Description
Omron S8VK-G03012-400 (also known as S8VKG03012400) is an industrial single-phase switch-mode DIN rail power supply from the compact S8VK-G series, where the MPN nomenclature denotes a single-phase input (G), 30 W rated power (030), 12 VDC output (12), and factory-applied conformal PCB coating (-400) for enhanced resistance to humidity and airborne contaminants. Accepting a universal 85 to 264 VAC (47 to 450 Hz), two-phase AC, or 90 to 350 VDC input, it delivers a tightly regulated 12 VDC at 2.5 A continuous current with a 120% Power Boost function (3.0 A / 36 W for up to 10 seconds) to handle transient inductive inrush loads. The unit achieves 82% typical efficiency (at 230 VAC) while maintaining ultra-low output ripple and noise below 30 mVp-p (at 20 MHz bandwidth), 0.4% maximum line regulation, and 0.8% maximum load regulation.
Housed in a space-saving IP20 fanless enclosure measuring 32 mm × 90 mm × 90 mm (1.26 in × 3.54 in × 3.54 in) and weighing 195 g (6.88 oz) max, the power supply snaps effortlessly onto standard TS-35 DIN rails using Omron’s one-hand sliding rail stopper. Front screw terminals provide dedicated connections for L, N, and PE inputs alongside dual +V and -V output terminals, a green DC ON LED indicator, and a front-panel V.ADJ potentiometer (-10% to +15% / 10.8 to 13.8 VDC). Engineered for extreme environments from -40 °C to +70 °C (-40 °F to +158 °F) with full rated load up to +55 °C (+131 °F), it integrates automatic-recovery intermittent overload protection (>121%), latching overvoltage protection (≥130%), 3.0 kVAC input-to-output galvanic isolation, and full compliance with UL 508 Listed, UL 1310 Class 2, UL/EN 62368-1, SEMI F47-0706, Lloyd’s Register, and EN 61204-3 Class B.
Key Features
- Conformal Coated 30W Output with 120% Power Boost: Delivers 12 VDC at 2.5 A continuous current (30 W) and 3.0 A boost current (36 W for up to 10 s at ≤30% duty cycle) with protective -400 PCB coating.
- Universal AC, Two-Phase & High-Voltage DC Input: Operates across 85 to 264 VAC (47 to 450 Hz), 2-phase 200 to 240 VAC networks, and 90 to 350 VDC backup buses with 82% typical efficiency.
- Low-Noise Regulation & Wide Voltage Trim: Holds output ripple and noise within 30 mVp-p max (20 MHz bandwidth) with 0.4% line regulation, 0.8% load regulation, and -10% to +15% (10.8–13.8 VDC) V.ADJ adjustment.
- Wide -40°C to +70°C Ambient Operating Range: Guarantees cold start at -40 °C (-40 °F) and 100% continuous load up to +55 °C (+131 °F) in standard vertical DIN rail mounting via natural convection.
- Comprehensive Overload & Overvoltage Protection: Features intermittent current limiting above 121% rated load with automatic recovery, plus latching overvoltage shutdown at ≥130% rated voltage and an internal 250 VAC 4.0 A HBC fuse.
- Ultra-Compact 32mm DIN Rail Footprint: Measures 32 mm (W) × 90 mm (H) × 90 mm (D) (1.26 × 3.54 × 3.54 in) and supports series operation and parallel/redundant pairing via S8VK-R redundancy modules.
- 3.0 kVAC Reinforced Isolation & Global Approvals: Certified to UL 508 Listed, UL 1310 Class 2 Output, UL/EN 62368-1, EN 50178, EN 60204-1 PELV, Lloyd’s Register Marine, SEMI F47-0706, and EN 55011 Class B.
