety certified for 90 to 264 VAC) |
| DC Input Voltage Range | 120 to 340 VDC (not safety agency certified for DC input) |
| Nominal Input Voltage | 100 to 240 VAC |
| Input Frequency Range | 47 to 63 Hz (safety certified for 50 / 60 Hz) |
| Efficiency (at 115 VAC) | 85% typ. |
| Efficiency (at 230 VAC) | 88% typ. |
| AC Input Current (at 115 VAC) | 13 A typ. (at 110 VAC full load) |
| AC Input Current (at 230 VAC) | 7 A typ. (at 230 VAC full load) |
| Inrush Current (Cold Start at 115 VAC) | 60 A typ. (at 100 VAC cold start) |
| Inrush Current (Cold Start at 230 VAC) | 60 A typ. (at 200 VAC cold start) |
| Power Factor (PF at 115 VAC) | 0.98 typ. (at 100 VAC) |
| Power Factor (PF at 230 VAC) | 0.95 typ. (at 200 VAC) |
| Power Factor Correction (PFC) | Active PFC (65 kHz switching stage) |
| Switching Frequency | 95 kHz (Main Converter) / 65 kHz (PFC Stage) |
| Mounting Style | Chassis Mount (8 × M4 bottom/side countersunk mounting holes, 5 mm max. screw penetration) |
| Cooling Method | Internal Forced-Air Fan Cooling (standard airflow enters over input/output terminals) |
| Overall Width (W) | 127 mm (5.00 in) |
| Overall Height (H) | 63 mm (2.48 in) |
| Overall Depth (D) | 198 mm (7.80 in) |
| Dimensional Tolerance | ±1.0 mm (±0.04 in) |
| Net Weight | 2.00 kg / 2,000 g (4.41 lbs / 70.55 oz) |
| Termination / Connector Style | Configurable Screw Terminal Blocks (AC Input & DC Output) + JST S12B-PHDSS Signal Header |
| Control & Monitoring Signals | Remote Sense (+S / -S); Series Operation Supported (Remote On/Off, Power Fail & Parallel available on /R, /FO, /RFO options) |
| Status Indicator | Green LED (DC Output OK) |
| Overload Protection (OLP) Threshold | >105% of rated output current |
| Overload Protection (OLP) Mode | Constant current limiting with automatic recovery; prolonged overload >5 s triggers latching shutdown |
| Overvoltage Protection (OVP) Mode | Latching shutdown (cycle AC input power to reset) |
| Overtemperature Protection (OTP) Mode | Latching shutdown (cycle AC input power to reset) |
| Withstand Isolation Voltage (I/P to O/P) | 4,000 VAC (1 minute) |
| Withstand Isolation Voltage (I/P to FG / Case) | 2,000 VAC (1 minute) |
| Withstand Isolation Voltage (O/P to FG / Case) | 1,500 VAC (1 minute) |
| Earth Leakage Current | < 1.2 mA |
| Operating Ambient Temperature Range | -20 °C to +60 °C (-4 °F to +140 °F) |
| Full-Load Operating Temperature Limit | +50 °C (+122 °F) at 100% rated load |
| High-Temperature Derating Rate | Linear derating from 100% load at +50 °C (+122 °F) down to 60% load at +60 °C (+140 °F) |
| Low-Line Input Derating | Linear derating from 100% load at 90 VAC down to 80% load at 85 VAC |
| Storage Temperature Range | -30 °C to +75 °C (-22 °F to +167 °F) |
| Operating Relative Humidity | 20% to 90% RH (non-condensing) |
| Storage Relative Humidity | 10% to 90% RH (non-condensing) |
| Temperature Coefficient | ±0.02% / °C |
| Vibration Resistance | 10 to 55 Hz (1 min sweep), 19.6 m/s² (2 G) constant along X, Y, Z axes for 1 hour each (non-operating) |
| Safety Approvals (UL / North America) | UL 62368-1, CSA C22.2 No. 62368-1, UL 60950-1 |
| Safety Approvals (IEC / EN / TÜV) | IEC 62368-1, EN 62368-1, IEC/EN 60950-1, EN 62477-1 (Overvoltage Category III) |
| Safety Approvals (Regional / Global) | CE Mark, UKCA Mark |
| EMC Conducted & Radiated Emissions | EN 55011 Class B, EN 55032 Class B, FCC Part 15 Class B, VCCI Class B |
| EMC Harmonic & Flicker Compliance | IEC 61000-3-2 |
| EMC Immunity Standards | EN 61000-4-2 (ESD ±8 kV air / ±4 kV contact), EN 61000-4-3 (Radiated 10 V/m 80M–1GHz), EN 61000-4-4 (EFT ±2 kV), EN 61000-4-5 (Surge ±2 kV normal / ±4 kV common), EN 61000-4-6 (Conducted 10 Vrms), EN 61000-4-8 (Magnetic 30 A/m), EN 61000-4-11 & EN 60601-1-2 Ed. 4 (Voltage Dips), SEMI F47 (>200 VAC) |
| MTBF (Telcordia SR-332 / Bellcore) | 1,222,361 hours (Telcordia SR-332 Issue 3, RWS1500B-24 reference at 25 °C ambient, full load) |
| Environmental Compliance | RoHS Compliant |
Industrial Applications & Compatible Systems
TDK-Lambda RWS1000B-24 delivers 1008 W of regulated 24 VDC bulk power for high-current industrial automation, factory machinery, and semiconductor capital equipment:
- Industrial Automation & Control Cabinets: Powers high-density 24 VDC PLC racks, distributed I/O manifolds, industrial safety relays, and 24 V solenoid valve banks with EN 62477-1 OVC III compliance.
- Semiconductor Fabrication & Wafer Handling: Supports wafer steppers, wet benches, and automated material handling systems requiring SEMI F47 line-dip ride-through above 200 VAC.
- Automated Test Equipment (ATE) & Burn-In Racks: Supplies low-ripple, tightly regulated 24 VDC bus power for production test fixtures, RF test beds, and electronic load racks.
- Robotics, AGVs & Material Handling Systems: Drives 24 VDC auxiliary actuator buses, servo brake coils, machine vision lighting arrays, and automated guided vehicle charging docks.
Installation, Thermal Management & MRO Guidelines
Follow these mechanical, thermal, and electrical integration practices to ensure full-load reliability and long electrolytic capacitor service life:
- Chassis Mounting Screw Depth Limit: Secure the enclosure using the 8 M4 mounting holes on the bottom or side faces while strictly limiting screw penetration depth to 5 mm maximum to avoid contacting internal high-voltage circuitry.
- Airflow Clearance & High-Ambient Derating: Maintain unobstructed intake clearance over the input/output terminal end and exhaust clearance at the rear fan grille, and derate output load linearly from 100% at +50 °C down to 60% (604.8 W) at +60 °C.
- Low-Line & Inrush Breaker Sizing: Derate maximum load linearly to 80% when operating between 85 and 90 VAC, and protect the AC feed with a C-curve or D-curve miniature circuit breaker rated to withstand the 60 A cold-start inrush pulse.
- Remote Sense & Terminal Orientation: Connect the +S and -S sense lines via twisted-pair wiring directly to the load distribution bus to compensate for high-current cable drop, and flip the output terminal block orientation if vertical cable entry simplifies cabinet routing.