Technical Specifications
| Manufacturer | Omron |
|---|---|
| Manufacturer Part Number (MPN) | S8VK-G03012-400 |
| Alternate Part Number | S8VKG03012400 |
| Compatible Equipment / Series | Omron S8V-CP Electronic Circuit Protectors, S8VK-R Redundancy Modules, S8V-NF Noise Filters, PFP-100N/50N DIN Rails, S82Y-VS10F/VS10S Mounting Brackets |
| Product Series | S8VK-G Series (Conformal Coated -400 Variant) |
| Product Category | Single-Phase DIN Rail |
| Component Type | Industrial AC-DC DIN Rail Switch-Mode Power Supply |
| Circuit Topology | Isolated Switch-Mode Power Supply (SMPS) with Photocoupler Feedback |
| Nominal Output Voltage | 12 VDC |
| Output Voltage Adjustment Range | 10.8 to 13.8 VDC (-10% to +15% guaranteed via front V.ADJ potentiometer) |
| Rated Output Current | 2.5 A |
| Output Current Range | 0 to 2.5 A continuous (up to 3.0 A in Power Boost mode) |
| Peak / Surge Output Current | 3.0 A (120% Power Boost for ≤ 10 s max, ≤ 30% duty cycle, average current ≤ 2.5 A) |
| Rated Output Power | 30 W |
| Peak Output Power | 36 W (120% Power Boost for up to 10 s) |
| Number of Outputs | 1 Output (Dual +V and Dual -V internally bussed terminal points) |
| Output Ripple & Noise (Max.) | 30 mVp-p max. (at 20 MHz bandwidth, 100 to 240 VAC input, 100% load, -25 to +70 °C) |
| Line Regulation | 0.4% max. (Input variation influence across 85 to 264 VAC at rated load) |
| Load Regulation | 0.8% max. (Load variation influence from 0 A to 2.5 A at 100 to 240 VAC) |
| Setup Time (at 115 VAC) | 550 ms typ. (Start-up time for cold start at 25 °C, rated output) |
| Setup Time (at 230 VAC) | 490 ms typ. (Start-up time for cold start at 25 °C, rated output) |
| Hold-Up Time (at 115 VAC) | 36 ms typ. (at 115 VAC input, 100% rated load) |
| Hold-Up Time (at 230 VAC) | 170 ms typ. (at 230 VAC input, 100% rated load) |
| AC Input Voltage Range | 85 to 264 VAC (Single-phase or 2-phase input up to 240 VAC +10%) |
| DC Input Voltage Range | 90 to 350 VDC (Requires external DC fuse rated 350 VDC min., 4 A; connect + to L terminal) |
| Nominal Input Voltage | 100 to 240 VAC |
| Input Frequency Range | 47 to 450 Hz (50 / 60 Hz nominal) |
| Efficiency (at 230 VAC) | 82% typ. (at 230 VAC input, 100% rated load) |
| AC Input Current (at 115 VAC) | 0.57 A typ. (at 100% rated load) |
| AC Input Current (at 230 VAC) | 0.37 A typ. (at 100% rated load) |
| Inrush Current (Cold Start at 115 VAC) | 16 A typ. (at 25 °C cold start) |
| Inrush Current (Cold Start at 230 VAC) | 32 A typ. (at 25 °C cold start) |
| Power Factor (PF at 230 VAC) | 0.43 min. (at 230 VAC input, 100% load) |
| Mounting Style | DIN Rail TS-35 (PFP-100N / PFP-50N / PFP-100N2); Optional Front/Side Screw Mounting via S82Y-VS10F or S82Y-VS10S Brackets |
| Cooling Method | Natural Air Convection (Fanless) |
| Overall Width (W) | 32 mm (1.26 in) |
| Overall Height (H) | 90 mm (3.54 in) |
| Overall Depth (D) | 90 mm (3.54 in) [excluding 4.7 mm rail stopper projection and 1 mm front cover] |
| Dimensional Tolerance | ±1 mm (±0.039 in) on outer W × H × D dimensions |
| Net Weight | 195 g (0.43 lbs / 6.88 oz) max. |
| Termination / Connector Style | IP20 Finger-Safe Screw Terminal Blocks with Hinged Terminal Cover (7.62 mm pitch; 2.9 × 2.7 mm wire insertion hole for #1 driver) |
| Input Terminal Pinout | Bottom Terminal Block: AC(L) [Positive for DC Input, Internal 250 VAC 4.0 A HBC Fuse], AC(N), PE (Protective Earth) |
| Output & Signal Terminal Pinout | Top Terminal Block: Dual -V (DC Negative Output), Dual +V (DC Positive Output) |
| Status Indicator | Green LED (DC ON: Lights solidly at 80% to 90% or more of rated output voltage; flashes during overload protection) |
| Terminal Wire Gauge Range | Input: AWG 24 to 12 (0.25 to 4 mm² solid / 0.25 to 2.5 mm² stranded); Output: AWG 20 to 12 (0.5 to 4 mm² solid / 0.5 to 2.5 mm² stranded); PE: AWG 14 to 12 (2.5 to 4 mm²); Strip length: 8 to 10 mm |
| Terminal Tightening Torque | 0.5 to 0.6 N·m (4.43 to 5.31 lb-in); max. terminal block force 75 N |
| Enclosure / Potting Material | Vented Industrial Enclosure with Conformal Coated Internal PCB (-400 Option) |
| Overload Protection (OLP) Threshold | > 121% of rated output current (above 3.03 A) |
| Overload Protection (OLP) Mode | Intermittent Operation (Hiccup Mode) with Automatic Reset upon fault removal |
| Overvoltage Protection (OVP) Threshold | ≥ 130% of rated output voltage (approx. 15.6 VDC) |
| Overvoltage Protection (OVP) Mode | Output Shut-Off Latching Mode (Turn off AC input for at least 3 minutes, then re-apply power to reset) |
| Short Circuit Protection (SCP) | Protected via Intermittent Overload Protection with Automatic Recovery |
| Withstand Isolation Voltage (I/P to O/P) | 3.0 kVAC for 1 min. (20 mA cutoff current) |
| Withstand Isolation Voltage (I/P to FG / Case) | 2.0 kVAC for 1 min. (20 mA cutoff current) |
| Withstand Isolation Voltage (O/P to FG / Case) | 1.0 kVAC for 1 min. (20 mA cutoff current) |
| Isolation Resistance (at 500 VDC) | 100 MΩ min. (between all output terminals and all input/PE terminals at 500 VDC) |
| Earth Leakage Current | 0.13 mA typ. at 115 VAC / 0.24 mA typ. at 230 VAC |
| Operating Ambient Temperature Range | -40 °C to +70 °C (-40 °F to +158 °F) with no condensation or icing |
| Full-Load Operating Temperature Limit | +55 °C (+131 °F) in Standard Vertical Mounting; +40 °C (+104 °F) in Face-Up Mounting |
| High-Temperature Derating Rate | Standard Vertical Mounting: Derate linearly at 2.5%/°C from +55 °C to +70 °C (62.5% load at +70 °C); Face-Up Mounting: Derate linearly from 100% at +40 °C to 20% at +70 °C; DC Input: Multiply load curve by 0.9 |
| Low-Line Input Derating | Derate load at 2.5%/V below 90 VAC input (down to 85 VAC) |
| Storage Temperature Range | -40 °C to +85 °C (-40 °F to +185 °F) with no condensation or icing |
| Operating Relative Humidity | 0% to 95% RH (non-condensing) |
| Storage Relative Humidity | 0% to 95% RH (non-condensing) |
| Temperature Coefficient | 0.05%/°C max. (115 to 230 VAC input) |
| Vibration Resistance | 10 to 55 Hz, 0.375 mm half-amplitude for 2 hours each in X, Y, and Z directions; Shock: 150 m/s² (3 times each in ±X, ±Y, ±Z) |
| Ingress Protection (IP) | IP20 (per EN/IEC 60529) with Conformal PCB Coating (-400) |
| Safety Approvals (UL / North America) | UL 508 Listed (Class 2 Output per UL 1310), UL 62368-1 Recognized (UR), cUL CSA C22.2 No. 107.1 (Class 2 Output per CSA C22.2 No. 223), cUR CSA C22.2 No. 62368-1 |
| Safety Approvals (IEC / EN / TÜV) | EN/VDE 50178, EN 62368-1, EN 60204-1 PELV, EN 61558-2-16 (Safety of Power Transformers) |
| Safety Approvals (Regional / Global) | CE, EAC (TR CU 004/2011, TR CU 020/2011), RCM (EN 61000-6-4), Lloyd’s Register Marine Standard, SEMI F47-0706 (200 to 240 VAC) |
| EMC Conducted & Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B (Conducted and Radiated Emissions) |
| EMC Harmonic & Flicker Compliance | Conforms to EN 61000-3-2 (Harmonic Current Emissions) |
| EMC Immunity Standards | Conforms to EN 61204-3 High Severity Levels and SEMI F47-0706 Voltage Sag Immunity (at 200 to 240 VAC) |
| MTBF (MIL-HDBK-217F) | 580,000 hours reference value (135,000 hours min.); 10-year min. service life expectancy (at 40 °C, 50% load); 5-year factory warranty |
| Environmental Compliance | RoHS Compliant, Conformal Coated PCB (-400) |
Industrial Applications & Compatible Systems
The Omron S8VK-G03012-400 is built for space-constrained industrial control cabinets and harsh environments requiring a conformal-coated, UL Class 2 limited-power 12 VDC source:
- PLC, Remote I/O & Industrial Sensor Networks: Powers 12 VDC proximity switches, photoelectric sensors, rotary encoders, and compact programmable logic controllers where UL 1310 Class 2 compliance eliminates downstream branch circuit fusing.
- Humid, Coastal & Marine Control Panels: Combines factory conformal coating (-400 suffix) with Lloyd’s Register certification (when paired with Schaffner FN2080-10-06 input filter and TDK ZCAT2035-0930 clamp core) for shipboard and high-humidity plant automation.
- Semiconductor Fabrication & Vision Inspection Tools: Meets SEMI F47-0706 voltage sag ride-through at 200–240 VAC and delivers ultra-clean <30 mVp-p ripple to sensitive 12 VDC machine vision cameras, barcode readers, and optical gauges.
- Solenoid Valves, Relays & Inductive Actuators: Leverages 120% Power Boost (3.0 A for up to 10 seconds) to reliably energize 12 VDC pneumatic solenoid manifolds, electromechanical contactors, and motorized dampers without nuisance voltage dips.
Installation, Thermal Management & MRO Guidelines
Follow these engineering and installation best practices to maximize service life and operational reliability:
- DIN Rail Clearance & Thermal Derating: Mount vertically on a standard TS-35 rail with at least 20 mm (0.79 in) top/bottom convection clearance; maintain 100% load up to +55 °C (+131 °F) and derate linearly at 2.5%/°C from +55 °C to +70 °C (multiply load rating by 0.9 when operating from a 90–350 VDC bus).
- Two-Phase & High-Voltage DC Input Protection: Because the internal 250 VAC 4.0 A HBC fuse is located exclusively on the AC(L) line, always install an external fuse or circuit breaker on the AC(N) line for 2-phase (200–240 VAC) operation, or a 350 VDC min. 4 A external fuse when supplying 90–350 VDC.
- Series, Parallel & Redundant Wiring Rules: Up to two units can be wired in series (with external Schottky barrier diodes rated ≥2× Vout and ≥2× Iout) or in parallel between -25 °C and +40 °C (trim V.ADJ within 50 mV and pair with an Omron S8VK-R redundancy module for N+1 backup).